DS-2C RAIN/SNOW SENSOR CONTROLLER
INSTALLATION INSTRUCTIONS

THE UNIT MUST BE IN STANDBY/RESET TO CHANGE CONFIGURATION SWITCHES.

RECOMMENDED SWITCH SETTINGS BY FUNCTION

Function

Trigger

LD Off

LD On

LTC

DEL

RAIN

SNOW

Snow sensor w\o LTC

TT>AT

2 Min

2 Min

OFF

OFF

OFF

ON

Snow sensor w\LTC

TT>AT>5°F

2 Min

2 Min

ON

OFF

OFF

ON

Snow controller w\o LTC

TT>AT

30-90 Min

2-6 Hr

OFF

ON

OFF

ON

Snow controller w\LTC

TT>AT>5°F

30-90 Min

2-6 Hr

ON

ON

OFF

ON

Precipitation sensor

Not Used

2 Min

2 Min

X

OFF

ON

ON

Precipitation controller

Not Used

30-90 Min

2-6 Hr

X

ON

ON

ON

Rain sensor

AT>TT

2 Min

2 Min

X

OFF

ON

OFF

Rain controller

AT>TT

30-90 Min

2-6 Hr

X

ON

ON

OFF

LT thermostat w\o LTC

TT>AT

2 Min

2 Min

OFF

X

OFF

OFF

LT thermostat w\LTC

TT>AT>5°F

2 Min

2 Min

ON

X

OFF

OFF

X = Do Not Care

FINE ADJUSTMENT FOR EFFICIENT OPERATION
The DS-2C is shipped with the TRIG TEMP and DELAY OFF adjustments in the center position, representing 
39°F (3.9°C) and 60 minutes of Delay-Off time respectively. It is also set for highest SENSITIVITY. Depending 
on local conditions the user may find that fine adjustment of the controls may provide more satisfactory 
operation. If the sensor does not trigger during very wet snows the trigger temperature may need to be 
adjusted higher. Constant triggers from snow falling from trees or overhangs may be reduced by adjusting 
SENSITIVITY. The Delay-Off time can also be adjusted to provide clean melt-off without excessive running 
time. Fine adjustment can both save operating expense and provide more reliable operation. However, to 
keep reliability high, always make adjustments in small increments.

Use Care When Replacing the Front Cover. Do Not Pinch the Gasket or Overtighten the Screws.

MANUAL OVERRIDE SWITCH OPERATION
An override switch mounted on the side is provided for testing and special operational requirements. 
Placing the switch in the AUTOMATIC position will allow the sensor to operate normally, activating the 
controlled equipment as needed. Placing the switch in MANUAL ON will close the load relay, activating the 
controlled equipment. The “STANDBY/RESET” position prohibits triggering of the unit, clears any active 
delay timer, and opens the load relay. In order to reduce excessive runtime for the heater the “Manual 
On” mode will remain in effect for up to 40 hours, then return to “Automatic” mode, even if the switch 
is still in the “Manual On” position. However, any trigger of the system will restart the 40 hour “Manual 
On” timer. You may put the DS-2C back into “Manual On” mode by switching to AUTOMATIC, then back to 
MANUAL ON. This will also restart the 40 hour timer. 
If the override switch is placed in MANUAL ON for less than 2 seconds, then switched back to AUTOMATIC 
the controller will execute one Delay-Off cycle. This can be used to clear a frost, hail, or drifted snow 
buildup without the danger of leaving the system in a continuous “Manual On” condition. 
“Standby/Reset” can still be used to clear this Delay-Off cycle.

Summary of Contents for DS-2C

Page 1: ...cation that exposes the moisture sensor to a clear view of the sky The unit should not be mounted directly under eaves or overhangs It should not be mounted so close to the ground that it may become buried in snow For proper temperature detection the DS 2C must be mounted outdoors away from furnace vents dryer vents and other sources of heat Note that when powered the DS 2C moisture grid will alwa...

Page 2: ... temperature If selected the snow sensor will clear a trigger below 5 F 15 C even if snow is still falling It will resume normal operation above 9 F 13 C However the sensor will remember if it was triggered before the drop below 5 F or if snow was detected during the cold period If so the sensor will execute one Delay Off cycle when the temperature rises above 9 F in order to melt any snow left be...

Page 3: ...stant triggers from snow falling from trees or overhangs may be reduced by adjusting SENSITIVITY The Delay Off time can also be adjusted to provide clean melt off without excessive running time Fine adjustment can both save operating expense and provide more reliable operation However to keep reliability high always make adjustments in small increments Use Care When Replacing the Front Cover Do No...

Page 4: ...While not as convenient as directly supplying power for the load this allows you to operate the DS 2C from one voltage while controlling a load of a different voltage without adding an external relay or contactor For example the DS 2C can be powered from 120VAC but can directly control a 24VAC signal for a boiler system or 277VAC for heating wire The following diagrams show a possible wiring schem...

Page 5: ...eft behind when water is evaporated out of the moisture grid will eventually damage the grid rings The moisture grid can be easily replaced by ordering and installing an MG 5 Moisture Grid Assembly and following the procedure below THIS PROCEDURE SHOULD ONLY BE PERFORMED BY QUALIFIED PERSONNEL Open all power and load breakers connected to the DS 2C Open the front cover and remove the cable connect...

Page 6: ... of 6 inches from the base conduit hub Repair costs of a modified unit will be quoted as the unit must be returned to the original unmodified condition prior to return shipping The customer shall be responsible for all costs incurred in the removal or reinstallation and shipping of the product for repairs Within the limitations of this warranty inoperative units should be returned freight prepaid ...

Reviews: