background image

11

SPECTRA COMMERCIAL AND RESIDENTIAL INSTALLATION GUIDE

Water Tank Refill

Steps:
1)

Close water heater drain valve.

2)

Open cold water supply to tank.

3)

Open hot water faucet in house to bleed air from system then close when full.

4)

Depress handle on pressure relief valve to bleed any remaining air from tank, then

close.

5)

If so equipped, unscrew indicator plug on motor end of pump (note commercial units

pump exterior) until all air is purged from pump. Tighten plug. Use vent couplings to

bleed air from lines.

6)

Carefully inspect all plumbing for water leaks. Correct as required.

7)

Before restoring electrical or fuel supply at water heater, adjust temperature setting

on tank.

• On tanks with both upper and lower elements, the lower element should be turned

down to the lowest setting, approximately 100

°

F. The upper element should be

adjusted to 130

°

F. Depending upon the specific needs of the customer, you may

want to adjust the upper element differently.

• On tanks with a single element, lower the thermostat setting to 120

°

F.

8)

After thermostat adjustments are completed, replace access cover and restore

electrical or fuel supply to water heater.

Steps:
1)

Make sure any valves in desuperheater water circulating circuit are open. Never

operate the DHW circulating pump dry.

2)

Turn on Spectra unit to first stage heat.

3)

DHW pump should be running. Be sure DHW pump disable switch (SW1 #2) is ON

(refers to commercial microprocessor only).

4)

The temperature difference between water entering and leaving the desuperheater

should be 5

°

 to 15

°

F. The water flow should be approximately 0.4 gpm per ton of

nominal cooling.

5)

Allow unit to heat water 15 to 20 minutes to be sure operation is normal.

6)

When the pump is first started, allow the pump to run for at least 5 minutes to insure

water has filled the circulator properly.

Desuperheater Note:

When servicing a unit’s refrigeration circuit, it is always good practice to disable the

desuperheater pump. This can be accomplished by using the DHW pump disable switch

(SW1 #2), on the commercial microprocessor with an electronic unit, remove the orange

wire lead from the "A" terminal on the power strip. Do not run DHW pump dry. If the unit is

placed in operation before the desuperheater piping is connected, be sure the pump switch

is set to the "OFF" position.

General

Be sure the available power is the same voltage and phase as that shown on the unit

serial plate. Line and low voltage wiring must be done in accordance with local codes or the

National Electric Code, whichever is applicable.

Unit Power Connection

Line voltage connection is made by connecting the incoming line voltage wires to the “L”

side of the contactor as shown in Figure 12 on page 12. Consult the UNIT ELECTRICAL

DATA on page 13 for correct fuse size.

Initial
Desuperheater
Start Up

Electrical
Connections

Summary of Contents for SPECTRA SX Series

Page 1: ...s for shipping damage removing the units from the cartons if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the d...

Page 2: ...side or end discharge and may be field converted from one to the other by replacing the discharge panel The new panel must be ordered Horizontal units are normally suspended from a ceiling by four 3...

Page 3: ...ase isolated from the ceiling joists by additional layers of vibration absorbing mesh Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a d...

Page 4: ...connector has a rubber gasket seal similar to a garden hose gasket which when mated to the flush end of any 1 threaded pipe provides a leak free seal without the need for thread sealing tape or compo...

Page 5: ...nsate drain assembly consists of a drain tube which is connected to the drain pan a 3 4 PVC female adapter and a flexible connecting hose The female adapter may exit either the front or the side of th...

Page 6: ...e brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished Cleaning and Flushing Prior to start up of any heat pump the water circulating...

Page 7: ...t up Obtain these forms from your commercial representative or contact WaterFurnace Ground Source Systems Once piping is completed between the unit flow center and the ground loop Figure 7 on page 8 f...

Page 8: ...be disposed of in various ways depending on local building codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Co...

Page 9: ...r faucet 5 Flush the tank by opening the cold water inlet valve to water heater to free the tank of sediments Close when draining water is clear 6 Disconnect the garden hose and remove the drain valve...

Page 10: ...faces of both connecting water lines with 3 8 wall closed cell insulation Figure 9 Water Heater Connection Kit Cold Drain Valve Coaxial Drain Tee In Out P T Relief Valve Long Elbow Venting Waste Valve...

Page 11: ...age heat 3 DHW pump should be running Be sure DHW pump disable switch SW1 2 is ON refers to commercial microprocessor only 4 The temperature difference between water entering and leaving the desuperhe...

Page 12: ...al strip PS and contactor CC Figure 12 Spectra SX Line Voltage Blower Relay Compressor Control Module Transformer Compressor Contactor Ground Lug Typical Electromechanical Control Box Configuration Te...

Page 13: ...0 60 28 3 34 2 50 50 208 230 60 3 197 254 21 0 13 5 99 0 4 6 18 1 21 4 30 30 460 60 3 414 506 11 5 7 4 49 0 2 3 9 7 11 5 15 15 575 60 3 518 633 9 0 5 8 40 0 2 3 8 1 9 5 15 15 SX068 208 230 60 1 197 25...

Page 14: ...3 Air flow Settings 4 L2 Orange Factory low voltage wiring Legend Switch High pressure Switch Low pressure Relay coil Temperature Limit Switch Field wire lug Ground Relay Contacts N O N C Polarized c...

Page 15: ...pressure Polarized connector Condensate Overflow Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Optional block Internal junction Quick conne...

Page 16: ...M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L 590 570 560 550 545 540 530 520 510 500 H 790 780 775 770 765 760 740 720 690 670 610 SX019 M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L...

Page 17: ...ble 3 6 Check the temperature of both the supply and discharge water Refer to Start Up Performance Table 2 7 Check for an air temperature drop of 15 to 25 F across the air coil depending on the fan sp...

Page 18: ...tem to desired normal operating mode and set temperature to maintain desired comfort level 20 Instruct the owner operator of the proper operation of the thermostat and system maintenance NOTE If perfo...

Page 19: ...t mode Check thermostat and field control wiring If steps above show that the unit control board is not indicating proper results i e LED indication replace board If LEDs are indicating properly repla...

Page 20: ...without notice WaterFurnace is a registered trademark and Spectra is a trademark of WaterFurnace International Inc 1999 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 P...

Reviews: