JOVYATLAS POWERMASTER S 6000-P BAX 4469 E
- 8 -
4
Technical Data
JOVYATLAS POWERMASTER S 6000
Output
cos
ϕ
0,7 ind.
6000VA / 4200W
Network supply
Voltage
230V
Input voltage ranges
176V - 276V
Current
27A
Frequency
50Hz ± 5% or 60Hz ± 5%
Phase
Single phase
Power factor
0.98
External
fuse protection
D02/35A
Battery
(installed in the
battery rack
POWERPACK
S 6000
)
Direct current link voltage
240 V
Backup time
9 minutes at 100% load 12 minutes at 80% load 21 minutes at 50% load
Model
Maintenance-free, closed lead acid batteries
Charging time
< 8 hours for a 90% discharge
Output
Voltage
230V standard (208V / 220V / 240V selectable at the panel)
Frequency
Automatic adjustment via the die UPS unit
Power factor
cos
ϕ
0,7 ind.
Phase
Single phase
Distortion factor
< 3% for a linear load
Overload behaviour
100 to 125% for 60 seconds
125 – 150% for 10 seconds
Crest Factor
3 : 1
Switch-over
behaviour
Power failure
0 ms
Overload switching
Automatic overload switching by the UPS unit
Noise level
At an approx distance of
1 metre
< 55dB(A)
Environment
Temperature
0°C to 40°C
+15 … +25°C (recommended)
Air humidity
0% to 90%, non-condensing
Storage at …
20°C with build in battery
-20 to +50°C without battery
Interfaces
RS 232 interface
Optional:
USB interface
Relay card
AS/400 - adapter
SNMP - adapter
Supports power management and diagnosis such as BATTERY LOW, UPS
ON/OFF
Software is compatible with operating systems such as: Windows
95/98/NT/2000/XP, Novell, Unix, etc current operating systems .
Dimensions
UPS
rack
POWERMASTER
S 6000
Width
430mm UPS
483mm Front Cover
Depth
671 mm
Height
3RU (130mm)
Dimensions
battery rack
POWERPACK
S 6000
Width
430mm Battery Tray
483mm Front Cover
Depth
597 mm
Height
3RU
Weight of UPS
POWERMASTER S 6000
approx. 23 kg
Weight of UPS
incl. battery
Powermaster S 6000
about 66 kg incl. batteries
Scope of delivery Hardware/software
UPS unit POWERMASTER S 6000 P
Battery rack POWERPACK S 6000
(according to backup time: 1-3)
Manual BAX 4469E
Interface cable
Software UPSMON