Code

Problem - Action / Remedy

LP, LP3

Problem: 

Low refrigerant level in the pool heat pump or the low-

pressure safety control is defective.

Atmospheric conditions as well as the pool water temperature 

should not be below the minimum operating temperatures as stated 

below in order to obtain efficiency and avoid codes from appearing 

on the electronic control temperature display ; these codes are not 

generally a problem with the pool heat pump at these conditions 

and is not covered by the warranty.

If temperatures are below the minimum temperatures listed below 

the pool heat pump should not be operated and must be switched 

off.

Model

Atmospheric 

conditions

must be above

Pool water 

temperature

must be above

Electroheat Ultra

32°F (0°C)

50°F (10°C)

Reversible (XLR)

43°F (6°C) 

65°F (18°C)

All others

52°F (11°C) 

65°F (18°C)  

Action / Remedy:

- If the LP or LP3 code is shown permanently, press “SET” or “ON/

OFF” depending of the model you have before to get to next step;

- Ensure the evaporator is clean. If not switch the unit OFF from

the circuit breaker (fuse) and use a garden hose to lightly clean

the evaporator, then allow it to dry before re-starting the pool heat

pump to avoid premature ice build up on the evaporator.

- Ensure installation instructions have been followed. Improper

installation, e.g. no air circulation could lead to the pool heat pump

continually going into LP or LP3 mode and the installation will 

need to be corrected by the owner.

HP, HP3

Problem: 

Low water circulation in the unit or the high-pressure 

control is defective. If the HP code is triggered and displayed 

3 times; this will cause the pool heat pump to shut down 

automatically. The HP3 code will then appear permanently 

(except for reversible electronic control with diagnostics).

Note: The pool pump will stop functioning only if the internal 

time delay of the pool heat pump is being used.

IMPORTANT: 

When the code HP3 is permanently displayed, 

before performing the steps below, please press the ¨SET¨ button 

for the electronic control Multi Function and ¨ON / OFF¨  for the 

electronic control with diagnostics and  the reversible electronic 

control with diagnostics (XLR) and electronic control with 

diagnostics.

I pg 32

Pool Heat Pump

Code

Problem - Action / Remedy

FS, DEF, FS4

Problem:

 Normal defrost cycle. The fan blades are turning, but 

the compressor has stopped. For Electroheat Ultra and Reversible 

model, the fan blades do not turn but the compressor runs.

Action / Remedy:

 Normal during defrost duration.

Atmospheric conditions as well as the pool water temperature 

should not be below the minimum operating temperatures as 

stated below in order to obtain efficiency and avoid codes from 

appearing on the electronic control temperature display ; these 

codes are not generally a problem with the pool heat pump at 

these conditions and is not covered under warranty.

If temperatures are below the minimum temperatures the pool heat 

pump should not be operated and must be switched off.

For Electroheat and Reversible (XLR) units, they will automatically 

stop without human intervention.

Model

Atmospheric 

conditions

must be above

Pool water 

temperature

must be above

Electroheat Ultra

32°F (0°C)

50°F (10°C)

Reversible (XLR)

43°F (6°C) 

65°F (18°C)

All others

52°F (11°C) 

65°F (18°C)  

For Electroheat model: If the unit carries out 5 consecutives defrost 

cycles  every 15 minutes or less, the pool heat pump is then put into 

protection mode (FS4). During this mode, the fan blade turns for 

30 minutes in order to cool the evaporator. The pool heat pump 

restarts automatically when the external temperature is at:  34˚F 

(1˚C).

For Reversible (XLR) Model: If the unit performs 4 consecutive 

cycles (heating and defrost) within 1-hour, the unit goes into 

protection mode and alternately displays the water temperature 

and the DEF code. The fan motor runs for 30 minutes to cool the 

evaporator and then stops. The compressor is always off. The unit 

restarts automatically when the outside temperature is 43°F (6°C) 

and more.

If the code stays on permanently:

- Ensure the evaporator is clean. If not 

switch the unit OFF from

the circuit breaker

 (fuse) and use a garden hose to lightly clean

the evaporator, then allow it to dry before re-starting the pool heat

pump to avoid premature ice build up on the evaporator.

- Ensure installation instructions have been followed, Improper

installation, e.g. no air circulation could lead to the pool heat pump

continually going into defrost mode and the installation will need to

be corrected by the owner.

Summary of Contents for ElectroHeat MKIV

Page 1: ...lation and Operation Manual Manuel d installation et d utilisation This equipment must be installed and serviced by a qualified technician Improper installation can create electrical hazards which cou...

Page 2: ...er wire as sized to comply with current Standards and local statutory authorities in relation to the circuit conductors supplying the equipment A cable connector is provided on this unit to connect a...

Page 3: ...osts and size of the unit required Pools not covered with a solar blanket lose 2 to 3 times more heat regardless of types of heating Record your model s information Keep this manual and your original...

Page 4: ...ided and will greatly reduce unit s heating capacity and efficiency The unit should be located as close as practically possible to the existing pool pump and filter to minimize water piping The use of...

Page 5: ...3 Units which are installed more than 1 metre below water level will require a flocheck valve to be fitted to prevent the heat pump from cycling when no water flow is detected 4 For units installed ab...

Page 6: ...s the metal framework of the pool the light the pump the filter if metal the pool heat pump any automatic chlorine generator and any other metal or electrical equipment bonded to your pool On some old...

Page 7: ...105 C 5 Close control box cover 6 Re install the access panel To control heaters that are operated in parallel connect wiring at same locations on heater Control It is imperative that each control cir...

Page 8: ...nditions air temperature will be warmer during day time hours To accelerate the initial heating period owners may opt to increase the ambient air temperature artificially around the evaporator area of...

Page 9: ...ettings To program the desired water temperature press BOTH the UP and DOWN arrow keys at the same time until the temperature degree displays change degree then release them Press the UP arrow or DOWN...

Page 10: ...the SET key until F C appears on the temperature display 2 Whilst F C is still on the display Press and release the UP or DOWN arrow key until C is displayed 3 Release all keys and the control will no...

Page 11: ...gs menu and set the off timer to switch the unit off automatically 4 The timer function may repeat and is only deactivated when the ON OFF button is selected 5 Timer error is less than 1min h Note Tim...

Page 12: ...d maintenance For Waterco pool heat pumps located within one kilometre from the coast a coating must be applied to the unit prior to site delivery on the evaporator fins and exposed metal surfaces to...

Page 13: ...it is mandatory that the water accumulated in the pool heat pump be drained completely before freezing weather prevails Improper winterizing may damage the pool heat pump and will void the warranty T...

Page 14: ...dried open the water IN and water OUT valves on the pool heat pump 6 Close the bypass valve to allow full water flow through the pool heat pump If water is now seen running from the outside of the po...

Page 15: ...off early 2 If you have installed a timer or the pool heat pump is equipped with an integrated timer be sure it is programmed to allow the pool pump to work for sufficient time in order to reach the...

Page 16: ...y Ensure vacuum robot or other cleaners are disconnected so that the water flows freely Check that there are no leaks on the pool plumbing there should be no air leaks in the pipework Service Analyser...

Page 17: ...and electronic control with diagnostics I pg 32 Pool Heat Pump Code Problem Action Remedy FS DEF FS4 Problem Normal defrost cycle The fan blades are turning but the compressor has stopped For Electro...

Page 18: ...watertight there should be no air intake Check the swimming pool and pool skimmer baskets and the drain at the bottom of the pool for obstructions Check the filter cartridges for obstructions wash or...

Page 19: ...panel please advise the Waterco service agent There are no other warranties express or implied including but not limited to implied warranties of merchantability or fitness for a particular purpose Du...

Page 20: ...nnecter un conducteur en cuivre de taille appropri e entre cet appareil et tout quipement m tallique bo tiers m talliques d quipement lectrique tuyau d eau m tallique ou tout conduit 1 5 m de l appare...

Page 21: ...ts d exploitation et la taille de l appareil requis Les piscines non recouvertes d une toile solaire perdent 2 3 fois plus de chaleur quel que soit le type de chauffage Enregistrez votre mod le d inf...

Page 22: ...pareil L appareil doit tre situ le plus pr s possible de la thermopompe et du filtre de la piscine en place pour minimiser la fuite d eau L utilisation de coudes 90 degr s et de coudes rayon court dan...

Page 23: ...l eau n cessitent l installation d une valve de v rification de d bit pour emp cher la thermopompe de se d clencher si aucun d bit d eau n est d tect 4 Pour les appareils install s au dessus du niveau...

Page 24: ...n rateur automatique de chlore et tout autre quipement m tallique ou lectrique coll votre piscine Sur certaines piscines plus anciennes ce fil de liaison de sous structure peut ne pas exister Dans ce...

Page 25: ...ture d au moins 105 C 5 Fermez le couvercle du bo tier de commande 6 R installer le panneau d acc s Pour contr ler les appareils de chauffage qui fonctionnent en parall le branchez le c blage aux m me...

Page 26: ...ons atmosph riques temp rature d air seront plus chaudes pendant la journ e Pour acc l rer la p riode de chauffage initial les propri taires peuvent prendre pour augmenter la temp rature de l air ambi...

Page 27: ...er Et R gler Les Param tres De Temp rature Pour programmer la temp rature de l eau d sir e appuyez simultan ment sur les touches HAUT et BAS en m me temps jusqu ce que le degr de temp rature affich e...

Page 28: ...ours indiqu sur l cran Appuyez sur la touche HAUT ou BAS jusqu ce que C soit affich 3 Rel cher toutes les touches et le panneau va maintenant tre configur pour Celcius N appuyez pas sur tous les autre...

Page 29: ...z dans le menu R glages et allumez un chronom tre pour allumer l appareil automatiquement 3 Pour Arr ter la fonction chronom tre lorsque la thermopompe est activ e entrez dans le menu R glages et arr...

Page 30: ...emplacement de la machine par rapport l eau sal e et l entretien Pour les thermopompes chauffage Waterco situ s moins d un kilom tre de la c te un enrobage doit tre appliqu avant leur livraison sur le...

Page 31: ...t obligatoire que l eau accumul e dans la Thermopompe soit drain e compl tement avant que la cong lation a lieu Une proc dure d hivernage d fectueuse peut endommager la Thermopompe et annulera la gara...

Page 32: ...un d bit d eau travers la thermopompe de chauffage Si l eau est maintenant vu l ex cution de l ext rieur de la Thermopompe ou l int rieur de la Thermopompe apr s une courte p riode de temps vous devez...

Page 33: ...Thermopompe est quip e d un chronom tre int gr V rifier qu il est programm pour permettre la thermopompe de la piscine de travailler pendant un temps suffisant afin d atteindre la temp rature programm...

Page 34: ...aspirateur automatique ou d autres appareils de nettoyage sont d connect s de sorte que l eau s coule librement V rifier qu il n y a pas de fuite dans la tuyauterie de la piscine il ne devrait pas y...

Page 35: ...robl me d action Solution FS DEF FS4 Probl me Le cycle normal de d givrage Les pales du ventilateur tournent mais le compresseur s arr te Pour les mod les Chaleur lectrique Ultra et r versible les pal...

Page 36: ...a piscine avec de l eau de la thermopompe V rifier si les tuyaux entre la thermopompe et la pompe de la piscine sont tanches il ne devrait pas y avoir de prise d air Examiner la piscine et l cumoire d...

Page 37: ...icites de qualit marchande ou d ad quation un usage particulier Pendant la p riode de garantie Waterco r parera ou remplacera sa discr tion sans frais tout produit ou pi ce jug d fectueux dans des con...

Reviews: