NATURALFLOW SERIES NF1500 

System Specification & Installation Instructions 

 

 

If in doubt contact the experts on 0800 628 356 or [email protected] 

 

New Zealand’s Leaders in Eco-Sustainable, Odourless Wastewater and Sewage Systems 

 

Wormorator® & Dose Chamber Specifications 

Tanks  are  made  of  Cotene  9050  which  is  a  linear  medium  density  polyethylene,  designed  specifically  for 
rotational molding of large tanks and products that require a high level of rigidity. It contains a fully formulated 
long  term  UV  stabilization  package  (with  a  minimum  UV8  rating)  and  is  suitable  material  for  wastewater 
treatment  containment  meeting  all  the  requirements  of  Section  4.3.3  of  AS/NZS  1547:2012  which  cross 
references the structural performance requirements of its section 2.4.2.3 back to the relevant provisions of 
AS/NZS  1546.1,  which  for  plastic  septic  tanks  constructed  via  by  rotational  molding  using  thermoplastics 
(polyethylene) are set out in Section 9 of that Standard. These tanks have an expected lifespan of 50 years.

SXL5000 Wormorator® Module 
1000ltrs Nominal capacity  
1200mm Diameter 
1400 mm O/A height  
 

Dose Chamber  
1500ltrs Nominal capacity  
1200mm Diameter over main body  
732mm Riser Diameter 
2125mm O/A height

Installation Location and Certification 

These tanks are not designed for vehicle loads and shall be located no closer than 1.50m to a driveway, road 
frontage or a building. If for any reason the tank is located where vehicle traffic may drive over the tank or 
approach closer than 1.50m, or where it may be trampled on by farm stock then the tank should be protected 
by a concrete slab designed to support these loads. Surface water must also be diverted from flowing into the 
installation. 

Installation must  be  certified  to  AS/NZS  1547:2012,  the  certificate to  be  issued  and  held  by  the  regulatory 
authority. 

High Water Table Installations 

All tanks have been engineered and designed with support ribbing for maximum strength, in accordance with 
the NZC 3604. Clauses B1 and B2 for structure and durability, to withstand any hydraulic pressures, both lateral 
and uplift, created by high water table conditions, even when the tanks are completely empty at install stage. 

As per the NaturalFlow Systems installation instructions, in these conditions, tanks must be anchored in with 
concrete around base, as per the installation instructions, to height as specified. 

Plumbing Pipes and Fittings 

All  internal  plumbing  is  done  with  PVC  pipes  with  appropriate  connections  according  to  AS/NZS  1260  and 
AS/NZS 4130.  

Backfill and Bedding 

Place and bed to NZBC G13/AS2, using compacted granular metal, in layers not exceeding 100mm. 

 

Summary of Contents for Naturalflow Series

Page 1: ...NaturalFlow Series NF1500 Treatment System System Specifications Installation Instructions...

Page 2: ...size in the TSS to less than 1mm This secondary treatment tray acts as an in built outlet filter AS NZS 1546 1 2008 Clause D3 3 and has a minimum life expectancy of 15 years It then trickle flows int...

Page 3: ...nstallation Location and Certification These tanks are not designed for vehicle loads and shall be located no closer than 1 50m to a driveway road frontage or a building If for any reason the tank is...

Page 4: ...be faulty with the same or equivalent part at no charge 5 Warranty of operation covers the performance of the NaturalFlow systems as connected to the effluent inflow for which they are designed and a...

Page 5: ...the UNISEAL and carefully connect Wormorator and Dose Chamber with DWV50 fitted to Wormorator see UNISEAL instructions appendix B N B pipe to protrude 50mm through UNISEAL 7 Where possible excavate a...

Page 6: ...ubrication to the UNISEAL and carefully connect Wormorator and Dose Chamber with DWV50 fitted to Wormorator see UNISEAL instructions appendix B N B pipe to protrude 50mm through UNISEAL 7 Where possib...

Page 7: ...ve water in tanks for at least 12 hours after installation is completed and then pump out to allow Wormorator to dry out Appendix B Instructions for fitting UNISEAL 1 Cut hole to the Hole saw size ind...

Page 8: ...e Grey Water from House Black Water from House Advanced Primary 1260 1260 2100 0 1560 540 To Disposal Field as per AS NZ 1547 2012 or relevant Local Authority requirements Matrix Filter 750mm Dia Lid...

Page 9: ...431 0042 E sales waterflow co nz South Island Office NaturalFlow South Ltd 82 Johns Road Belfast Christchurch 8051 P 03 323 8541 E sales naturalflowsouth co nz www naturalflow co nz We do it simpler...

Page 10: ...Home Owner Care Guide We do it simpler by Waterflow NZ Ltd...

Page 11: ...d y n a t u r e Love nature Stay c l o s e t o n a t u r e It will never fail yo u Contents To The Home Owner 3 4 5 8 9 10 11 Waterflow NZ Ltd Warranty Caring For Your Wastewater And Sewage System In...

Page 12: ...cesses We would encourage you to monitor and care for your NaturalFlow system yourself with our backing and support and by doing so you will learn how your system works and operates and how to keep it...

Page 13: ...connected to the effluent inflow for which they are designed and has been installed to the criteria as set out in the relative installation instructions and procedures and has an assigned Service Mai...

Page 14: ...orator build up Six monthly level should be no higher than 200mm below inlet pipe simple observation through lid adequate 2 Field performance particularly looking for any undue odours or effluent brea...

Page 15: ...old water use Do you know how many litres of water your toilet uses to flush Most older homes have toilets with 11 litre reservoirs while newer high efficiency dual flush toilets use 6 3 5 5ltrs or do...

Page 16: ...contaminate surface or ground waters Care for your Land Application System Your land appliaction system is an important part of your wastewater system Here are a few things you should do to maintain...

Page 17: ...ed regularly to optimize growth and prevent the grass from becoming rank Use signs fences and or plantings to prevent any vehicle or stock access Keep records of all maintenance undertaken on the wast...

Page 18: ...bactericides destroying the essential micro organisms required to achieve the high level of biodegradation in the treatment and disposal systems The following matters need to be considered when using...

Page 19: ...le cleaners and those low in chlorine levels Ammonia Based Cleaners Instead sprinkle baking soda on a damp sponge For windows use a solution of 2 Tbs white vinegar to 1 litre of water Place the mixtur...

Page 20: ...arex dissita Carex maorica Carex secta Carex tenuiculmis Carex virgata Cordyline australis Cabbage Tree Cordyline Midnight Star Leptospermum Burgundy Queen Flowering Ti Tree Lomandra Tanika Phomium Su...

Page 21: ...State Highway 12 Maungaturoto 0547 New Zealand P 09 431 0042 E sales waterflow co nz South Island Office NaturalFlow South Ltd 82 Johns Road Belfast Christchurch 8051 P 03 323 8541 E sales naturalflo...

Reviews: