![WarmFlow Air Source A-Series Manual Download Page 45](http://html1.mh-extra.com/html/warmflow/air-source-a-series/air-source-a-series_manual_3398977045.webp)
Page 43
Table 13 Thermal Disinfection Parameters
Parameter
Name
Range
Default
Description
G01
Setpoint
60~70°C
70°C
Hot water thermal disinfection target
temperature
G02
Time of Duration
0~60min
0min
Duration of thermal disinfection cycle
(0 is off)
G03
Start Time
0~23h
0h
Time when thermal disinfection is on
G04
Work cycle
1~30days
7days
Thermal disinfection cycle schedule
(default is once every 7 days)
Table 14 Temperature Parameters
Parameter
Name
Range
Default
Description
R01
Hot Water
Setpoint
R06~R07
55°C
Hot water target setpoint
R02
Heating Setpoint
R08~R09
40°C
Heating target setpoint
R03
Cooling Setpoint
R08~R09
12°C
Cooling target setpoint
R04
Power-on Return
Difference
0.5~10°C
2°C
Hysteresis differential for heating and
cooling setpoint
R05
Standby Temp
Difference
*
2°C
Temperature difference above the hot
water setpoint to return to standby mode
R06
Min Hot Water
Setpoint
*
40°C
Minimum hot water setpoint allowed
R07
Max Hot Water
Setpoint
*
65°C
Maximum hot water setpoint allowed
R08
Min Heating
Setpoint
*
20°C
Minimum heating setpoint allowed
R09
Max Heating
Setpoint
*
50°C
Maximum heating setpoint allowed
R10
Min Cooling
Setpoint
*
12°C
Minimum cooling setpoint allowed
R11
Max Cooling
Setpoint
*
20°C
Maximum cooling setpoint allowed
R12
Electric Heating
0/1/2
00
Electric Heating Function, 0 for not used,
1 for in-line heater, 2 for tank immersion
R13
Electric Heater
Start Difference
*
5°C
Hysteresis differential for electric heater
R14
Electric Heater
Start AT
*
2°C
Outside temperature below which the
electric heater is enabled
R15
Delay of Electric
Heater
*
30mins
Delay time for electric heater to start as
outside temperature falls below R14
R16
Electric Heater
Start at Once AT
*
-5°C
Outside temperature below which the
electric heater starts without delay
Summary of Contents for Air Source A-Series
Page 35: ...Page 33 Figure 26 Heating DHW Schematic Figure 27 Heating Only Schematic...
Page 60: ...Page 58 This page is intentionally left blank...
Page 61: ...Page 59...
Page 62: ...Page 60 This page is intentionally left blank...
Page 64: ...Page 62...
Page 65: ...Page 63...
Page 66: ...Page 64...
Page 67: ...Page 65...
Page 68: ...Page 66...
Page 69: ...Page 67...
Page 70: ...Page 68...
Page 71: ...Page 69...
Page 72: ...Page 70...
Page 73: ...Page 71...
Page 74: ...Page 72...
Page 75: ...Page 73...