4

START UP

BEFORE CONTINUING, CHECK FOR OPEN DRAIN VALVES OR 
OTHER SOURCES OF FLOODING BEFORE STARTING UNIT.

1.  Prime  pump  if  necessary  and  adjust  tank  precharge  to  manufacturer’s 

recommendation for intended pressure range. The factory WWDPC setting 
is 40 psi cut-in and 60 psi cut-out.

2.  Turn  on  power  and  ensure  WWDPC  display  illuminates, 

“88”

  will  appear, 

then code revision number, then “00”.  Display will blank momentarily and 
the pump will start. If not, check installation.

3.  The display will now read the current line pressure.
4.  Allow the pump to reach the factory cut-off setting of 60 psi. IF THE PUMP 

CANNOT  REACH  THIS  SETTING,  DISCONNECT  POWER  AND  SEE  THE 
TROUBLESHOOTING SECTION ON PAGE 5.

5.  Check for leaks and repair as necessary before proceeding.
6.  Proceed to the ADJUSTMENT section.

NOTE:

  During  the  first  30  seconds  after  start  up,  the  pump  can  be  made  to 

operate  manually  by  depressing  the 

arrow  for  6  seconds.  This  is  useful  for 

priming jet pumps.

DEVICE ADJUSTMENT (Entering Programming Mode)

NOTE:

 Differential pressure cannot exceed 55 psi or be less than 10 psi. If display 

will not change, alter cut-in or cut-out to within 55 psi.

1.  Press  and  hold

  

.  When 

“LO”

  appears,  release.  This  will  determine  the 

pressure at which the pump activates.

2.  When number appears, tap 

5

 or 

6

 to change cut-in setting.

3.  Press 

 again. When 

“HI”

 appears, tap 

or 

6

 to change cut-out setting. 

This will determine the pressure at which the pump shuts off.

NOTE:

 Depressing 

 a third time will display the last Error Code in memory (see 

Error  Code  table  in  Troubleshooting  section).  If  no  errors  have  occurred,  the 
display will show 

“- -”

4.  After  approx.  10  seconds 

“Pr”

  will  appear,  indicating  the  settings  are 

programmed. Display will then revert to line pressure.

NOTE:

 The settings will now be stored until changed manually, even in the event 

of power failure.

NOTE:

  If  pump  cannot  reach  cut-out  setting  within  5  minutes  with  no  water 

running, lower the pressure settings to fall within the pump’s pressure capabilities.

NOTE:

 Pressing 

5 6 

together for 3 seconds will rotate the screen 180 degrees. 

This is useful if the control is mounted in an inverted position.

OPERATION

The  WWDPC  incorporates  an  accurate  pressure  sensing  system  capable  of 
maintaining  the  set  pressure  range  without  the  need  for  regular  service  or 
adjustment.  The  WWDPC  controls  the  on/off  cycling  of  the  pump  within  the 
selected pressure range (see ADJUSTMENT section).
The WWDPC also incorporates built-in diagnostic functions to protect the system 
and  alert  the  user  or  installer  to  potential  problems.  If  a  fault  is  found,  an  error 
code will be displayed, indicating that service may be necessary. Error codes are 
listed in the TROUBLESHOOTING section.

Summary of Contents for WWDPC

Page 1: ...PC Keep this manual with the product This manual may become out of date by later amendments Check our web site www waterworkerDIY com or ask your WATER WORKER supplier for any updates relating to your...

Page 2: ...be mounted near the pressure tank or pump depending upon the installation LOCATE THE WWDPC FOLLOWING ALL LOCAL CODES DO NOT LOCATE THE UNIT WHERE IT CAN BE AFFECTED BY FLOODING 2 You may assemble the...

Page 3: ...has openings to accept standard conduit terminations Outdoor installations must use watertight connections UNIT MUST NOT BE SUPPORTED SOLELY BY THE ELECTRICAL CONDUIT WATERTIGHT CONDUIT CONNECTIONS MU...

Page 4: ...es 2 When number appears tap 5 or 6 to change cut in setting 3 Press again When HI appears tap 5 or 6 to change cut out setting This will determine the pressure at which the pump shuts off NOTE Depres...

Page 5: ...and remedy Pump rapid cycles Pressure tank too small Differential too narrow Waterlogged pressure tank Improper tank air charge Improper wiring Size tank per manufacturer s literature Spread range via...

Page 6: ...freezing temperatures or temperatures in excess of 120 degrees Failure to properly size the system or follow instructions in the Manual may result in excessive strain on the system and may lead to pr...

Page 7: ...may be internal corrosion and any re pressurization or additional pressure could result in rupture or explosion Do not install with components that are incompatible with the WWDPC This product can exp...

Page 8: ...WATER WORKER is a registered trademark in the U S and elsewhere All rights reserved T 401 884 6300 F 401 885 2567 www waterworkerdiy com...

Reviews: