Electric Underfloor Installation

see numbering on diagram below

2. 

Connect to Power Supply (Live – MAX 240V)

3. 

Connect to Power Supply (Neutral – MAX 240V)

4. 

Connect to Warmup heater(s) (Neutral – MAX 3600W/ 

16 Amps)

5. 

Connect to Warmup heater(s) (Live – MAX 3600W/ 16 

Amps) 

7. 

Connect to 1st wire of floor sensor (colour not 

important)

8. 

Connect to 2nd wire of floor sensor (colour not 

important)

Central heating Installation

see numbering on diagram below

2. 

Connect to Power Supply (Live – MAX 240V)

3. 

Connect to Power Supply (Neutral – MAX 240V)

4. 

Connect to Boiler circuit (Neutral if present– MAX 

3600W/ 16 Amps)

5. 

Connect to Boiler circuit (

240V Switch Live

 – MAX 

3600W/ 16 Amps)

For extra low voltage or volt-free systems a contactor must 

be used. Contact Warmup for more details.

Connecting the 4iE directly to extra low voltage or volt-free 

boilers may cause damage to the boiler circuit.

Hydronic Underfloor Installation

see numbering on diagram below

2. 

Connect to Power Supply (Live – MAX 240V)

3. 

Connect to Power Supply (Neutral – MAX 240V)

4. 

Connect to wiring centre (Neutral if present – MAX 

3600W/ 16 Amps)

5. 

Connect to wiring centre (Switch Live – MAX 3600W/ 16 

Amps) 

7. 

Connect to 1st wire of floor sensor (colour not important)

8. 

Connect to 2nd wire of floor sensor (colour not important)

Special Installation

see numbering on diagram below

Second sensor installation: (2nd floor probe or exterior probe)

6.   Connect to 1st wire of external sensor/ 2nd floor sensor

7.   Connect to 2nd wire of external sensor/ 2nd floor sensor

Master/Relay installation: (connecting 2 stats together)

6.   Connect to terminal 6 on other thermostat

7.   Connect to terminal 7 on other thermostat

Mounting Thermostat thermostat

1. 

Push excess wire back through the wall box and 

insert thermostat back module into wall box. 

2. 

Put fixing screws through mounting holes and 

tighten.

3. 

Ensure that thermostat is straight before tightening 

completely.

4. 

Replace thermostat front housing; 

 

i) align and sit front housing on to hinges, 

 ii) push lower half of front housing until a      

‘click’ is heard. 

5. 

Ensure front housing is securely fixed.

6. 

IMPORTANT: Tighten both retaining screws

Powering Up

You can now power up the thermostat and begin the 

programming process. An easy to follow menu will 

guide you through the rest. If you want to turn on / off 

the thermostat and heating system then hold down the 

recessed button on the bottom of the stat for 3 seconds

Error Messages

Your thermostat can give you two error indications:

1. 

 “er1”: This will occur if no floor sensor is detected

2. 

 “er2”: This will occur if the floor sensor has a short 

circuit

4

33

OB

16

17

Summary of Contents for 4iE WiFi

Page 1: ...ome is at the right temperature at the right time Energy monitoring Graphical display of your energy usage and cost with comparisons and forecasts WarmAppsTM Get apps on your 4iE like traffic alerts a...

Page 2: ...the home screen To wake the 4iE just tap the screen or press Wake Hold the power button on the bottom of the device for 3 seconds to turn the thermostat on or off The icons at the bottom of the scree...

Page 3: ...rocedure as below and you can set up a MyWarmup account at any time in the future Important Ensure you choose the correct System Type Electric underfloor Hydronic underfloor or Conventional central he...

Page 4: ...mail you can connect your 4iE to the account Ensure your 4iE is connected to the internet If you see an error icon on the homescreen like below then your thermostat is not connected to the internet If...

Page 5: ...re finished The programming works by setting Comfort Periods of warm temperatures shown with a green line Any time not covered by a Comfort Period will use a lower Setback temperature to save energy T...

Page 6: ...til you raise the temperature again Preset Programs You can select a preset program schedule to get you started You can edit the program whenever you like by following the steps in Set Your Heating Pr...

Page 7: ...f your system Press Energy Settings and select if you have a single rate tariff or a standard low energy tariff where you have a discounted cost during part of the day Enter your cost per KWH and rele...

Page 8: ...stats 3 Use low voltage cable to connect terminal 7 of both thermostats in addition to floor sensor cables on the Master thermostat 4 Set Relay thermostat to Relay mode first then set the Master therm...

Page 9: ...portant 8 Connect to 2nd wire of floor sensor colour not important Special Installation see numbering on diagram below Second sensor installation 2nd floor probe or exterior probe 6 Connect to 1st wir...

Page 10: ...h latest IEE Wiring Regulations and appropriate Statutory Regulations Location The thermostat should be installed inside a single gang electrical wall box that is at least 30mm deep For optimal perfor...

Page 11: ...ll not apply if it is shown by Warmup that the defect or malfunction was caused by failure to follow the instruction manuals incorrect installation or damage which occurred while the product was in th...

Reviews: