WARMBOARD COMFORT SYSTEM  //  GAS

Once the system is plumbed and pressure tested with 
air (T&M Installation Guide), the next step is to fill the 
system with water and purge the air in the lines.

Air in a closed loop heating system can create noise 
and inhibit the flow of water. Follow these steps to 
save hours or days of frustration.

 

Purge Air, Fill with Water

Follow these steps to fill and purge air the system. 
This should be done one manifold at a time. In this 
example, we’ll begin with Manifold 1 (illustration).

 

f

Thread a discharge hose on to valve 

A

,  

and ensure the other end of the hose reaches 
the exterior of the house (or drain)

 

f

On valve 

A

, make sure the ball valve is closed  

and the hose bib is open

 

f

Close all hose bibs and ball valves on  
the remaining manifold return lines (

B

C

)

 

f

On the supply side, close the hose bib  
and open ball valve 

D

 

f

To fill Warmsource and the Manifold 1 loops  
with water (city or well supply), lift the fast fill lever 
on the pressure reducing valve 

E

 

f

Check each loop flow meter on Manifold 1 and 
confirm good flow is taking place. You may need to 
open the loop flow restrictors (pg. 14, step 4)

 

f

Continue filling the system with water for 10–15 
minutes until air cannot be seen or heard escaping 
the hose

 

f

Close the fast fill lever, then slowly close hose bib 

A

 

f

Manifold 1 is now complete. Repeat this process for 
each manifold (

B

C

)

 

f

Once complete, ensure the pressure gauge located 
inside Warmsource reads 12–18 PSI

Propylene Glycol

In some situations, it may be necessary to add 
propylene glycol to prevent freezing. To do this,  
open ball valve 

D

 and add via the hose bib.  

Use the manufacturer’s recommendation for the 
correct mix (generally 10-30%). 

ONLY

 use propylene 

glycol for freeze protection.

To fill the system with a propylene glycol/water 
solution, we recommend a Liberty 331 Portable 
Transfer Pump, or equivalent (homedepot.com).  
To maintain the propylene glycol feed for many years, 
we recommend the Axiom MF200 Pressure Pal.

FILLING & PURGING

Reference the Lochnivar Noble Manual (pg. 59) 
for allowable mineral levels and quality of the 
water. Filtered water or a corrosion inhibitor may 
be required.

D

*Size according on WCS Design Drawings

A
B
C
D
E
F
G

3/4

" Combo ball valve/hose bib*

3/4

" Combo ball valve/hose bib*

3/4

" Combo ball valve/hose bib*

1/4

" Combo ball valve/hose bib

Fast fill lever/pressure reducing valve

Backflow preventer

1/2

" ball valve

C

A

B

E

F

G

Manifold 1

Manifold 2

Manifold 3

Manifold 1

Manifold 3

Manifold 2

SUPPLY

RETURN

Summary of Contents for Warmsource

Page 1: ...For use with Warmsource and Warmsource Flex natural gas boiler Warmsource and Warmsource Flex propane gas boiler WARMBOARD COMFORT SYSTEM 0622 Installation Guide...

Page 2: ...no programming or commissioning and water temperatures are calibrated using our Indoor Reset algorithm 7 DO NOT adjust any boiler settings without consulting Warmboard Changes made through the boiler...

Page 3: ...S f Install tubing some loops before walls and use the provided labels to keep track of loops and zones f Frame walls roof sheeting f Install tubing manifolds some loops f Install all 110 volt electri...

Page 4: ...up water for evaporation f Backflow preventer required by code in many jurisdictions it prevents water in the closed loop system from mixing with the domestic water f 11 4 combo ball valve hose bib f...

Page 5: ...3 48 2 121 4 2 281 2 33 27 33 121 2 Pressure Relief Valve Mounting Bracket Air Vent r Exhaust Air Intake ensate right Gas right Supply back Return front 9 43 8 3 48 9 43 8 3 48 2 121 4 2 281 2 33 27...

Page 6: ...5 81 2 21 4 151 2 51 2 91 4 110K 150K 199K 171 2 11 2 199K 150K 23 4 91 4 113 4 121 2 151 4 21 2 91 4 111 4 13 16 21 4 151 2 171 2 Bottom View 80K Top View 80K 80K 5 81 2 21 4 151 2 11 2 51 2 91 4 110...

Page 7: ...depicts the space necessary for piping and mechanical components The minimum depth is 40 for access and serviceability Electrical Requirements f Warmsource boiler 160W Warmsource pump 30 165W varies...

Page 8: ...res two individuals to move safely Connections f Connect the PVC intake and exhaust lines gas line condensation discharge line and pressure relief discharge line per the Lochnivar Noble Manual f Plumb...

Page 9: ...er field supplied 9 17 24 2 Supply back Return front Mounting Bracket 43 8 Pressure Relief Valve Air Vent Air Exhaust Air Intake Condensate Gas 1 11 4 Copper field supplied 9 17 24 2 Supply back Retur...

Page 10: ...8 18 121 2 151 4 21 4 151 2 11 2 17 80K 80K 23 4 5 9 110K 23 4 15 150K 23 4 91 4 113 4 18 18 121 2 151 4 5 81 2 17 21 4 151 2 11 2 41 4 81 2 17 43 4 81 2 80K 199K 150K 23 4 91 4 113 4 18 18 18 121 2 1...

Page 11: ...ecessary for piping and mechanical components The minimum depth is 40 for access and serviceability Electrical Requirements f Warmsource boiler 160W Warmsource pump 30 165W varies by heat load Smart R...

Page 12: ...ure relief discharge line per the Lochnivar Noble Manual f Plumb the cold water line to the backflow preventer and the pressure reducing valve WCS Design Drawings f Plumb Warmsource Flex to the boiler...

Page 13: ...filling the system with water for 10 15 minutes until air cannot be seen or heard escaping the hose f Close the fast fill lever then slowly close hose bib A f Manifold 1 is now complete Repeat this pr...

Page 14: ...Warmsource will reach the target temperature in about 10 minutes f Step 4 Return to each manifold and adjust the flow rates of each loop 1 Unthread and discard the white caps from the return side of t...

Page 15: ...ur WCS Design Drawings Controls Warmboard Controls consist of the following f 110 volt thermostats one per heating zone f 110 volt Manifold Controller one per manifold f 24 volt solenoid valve loop ac...

Page 16: ...to behave inaccurately If there are any discrepancies regarding the thermostat or zoning contact us immediately f Remove the appropriate thermostat from the box f Grip the face of the thermostat on th...

Page 17: ...inal connection AC1 Fan on the Smart Reset Controller SRC f Connect the wires from the AC unit to the terminal block accordingly RC 24v power red wire Y Cooling Call yellow wire G Fan green wire f To...

Page 18: ...nutes the green lights will turn blue indicating that the actuators have opened and water is flowing to the zone f If something does not appear to be working properly consult your Warmboard Engineered...

Page 19: ...EXCLUDED FAILURE TO INSTALL WARMBOARD PRODUCTS ACCORDING TO MANU FACTURER S INSTRUCTIONS WILL VOID ALL APPLICABLE WARRANTIES IT IS EXPRESSLY UNDERSTOOD THAT WARMBOARD IS NOT RESPONSI BLE FOR ANY CONSE...

Reviews: