background image

 

13 

 

FILTER/MEMBRANE REPLACEMENT 

1. 

Turn off water supply to RO system by changing switching the valve control 
from “run to “off”.  The system will be depressurized when the feed pressure 
gauge reads zero.

 

2. 

Disconnect the locking bar and place the fittings (with tubing still connected) 
into a tub or bucket to collect any water than may drain from the tubing.

 

3. 

Move the system into a contained area, such as a sink or tub.

 

4. 

Remove the support leg from the three sumps and unscrew the top sump as 
shown (Figure 5) to access the pre-filter element.  The support leg functions 
as a wrench to loosen/tighten the sump.

 

NOTE: Do not disconnect the tubing from the fittings on the manifold.  Remove 

the locking bar and pull the fittings out.  Lubricate O-rings with silicone 
prior to reassembly. 

NOTE: If only changing the pre-filter, the other two sumps do not need to be 

removed.  If changing the membrane elements, the pre-filter should also 
be changed. 

5. 

Remove the exhausted pre-filter and discard

 

CAUTION

: The person handling the filters and membrane elements must have 

clean hands to keep the system sanitized.  The use of sterile/latex 
gloves is recommended. 

6. 

If changing the membranes: 

a.  Remove membrane sumps.  Remove and discard used elements. 
b.  Remove new elements from packaging. 

CAUTION

: Elements contain a food grade preservative.  The use of sterile/latex gloves is highly recommended. 

c. 

Lubricate element O-rings, brine seals and sump O-rings with silicone lubricant.   

d.  Securely insert O-ring end of elements 

into manifold (Figure 6)  

e.  Replace sumps and tighten until sump 

bottoms out on manifold. 

NOTE: The system should be sanitized whenever a 

membrane element or filter is replaced. 

7. 

Sanitize the system.

 

a.  The manifold should be positioned flat 

with the sump connections facing up. 

b.  Pour a tablespoon (15 milliliters) of 

chlorine bleach into the center opening 
of the pre-filter sump connection (Figure 
6). 

8. 

Install pre-filter. 

a.  Remove new pre-filter from packaging.  Ensure gaskets are secure.  Insert pre-filter into proper opening on 

manifold. 

b.  Lubricate sump O-ring with silicone lubricant. 
c. 

With the pre-filter element in place, screw the sump into the connection.  Tighten until it bottoms out on 
manifold. 

9. 

Reconnect the fittings to the manifold and lock in position with locking bar. 

10. 

Turn drain flow control valve (gray valve with black circular handle) to the fully open position. 

11. 

Re-position the assembly onto the skid assembly and turn on the water supply back onto the RO.  Turn the valve control 
from “off” to “run” to supply pressurized water to the RO system.  Verify there are no leaks. 

a.  Air will need to be bled from the system.  Consult startup procedure to bring the system back into service.  Allow 

water to flow to drain for at least 30 minutes to flush out membrane preservative before adjusting the drain flow 
control valve to re-establish the correct permeate-to-concentrate (product water-to-drain water) ratio, per table 
2.0. 

12. 

The RO system is now ready for use. 

 

 

Figure 5 

Figure 6 

Turn counterclockwise 

to loosen 

Pre-filter 

Summary of Contents for WHRO-700

Page 1: ...amsey MN 55303 Phone 1 866 405 1268 Fax 763 427 5665 www watercontrolinc com 0222 Installation Manual WHRO 700 Whole House Reverse Osmosis System Standard and MAX Systems For questions regarding this...

Page 2: ...2 This page intentionally left blank...

Page 3: ...ater vs Drain Water Flow Ratio 10 CONTAMINANT REJECTION 11 MEMBRANE LIFE 11 MAXIMIZING MEMBRANE ELEMENT LIFE 11 TROUBLESHOOTING 11 Table 3 0 Booster Pump Flow and Pressure Capabilities 12 MAINTENANCE...

Page 4: ...pre installed components o Float switch o Ozone tubing o 1 tank outlet and overflow connection 2 75 x 17 Sediment pre filter o Includes PS3038333 filter cartridge 5 micron carbon block This cartridge...

Page 5: ...5 SYSTEM DIAGRAM...

Page 6: ...6 TYPICAL INSTALLATION DIAGRAM...

Page 7: ...h water in the storage tank or in the RO membrane elements 1 Locate storage tank and skid assembly in appropriate location Both tank and skid assembly should be placed on a level surface 2 Verify insi...

Page 8: ...ESSURIZE Slowly increase the amount of water feeding the RO system until the feed valve is completely open At this point most of the water should be passing through the DRAIN flow meter Allow the syst...

Page 9: ...p now provides water pressure throughout the home facility The pump comes equipped with an internal pressure sensor so that when the pressure in the system is relieved e g a faucet is opened the pump...

Page 10: ...sed In the case of RO systems this ratio can be defined mathematically using the equation System Recovery Permeate Flow gallons minute Feed Flow gallons minute 100 Most residential RO systems operate...

Page 11: ...is used the longer the membrane elements generally tend to last TROUBLESHOOTING ISSUE POSSIBLE CAUSE CORRECTIVE ACTION Pump runs continuously Water leak in building which results in pump sensing drop...

Page 12: ...rtridge WHRO 700MAX installations with chloramine treated city water 18 months FST 5418 RC 2b Replace 9 x 40 GAC pre filter cartridge WHRO 700MAX installations with chlorine treated city water 54 mont...

Page 13: ...nd sump O rings with silicone lubricant d Securely insert O ring end of elements into manifold Figure 6 e Replace sumps and tighten until sump bottoms out on manifold NOTE The system should be sanitiz...

Page 14: ...p pushing and open outlet valve 11 Check system for leaks and ensure system integrity CARTRIDGE REPLACEMENT 1 Turn off water supply by shutting off the inlet and outlet ball valves Figure 7 2 Properly...

Page 15: ...oubleshooting WCC recommends that the performance log be updated weekly The performance log can be helpful to help determine when pre filters or RO membranes require service or will require service in...

Page 16: ...IMPLIED INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHAT IS NOT COVERED BY THESE WARRANTIES 1 Conditions damages and health effects resulting from any of the follo...

Page 17: ...e sample 4 Lightly stir the meter to dislodge any air bubbles 5 Wait until the display stabilizes Once the reading stabilizes approx 10 seconds press the HOLD button to view the reading out of the wat...

Page 18: ...ozone generator on push in the main power switch located on the on the front of the ozone generator into the ON position a The red light above the main power button will illuminate b The LED will indi...

Page 19: ...run only 6 Runs for 2 minutes every hour repeats every hour 7 Runs for 5 minutes every hour repeats every hour 8 Runs for 10 minutes every hour repeats every hour 9 Runs for 15 minutes every hour rep...

Page 20: ...20 Water Control Corporation 7150 143rd Ave NW Ramsey MN 55303 Phone 1 866 405 1268 Fax 763 427 5665 www watercontrolinc com 1021...

Reviews: