Water Mist WM-A1584 Installation, Operation And Maintenance Manual Download Page 8

Watermist Fire Technologies

Page 8

9.  Commissioning

Th e following procedure is to be followed to safe guard equipment and prevent personal injury. Th e 

equipment uses dangerous voltages and stores electrical energy, therefore commissioning and testing 

must be carried out by qualifi ed personnel.

All electrical installation and testing must be carried out in line with BS7671: 1992.

Commissioning Procedure

1. 

Carry out visual inspection and carefully check for any damage, which may have occurred dur-

ing transit.

2. 

Equipment should fi rst be checked to ensure that any connections, which may have become 

loose during transit are tightened.

3. 

Ensure that all external cables to be connected to equipment are suitably rated. Also check that 

all cable glands are correctly earthed.

 

As a minimum:
i) 

Carry out a visual inspection of the installation for compliance to the regulations and is 

free of damage.  

ii) 

Check the protective conductor continuity.

iii)  Measure insulation resistance
iv)  Verify the polarity of the conductors.
v) 

Measure the earth loop impedance.

vi)  Test the operation of any ELCBs.

(refer to BS7671 for full details)

4. 

Please note megger test equipment is not permitted to be used while connected to the power 

pack, otherwise will cause serious damage to internal components. 

5. 

As the equipment relies primarily on natural convection for cooling purposes, it is important 

that the enclosure is checked/sited in a position with a free fl ow of air. Th is also applies to equip-

ment fi tted with cooling fans.  

6. 

Connect the A.C. mains supply to the mains terminal, making sure to connect to the input volt-

age stated in manual. Connect the earth connection to the earth stud provided and check  all 

other earth points are fi rmly connected.

7. 

Before connecting any other external connections remove the mains fuse. Switch on the A.C.       

mains supply and check supply voltage and polarity are correct. Replace the fuse and check 

that the power supply unit indicates the correct indications as per the information contained in                

that the power supply unit indicates the correct indications as per the information contained in                

this document. Check power supply D.C. output voltages are correct as per the information                

this document. Check power supply D.C. output voltages are correct as per the information                

contained in this manual.

8. 

Caution to be exercised when connecting batteries, ensure correct polarity is observed, ensure 

correct battery type (2 x 12v sealed rechargeable lead acid) is used.    

Th ere are no user serviceable parts and no user functions. All maintenance and repair work must only 

be carried out by authorised and fully trained How Fire/C.E.L personnel.

Th e occurrence of a PSU fault should be indicated at access level 1 (applicable to Fire Alarm System 

applications).  If  a  power  supply  fault  is  indicated  then  call  the  authorised  Service/Maintenance 

Engineer.  

Summary of Contents for WM-A1584

Page 1: ...1320 fax 01525 285864 Water Mist Fire Technologies Ltd Unit 5 Youngs Industrial Estate Stanbridge Road Leighton Buzzard Bedfordshire LU7 4QB WM A1584 10 AMP POWER SUPPLY WM A1584 10 AMP POWER SUPPLY I...

Page 2: ...arning 3 IMPORTANT NOTE ON BATTERIES 3 3 General Description 4 4 Specification 5 5 Termination List 5 6 Adjustments and Indications 6 7 Installation Procedure 7 Enclosure Housing 7 Earthing Arrangemen...

Page 3: ...data WARNING If required clean the case of the battery with a cloth that has been soaked or dampened with distilled water Do not use organic solvents such as petrol paint thinners benzene or mineral s...

Page 4: ...8 volt output is derived from the DC output of the switchmode power supply whilst the 5v DC output is derived via a regulator on the WM A1584 controller board In the event of Mains failure the power s...

Page 5: ...584 a delay of 3 seconds is initiated and if the fault still exists after this delay period the Common Fault output CF is activated Note 3 When a fault associated with the Mains input is detected by t...

Page 6: ...ated 5 8V Fault Amber Flashes whenever 5v DC regulator output is above 9v DC and below 4v DC MAIN Mains input fault Amber Flashes whenever the DC input from the switch mode unit falls below 28v DC or...

Page 7: ...ich can incorporate 2 x 12v rechargeable Lead Acid Batteries The power supply should be mounted on to a metal chassis or back plane using the 5 o M5 x 20mm bolts provided Figure 1 provides information...

Page 8: ...convection for cooling purposes it is important that the enclosure is checked sited in a position with a free ow of air This also applies to equip ment tted with cooling fans 6 Connect the A C mains s...

Page 9: ......

Reviews: