WÄRTSILÄ JOVYCUBE 160
BAX 5157
- 13 -
3 Installation
Remove the packaging immediately after receiving the UPS and check the system for transport
damages. The transport company must be informed immediately after receipt of the UPS in the event
of any damage caused during transportation. If the UPS is not installed immediately it must be stored in
an upright position as indicated on
the packaging and kept in a dry, well ventilated room. If the UPS is
not stored in the original packaging, it must be protected from dust and moisture.
3.1
Installation
The UPS must be set up in a clean, dry, dust-free room. The operator must ensure that the room is
adequately ventilated, so that the system is sufficiently cooled and overheating is prevented. Please
observe the set-up diagram in the appendix. If the UPS is supplied with built-in batteries, the exchange
of air with the external environment must be in accordance with EN 62040, appendix N.
3.2
Electrical connections, cross sections, fuses
The electrical connection of the UPS unit is the task of the electrician providing the electrical installation
services. This task is not carried out by the UPS manufacturer. For this reason, the following
recommendations are only an indication, as the UPS manufacturer is
not responsible for the electrical
installation.
In all cases, we recommend installing and connecting the input and output in conformity with local
regulations and standards.
In particular, take care to ensure a clockwise rotation phase sequence
during electrical installation.
If no error message is generated, the Jovycube will also operate with an
anti-clockwise rotating field, and this may result in destruction of the UPS/modules if the manual bypass
is used. In the event that strong electromagnetic fields are emitted, we recommend the use of shielded
cables between the UPS and the load.
ATTENTION:
Even when the mains voltage is switched off there is a dangerously high battery voltage
inside the device. All installation and connection work may therefore only be carried out
by a qualified electrician. Before commencing work, electricians must read this manual
carefully to familiarize themselves with the special features of this UPS unit. The UPS
output still carries voltage even in the event of a mains failure. For this reason, the installer
must clearly label the outlets and sockets on the UPS unit in accordance with EN 62040!
ATTENTION:
The input line between the mains and the UPS unit must be protected against short
circuits!
The use of FI safety switches before the UPS unit is not recommended.