Error Causes

 

Action to Be Taken

 

 

  Power capacity is too small. 

  Voltage drop due to wiring resistance. 

 A motor of large capacity connected to the same power 

system has been started. 

  Defective electromagnetic contractor.

 

  Check the source voltage and wiring. 

  Check the power capacity and power system.

 

 

 Extremely rapid accel. 

  Short-circuit or ground- fault at the inverter output side. 

  Motor of a capacity greater than the inverter rating 

has been started. 

  High-speed motor and pulse motor has been started. 

 

  Extend the accel. time. 

  Check the load wiring.

 

 

 

  Motor dielectric strength is insufficient. 

  Load wiring is not proper. 

  Check the motor wiring impedance and the load 

wiring. 

 

 

  Insufficient deceleration time. 

  High input voltage compared to motor rated voltage. 

  Extend the accel. time. 

  Use a braking resistor. 

 

  Defective cooling fan. 

  Ambient temperature rise 

 Clogged filter. 

 Check for the fan, filter and the ambient 

temperature.  

 

  Overload, low speed operation or extended accel. time. 

  Improper V-f characteristic setting 

  Measure the temperature rise of the motor. 

  Decrease the output load. 

  Set proper V/f characteristic. 

 

  Improper rated current (Cn-09) setting 

  Set proper V/f characteristic. 

  Set proper rated current (Cn-09) 

 If inverter is reset repetitively before fault 

removed, the inverter may be damaged. 

 

 

  Machine errors or overload 

  Check the use of the machine. 

  Set a higher protection level (Cn-32). 

 

 

 

 

 

 

 

 

 

 

  Fault input of external signal 

e

g

h

i

 and 

j

  Identify the fault signal using Un-11. 

 

 

 

 

  Disturbance of external noise 

  Excessive impact or vibration 

  Reset NVRAM by running Sn-03.   

 Replace the control board if the fault can’t be 

cleared. 

 

 

 Improper setting of ASR parameter or over-speed 

protection level. 

  Check the parameters of ASR and the 

protection level. 

 

 

 The PG wiring is not properly connected or 

open-circuit. 

  Check the PG wiring. 

 

 

 Improper setting of ASR parameter or speed 

deviation level.

 

  Check parameters of ASR and speed deviation 

level. 

 

 External  noise 

 Excessive vibration or impact Communication wire 

 Not properly contacted 

 Check the parameter setting, including Sn-01, Sn-02. 

 Check if the comm. wire is not properly contacted. 

 Restart, if fault remains, please contact to us. 

-9-2-  

Summary of Contents for TCW-7055

Page 1: ...ontact us directly Phone 800 314 8081 Fax 828 397 8615 125 lb Washer Extractor Model TCW 7055 Installation Maintenance Manual Parts List PO Box 1369 Hickory NC 28603 INDUSTRIAL LAUNDRY EQUIPMENT A Div...

Page 2: ......

Page 3: ......

Page 4: ......

Page 5: ......

Page 6: ...1 29 10 15 23 22 21 8 22 24 20 14 2 31 31 28 12 18 17 16 9 15 14 11 13 13 26 31 28 12 6 14 25 19 5 21 4 2 22 23 19 7 3 02 1...

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...FRONT ASSEMBLY KEYPAD TOP VIEW RIGHT HAND SIDE LEFT HAND SIDE 6 01...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ...erature 1 Steam opener isn t activated 2 The boiler does not supply steam 3 The steam Y filter is blocked 1 Turn on the opener 2 Turn on the boiler 3 Clean the filter Fault 04 After draining for 2 min...

Page 24: ......

Page 25: ...ace time Ou Over voltage Detection level Approx 400V for 220V class Approx 800V for 440V class Cn 01 400V Approx 700V for 400V Class Cn 01 400V Increase decal time and or add braking resistor FU Fuse...

Page 26: ...detected by the electronic thermal relay motor protection Operation Fault Inverter Over Load The electronic thermal sensor detects inverter overload while the output current exceeds 112 of rated value...

Page 27: ...f characteristic setting Measure the temperature rise of the motor Decrease the output load Set proper V f characteristic Improper rated current Cn 09 setting Set proper V f characteristic Set proper...

Page 28: ...d according to the stop method preset by Sn 04 No operation blinking Alarm RS 485 Interrupt MODBUS Communication fault occurs The inverter remains operating No operation Comm Fault Transmission fault...

Page 29: ...eed search of the inverter Inverter KVA setting error Set proper KVA value Be aware of the difference of 220V and 440V The value of Sn 25 Sn 28 is not in ascending order Ex Sn 25 05 Sn 28 02 those are...

Page 30: ......

Reviews: