Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E
- 6 -
1
Technical Data
Wärtsilä JOVYSTAR HP
Online UPS-Type
200 kVA
250 kVA
300 kVA
Output
Output apparent power (cos
φ = 0,9)
200 kVA
250 kVA
300 kVA
Output active power (cos
φ = 1)
180 kW
225 kW
270 kW
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
-
Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V
3 x 400/230 V
3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
50/60 Hz
±0,001 Hz
±2 Hz
Rated output current (cos
φ = 0,9)
290 A
362 A
435 A
Rated output current (cos
φ = 1,0)
261 A
325 A
391 A
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
< 1 %
< 5 %
Input
Input voltage
3 x 400/230 V +15 % -20 %
Input frequency
50/60 Hz ±5 Hz
Input current (at 100 % load, without battery charging)
273 A
341 A
410 A
Input current (at 100 % load, max. battery current)
303 A
383 A
450 A
Input power factor (at 100 % load)
> 0,99
Input current THD (at 100 % load)
< 3 %
Battery
Number of battery cells
300
Compensation charging voltage
680 V (2,27 V/Z)
Cut-off voltage
496 V (1,65 V/Z)
Max. battery charging current (at 100 % load)
30 A
40 A
Max. battery charging current with activated DCM
(
D
ynamic
c
harging
m
ode, only at partial load)
100 A
Battery charging characteristic
IU (DIN 41773)
Overload capability/Output short circuit characteristic
Overload capability inverter
>100 % to 125 % to 10 min
> 125 % to 150 % to 1 min
> 150 % to 199 % to 10 s
= 200 % for 100 ms
Overload capability static bypass
150 % continuously
1000 % to 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
1. Current limitation to 200 % for 100 ms
2. Current limitation to 125 % for another 5 s
462 A
289 A
580 A
363 A
694 A
434 A
Design/Conformity
Dimensions (W x H x D)
1220 x 1905 x 895 mm
Weight (without battery)
970 kg
1090 kg
1170 kg
Paint
RAL 5026 / RAL 9006
Noise level
< 62 dB
EMV-class according to IEC EN 62040-2
C3
Class of protection according to IEC EN 62040-3
VFI SS 111
International protection
IP 20
Other data
Efficiency normal mode (at 100 % load)
> 95 %
Efficiency battery mode (at 100 % load)
> 96 %
Efficiency eco-mode (Offline-mode)
> 98 %
Max. crest factor without power reduction
3 : 1
Heat dissipation
(at 100 % load and rated input voltage)
11,0 kW
13,7 kW
16,5 kW
Requirements to the installation position
Max. installation altitude without power reduction
< 1000 m
Power reduction for installation altitude according to
IEC EN 62040-3
1 % every 100 m above 1000 m up to 5000 m
Required air cooling volume
3500 m³/h
4100 m³/h
4500 m³/h
UPS operating ambient temperature
0 to +40 °C
UPS storage temperature
-10 to +70 °C
Battery ambient temperature
(recommended battery ambient temperature, see also
battery operating instruction)
0 to +25 °C
+20 °C
Battery storage temperature
0 to +25 °C
Relative humidity (non condensing)
< 95 %
Wärtsilä JOVYSTAR HP E
Summary of Contents for JOVYSTAR HP 200 kVA
Page 1: ...Operating manual W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E...
Page 18: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 18...
Page 19: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 19 4 3 2 Dimensions W rtsil JOVYSTAR HP E 400 kVA...
Page 20: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 20...
Page 22: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 22...
Page 23: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 23 4 3 4 Dimensions W rtsil JOVYSTAR HP E 800 kVA...
Page 24: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 24...
Page 25: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 25...
Page 28: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 28 Terminal board 400 kVA...
Page 29: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 29 Terminal board 500 800 kVA...