2016156_b•en•2020-02-01

We reserve the right to make technical changes

4

KNX SA 8M230 REG

X5

X1

X6

   

F1

6,3 AT H

L
N

PE

Supply line

230 V AC, 

50/60 Hz, 16 A, 

3 x 1.5 mm

2

   

F2

6,3 AT H

     F1

6,3 AT H

     F2

6,3 AT H

M∼

M∼

Motor 1

sun shading system

Motor 2

sun shading system

1

3

2

BU BK BN GNYE

N

1

3

2

BU BK BN GNYE

PE

N

PE

M∼

Motor 3

sun shading system

1

3

2

BU BK BN GNYE

N

PE

M∼

M∼

Motor 5

sun shading system

Motor 6

sun shading system

1

3

2

BU

BK BN GNYE

N

1

3

2

BU

BK BN GNYE

PE

N

PE

M∼

Motor 7

sun shading system

1

3

2

BU

BK BN GNYE

N

PE

M∼

Motor 8

sun shading system

1

3

2

BU

BK BN GNYE

N

PE

M∼

Motor 4

sun shading system

1

3

2

BU BK BN GNYE

N

PE

KNX

-

KNX+

-

+

-

+

N

ATTENTION:

 

Only one motor can be connected per 

motor terminal set. 

If interconnected, the motor will 

be damaged!

The total power per fuse must not 

exceed 1000 VA.  

All motor lines 

H05-RR-F 4 G 0.75 black, 

type WAREMA

All bus lines 

YCYM 2×2×0,8 mm 

KNX Bus

KNX Bus

M1.1

M1.2

M2.1

M2.2

X2

L

M3.1

M3.2

M5.1

M5.2

M6.1

M6.2

M7.1

M7.2

M4.1

M4.2

M8.1

M8.2

KNX SA 6M230 REG

X5

X1

X6

     F1

6,3 AT H

     F2

6,3 AT H

KN

X-

KNX+

N

M1.1

M1.2

M2.1

M2.2

X2

L

M3.1

M3.2

M4.1

M4.2

M5.1

M5.2

M6.1

M6.2

Motor allocation KNX SA 6M230 REG

Fig. 5 

Connection example KNX SA 8M230 REG