Alarm
Code
Fault
Possible Cause(s)
Suggested Action(s)
Action By
User
Engineer
TP
Low Ambient Temperature Warning
The ambient temperature is too low.
Test the operation of the ambient
temperature sensor and re-
connect/replace if necessary.
E04
Electric Overheat Protection
The compressor is overloaded.
Check the operation of the
refrigeration circuit in terms of
gas pressure and charge.
E08
Communication Error
There is a communication error between the
controller and the unit.
Check the wiring and
connections between the
controller and the unit.
E11
High Pressure Protection
The high pressure switch in the refrigeration
circuit has been tripped.
Check the operation of the high
pressure switch and refrigeration
circuit in terms of gas pressure.
E12
Low Pressure Protection
The low pressure switch in the refrigeration
circuit has been tripped.
Check the operation of the low
pressure switch and refrigeration
circuit in terms of gas pressure.
E19
Primary Anti-freezing Protection
The ambient temperature is low.
Test the operation of the ambient
temperature sensor and re-
connect/replace if necessary.
E29
Secondary Anti-freezing Protection
The ambient temperature is low.
Test the operation of the ambient
temperature sensor and re-
connect/replace if necessary.
E032
Low Flow Error
There is not enough flow in the heating circuit.
Check the plumbing circuit for
blockages or air, valves are open
and the operation of the
circulating pump.
E051
Compressor Overload
The compressor is overloaded.
Check the operation of the
refrigeration circuit in terms of
gas pressure and charge.
E171
Anti-freezing Protection
There is not enough flow in the heating circuit.
Check the plumbing circuit,
valves and operation of the
circulating pump.
F031
DC Fan Motor 1 Error
There is no connection between the fan module
and motor.
The fan motor is in locked rotor state.
Check the connection between
the fan module and motor.
Replace the fan motor.
F032
DC Fan Motor 2 Error (AS03 models only)
There is no connection between the fan module
and motor.
The fan motor is in locked rotor state.
Check the connection between
the fan module and motor.
Replace the fan motor.
Summary of Contents for Air Source A-Series
Page 35: ...Page 33 Figure 26 Heating DHW Schematic Figure 27 Heating Only Schematic...
Page 60: ...Page 58 This page is intentionally left blank...
Page 61: ...Page 59...
Page 62: ...Page 60 This page is intentionally left blank...
Page 64: ...Page 62...
Page 65: ...Page 63...
Page 66: ...Page 64...
Page 67: ...Page 65...
Page 68: ...Page 66...
Page 69: ...Page 67...
Page 70: ...Page 68...
Page 71: ...Page 69...
Page 72: ...Page 70...
Page 73: ...Page 71...
Page 74: ...Page 72...
Page 75: ...Page 73...