Installation and operation manual DC 

5.4

 

 Error code 

When the unit detects a failure, an error code is shown on the controller. The following 
table gives the description of the error and the action to take. 

ERROR CODE 

DESCRIPTION 

 

E01

 

The 

HP

 pressure switch has detected an abnormality in the refrigerant 

regulation. The sensor signals an excessive refrigerant pressure during heat 
pump operation. 

Contact the after-sales service.

 

 

E02

 

The 

LP

 pressure switch has detected an abnormality in the refrigerant 

regulation. The sensor signals a low refrigerant pressure during heat pump 
operation. 

Contact the after-sales service.

 

 
 
 

 
 

E03

 

Faulty contact in the flow sensor.  
 

Solution:

 

-Check the calibration of the water inlet and outlet valves and the water 
pressure in your system must be greater than 0.9 bar 
-Make sure the flow sensor wires are connected to the electronic board, to 
test it, disconnect the wires and then reconnect them. 

-Close the hydraulic valves, remove the flow switch, clean the inside of the 
flow switch if it is dirty or has any limescale in it 
Apply pressure to the detector vane to trigger the contact manually and 

simulate the flow of water, if the error code disappears after one minute of 
maintained pressure, it means the flow sensor is working, otherwise, if the 
error code remains set, replace the flow sensor 

 

 

E04

 

The 

LP&HP

 pressure switches have detected an abnormality in the 

refrigerant regulation.  The sensors are malfunctioning due to not enough 
refrigerant in the heat pump. 

Contact the after-sales service.

 

 

 
 

E08

 

The connection between the control box and the heat pump is not working. 

Solution:

 

 

-Make sure the control wires are connected to the electronic board in place: 
"12V brown wire - NET blue wire - GND green & yellow wire" 
-Check the connection of the remote command wire connection 

If this does not resolve the fault, replace the control box 

 
 
 

 

P01

 

Fault in the water inlet temperature sensor. 

Solution:

 

 

-Check the calibration of the water inlet and outlet valves 

-Make sure the sensor wires are connected to the electronic board 
-Check that the sensor is correctly installed on the hydraulic heat exchanger 
-Check the condition of the sensor, make sure that the cable is not damaged 
or cut 

after the checks, if the error code remains set, replace the sensor 

 

P02 

 

 

Fault in the water outlet temperature sensor. 

Solution:

 

 

-Check the calibration of the water inlet and outlet valves 

-Make sure the sensor wires are connected to the electronic board 
-Check that the sensor is correctly installed on the hydraulic heat exchanger 
-Check the condition of the sensor, make sure that the cable is not damaged 
or cut 

after the checks, if the error code remains set, replace the sensor 

Summary of Contents for DC55

Page 1: ...1 Installation and operation manual DC...

Page 2: ...llation The installation of this heat pump must be carried out by qualified personnel This heat pump meets the manufacturing and communication standards defined by FPP s DTP10 and NFPAC The maintenanc...

Page 3: ...Power consumption kW 0 19 1 32 0 25 1 84 0 37 2 80 0 38 3 60 Cooling capacity kW 3 72 4 3 6 2 7 69 Cooling power consumption kW 1 45 1 78 3 3 2 66 EER 2 57 2 43 1 86 2 89 Casing material ASA ASA ASA...

Page 4: ...4 Installation and operation manual DC 2 3 Dimension of swimming pool heat pump DC 55 75 2 4 Dimension of swimming pool heat pump DC 95...

Page 5: ...gram Your heat pump should be level and at least 15 cm above the ground We recommend you use blocks and drain the condensation into a sump which can be covered with gravel If any of these recommendati...

Page 6: ...treatment system or discharge Upstream of this BYPASS an OUT pipe with a shut off valve will be connected to the water inlet of the heat pump and a RETURN pipe with a shut off valve will be connected...

Page 7: ...on an independent panel connected to the main switchboard with a differential circuit breaker If this is not the case add a differential circuit breaker to the heat pump s independent panel Model Supp...

Page 8: ...Set the water outlet valve of the heat pump to 1 3 At the end of these adjustments check your sand filter pressure gauge the pressure should not increase beyond 0 2 bar the pressure should stay in the...

Page 9: ...an operation in progress and returns to the previous operating level Up switch Used to scroll through the parameters and operating and temperature values Down switch Used to scroll through the parame...

Page 10: ...gramming Displayed when a time schedule is being recorded Water outlet symbol Displays the water outlet temperature Water inlet symbol Displays the water inlet temperature Lock symbol Displayed when t...

Page 11: ...ange of mode Sous In the main interface briefly press to toggle the unit between heating cooling and automatic modes Mode chauffage Mode refroidissement Mode automatique Appuyez bri vement pour passer...

Page 12: ...lue you want wait 5 seconds and the temperature displayed will be saved as the set temperature The system will automatically store the user setting and return to the main interface Setting the clock A...

Page 13: ...Press the symbol for 3 seconds to display the symbol To set your schedule use the up and down arrows To check your programme and exit press Silence mode When silent mode is active it appears on the sc...

Page 14: ...low sensor is working otherwise if the error code remains set replace the flow sensor E04 The LP HP pressure switches have detected an abnormality in the refrigerant regulation The sensors are malfunc...

Page 15: ...r cut after the checks if the error code remains set replace the sensor P06 Significant temperature difference between the water inlet and the water outlet or fault in the electronic board PCB Solutio...

Page 16: ...the correct operation of your machine but we recommend that you clean the evaporator to stop the process 6 2 Wintering Winterisation is mandatory at the end of the period of use to prevent any damage...

Page 17: ...at pump has not been installed using best practice following the recommendations described in this manual Routine maintenance has not been carried out especially the cleaning of the evaporator and the...

Page 18: ...s provided for in this guarantee are exclusive and are Warmpac s only obligation any other claim made by any person will have no effect 6 5 Safety advice Do not touch the fan when it is running it cou...

Reviews: