Wärtsilä JOVYTEC L 6kVA
– 10kVA BAX 3297_en
- 33 -
11.
Internal manual bypass
ATTENTION:
Prior to switch the internal manual bypass switch on the rear side of the UPS it is
absolutely mandantory to switch the UPS to the internal electronic bypass by means of
the operating panel.
For switching the UPS over to the manual-bypass operation, make sure the UPS is operating already on the
internal electronic bypass. If so, the Ups may be switched to the internal manual bypass bey means of the service-
switch on the rear side of the UPS.
For returning from the internal manual bypass, first verify, that the logic of the UPS is set to the internal electronic-
bypass. If this is verified, the service-switch on the rear side of the UPS may be set to normal operation, after this
the UPS may be set to online-mode by means of the operating panel.
11.1.
External bypass (Optional)
For this UPS
– Device is an optional additional External Manual Bypass available.
This additional External Manual Bypass will be described in Manual BAX 3993!!!