3.5.4 EG FULLY ELECTRONIC CONTROL VALVE
Ensure gas supply and power supply (caution 240V) to the unit
•
Refer to data plate on this specification for settings. The data plate is attached to the under carriage of the burner.
•
Remove front grate and ensure the CAT5 cable to the control receiver is still connected.
•
Loosen the jet test point and attach manometer (digital is preferred). The test point is on the right hand side of the gas burner, as
shown below.
Gas Test Nipples for SG / EG Fires
Note: Any alterations to pressure is to be carried out by a certified gasfitter
•
Light appliance, adjust to high flame setting and check pressure, adjust to low flame and check pressure.
•
If adjustments are necessary, remove the cap . The pressure adjustment screw and nut are on the front side of the gas control
valve and are factory set.
High Pressure Setting
:
•
Set the modulator to maximum condition. Screw in nut A to increase the outlet pressure then screw nut A out to decrease the
pressure to the desired settings. Use 10mm spanner.
Low Pressure Setting:
•
Turn off the power to the modulator (by disconnecting the modulator harness connection at the valve
-
see wiring.) and, keep nut A
stationary. Use a screwdriver to screw in screw B to increase the pressure and screw it out to decrease the pressure. Carefully
replace the modulator plastic cap.
WARNING:
To ensure the correct operation of the modulator it is necessary that the plastic cap is returned to its original location.
DIAGRAM B
Modulator Harness Connections
Screw B