29 March 2021

 

Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification.

 

All Dimension are in mm

 

8

 

ADJUSTMENT OF HI—LOW PRESSURE                   (SG ONLY)                      (Only to be Adjusted by Gasfitter)                            

Note*  Control Valves are Factory Set but may require adjustment onsite .

 

Turn Appliance Off & Remove Front Plastic Cover on Igniter , Pull Cover to Slide off .

 

Unscrew Test Nipple on the Burner Manifold & fit the Test Gauge Securely 

-

 See Diagram

 

* To Set the High : Light the Burner & turn to High 

-

 Then Adjust the High Screw to the Desired Pressure . See Spec

s

 

* To Set the Low : Light the Burner & turn to Low 

-

 Then Adjust the Low Screw to the Desired Pressure . See Spec

s

 

Extinguish Appliance, remove Test Equipment and Secure Test Nipple .

 

* Check Valve & Burner for Correct Operation & check Fire for Gas Leaks .

 

Adjustment of High & Low Settings Must be Carried out by a Certified Gas Fitter Only 

.

 

ADJUSTMENT OF THE PILOT—

FLAME              (BOTH SG & EG)               (Only to be Adjusted by Gasfitter)   

 

Note: 

When the Base screw is removed, gas will leak from the out let, ensure that the pilot is not adjusted 

or the screw is removed when the fire is burning.

 

• 

Adjustment of Pilot 

-

 3 Flame : Unscrew Base Screw  as shown in Diagram 2  .

 

• 

Insert  a  Screw  Driver  as  shown  in  Diagram  3  and  adjust  the  Adjustment  Screw  up  inside  the  3 

Flame Pilot to adjust the Flame Height .

 

• 

The Flame must always be passing over the Electrodes &/or File Tube on either side .

 

• 

Replace the Base screw and check for leaks.  

 

3 Flame Pilot in

 

Assembled State

 

Correct Operation of

 

3 Flame Pilot

 

3

 

2

 

Note: to Gas Fitters

 

The 3 flame pilot may need adjustment 

after a period of running time on set up  
as  the  increase  in  heat  in  the  fire  will 

induce  a  higher  draft  in  the  fire,  and 
may  pull  in  flame  away  from  the  File 
Tube causing the fire to shut down.

 

Gas 

Test 

Nipple 

for SG 

Burn-

1

 

Summary of Contents for SG-EG 600 Twin

Page 1: ...tified Warmington installer or an approved NZHHA installation technician See www homeheat co nz members for a certified NZHHA SFAIT Installer in your area A licenced certified gas fitter and licenced...

Page 2: ...from inside the building to the outside A lower pressure in the building may induce a draft down the flue system and back into the building causing the fire to smoke or spill into the building Care n...

Page 3: ...win LPG Nominal Pressure kPa 2 75 kPa 2 75 kPa 2 75 kPa 2 75 kPa 2 75 kPa Nominal Injector Size mm 4 X 1 1mm 4 X 1 2mm 4 X 1 3mm 4 X 1 0mm 4 X 1 0mm Max Supply Pressure kPa 3 0 3 0 3 0 3 0 3 0 Min Sup...

Page 4: ...the Data Plate is correct for the available supply LPG or NG A Copper Gas supply capable of supplying the correct MJ h should be brought into the rear of the Installation Cavity through the hole prov...

Page 5: ...als onto the Bottom Row Each Coal randomly positioned with the Torn roughest Face Outward Ensure Coal positioning does not directly block the 3 Flame Pilot The placement of the Coals Logs may vary to...

Page 6: ...Dimension are in mm 6 SG 600 700 780 900 1100 twin burner Burner Only Installation Guide Only Traditional Classic Grate Pure Grate Installation to comply with current standards When installing a fitte...

Page 7: ...ng the Switch in a Depressed State repeat steps 2 3 if neces sary Once the Pilot Flame is lit hold this position for 3 5 seconds release from the Depressed State before setting the Flame Control to Fu...

Page 8: ...ire for Gas Leaks Adjustment of High Low Settings Must be Carried out by a Certified Gas Fitter Only ADJUSTMENT OF THE PILOT 3 FLAME BOTH SG EG Only to be Adjusted by Gasfitter Note When the Base scre...

Page 9: ...nsion are in mm 9 EG On Off 600 700 780 900 1100 twin burner Burner Only Installation Guide Only Traditional Classic Grate Pure Grate NOTE IMPORTANT INFORMATION FROM THE STANDARD Installation to compl...

Page 10: ...kPa value in the Table for maximum output NOTE If setting the Pressure is required it is to be carried out by a Certified Gas Fitter If adjustments are necessary remove the dust cap on the control val...

Page 11: ...pat tern and glow During the Initial Burning in period some smoke and smell may be experienced the appliance should be run in a well ventilated room until these dissipate Test Point Inlet Modulator Ha...

Page 12: ...ch 2021 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm 12 ON OFF SWITCH SIT 840 WIRING D...

Page 13: ...nsion are in mm 13 EG Hi Low 600 700 780 900 1100 twin burner Burner Only Installation Guide Only Traditional Classic Grate Pure Grate NOTE IMPORTANT INFORMATION FROM THE STANDARD Installation to comp...

Page 14: ...e NOTE If setting the Pressure is required it is to be carried out by a Certified Gas Fitter If adjustments are necessary remove the cap The Pressure Adjustment Screw and Nut are on the Front Side of...

Page 15: ...e their full flame pattern and glow During the Initial Burning in period some smoke and smell may be experienced the appliance should be run on the high position in a well ventilated room until these...

Page 16: ...h 2021 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm 16 HIGH LOW SWITCH SIT 845 WIRING...

Page 17: ...on are in mm 17 EG with remote 600 700 780 900 1100 twin burner Burner Only Installation Guide Only Traditional Classic Grate Pure Grate NOTE IMPORTANT INFORMATION FROM THE STANDARD Installation to co...

Page 18: ...ccept The days of the week will begin to flash Setting the day of the week function Press and release the or button to change the day of the week to the following or previous day Press and hold the or...

Page 19: ...of the week press OK First period s start time The display will indicate P1 on the top The Hour and AM PM settings will now flash To set the P1 starting time Press and release the or button to increa...

Page 20: ...le Play Store https play google com store apps details id com millec intelligythermostatmkii For instructions on how to push the appliance to your Wi Fi please go to the Warmington website and find de...

Page 21: ...nite first and once this is on it will ignite the main burner Pressing and releasing the power button again will switch off the appliance When the appliance is turned on the gas fire will be set to me...

Page 22: ...essure is required it is to be carried out by a Certified Gas Fitter If adjustments are necessary remove the cap The Pressure Adjustment Screw and Nut are on the Front Side of the Gas Control Valve sh...

Page 23: ...lame pattern and glow During the Initial Burning in period some smoke and smell may be experienced the appliance should be run on the high position in a well ventilated room until these dissipate DIAG...

Page 24: ...2021 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm 24 FULLY MODULATING SIT 845 WIRING...

Page 25: ...rve the following precautions associated with any heating appliance or open fire Do not cover or restrict the fireplace upper or lower vents in any way as this may result in a build up of hazardous ga...

Page 26: ...serviced annually and any service operation must be carried out by a qualified service person WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING A...

Reviews: