background image

3

warema_2051514_alhb_en_v2•2022-07-01

We reserve the right to make technical modifications

Technical data

BACnet 4M230.8I AP

min.

typ.

max.

Unit

Operating voltage

198

230

253

V AC

Mains frequency

50

50

60

Hz

Power consumption in standby 

mode at 230 V AC

0.7

-

2.3

W

Output per drive*

Switching capacity 230 V AC/

cos φ = 0.6

500

VA

*The total power per fuse must not exceed 1000 VA.

BACnet interface

Protocol

BACnet MS/TP

Address range for BACnet

0 - 255 (0x00 to 0xFF)

Bus interface

RS485 (two-wire bus) with 

potential equalisation in bus/

line topology, terminate with 

120 Ω (

see Fig. 5, terminal 

X11

) and activate BIAS resis-

tors in the router.

Transmission format

8 N 1

BACnet device profile

BACnet Application Specific Controller (B-ASC)
BACnet MS/TP in accordance with ISO 16484-5:2017
BACnet Protocol Revision 16

Inputs, local operating elements

Current, active

0.5

1

1.5

mA

Ambient conditions

Operating temperature

0

50

°C

Storage temperature

0

70

°C

Humidity 

(not condensing)

10

40

85

%F

rel

Degree of soiling

2

Connection

Connecting line 

Spring terminal U/Contact

Permissible line cross-section

max. 2.5 mm²

Stripping length

min. 8 mm

Motor outputs

Spring terminals

Permissible line cross-section

max. 2.5 mm²

Stripping length

min. 8 mm

Inputs

Spring terminals

Permissible line cross-section

max. 2.5 mm²

Stripping length

min. 8 mm

BACnet interface

Spring terminals

Permissible line cross-section

0.6 - 0.8 mm 

 

Stripping length

5 - 6 mm

Housing

Dimensions

See Fig. 4

Surface-mounted housing 

degree of protection

IP30

Safety class  

(PE is looped through)

I

Miscellaneous

Conformity

 

Specified under  

www.warema.de/ce

This device complies with the EMC directives for use in 

residential and commercial areas.

Article numbers

BACnet 4M230.8I AP

2047065

Strain relief set  

for surface-mounted hous-

ing

1002236

WAREMA Renkhoff SE

Hans-Wilhelm-Renkhoff-Strasse 2

97828 Marktheidenfeld

Germany

Fuse protection

BACnet 4M230.8I AP

Quan-

tity

Fuse protection

BACnet 4M230.8I AP

1 x

6.3 AT H

3 ‒ 4 mm

158 mm

119 mm

132 mm

180 mm

60 mm

Fig. 4 

Surface-mounted housing dimensions

Summary of Contents for BACnet 4M230.8I AP

Page 1: ...annot be assumed the device must not be started or must be deactivated This assumption is justified if the housing or the connecting lines show signs of damage the device is no longer working ARNING W It is important to comply with the following points in the interest of personal safety Children may not play with the operating elements of the control unit or the remote control Store remote control...

Page 2: ...ed LED Communication error CRC ERROR Red LED Communication error Framing ER ROR Red LED Incomplete frames Red LED Input bridged Yellow LED Output active Yellow LED Maintenance There are no parts inside the device that require mainte nance In the event of a malfunction the built in miniature fuses should only be replaced by a certified electrician Liability Failure to comply with the product inform...

Page 3: ...age temperature 0 70 C Humidity not condensing 10 40 85 Frel Degree of soiling 2 Connection Connecting line Spring terminal U Contact Permissible line cross section max 2 5 mm Stripping length min 8 mm Motor outputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm Inputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm BACnet ...

Page 4: ...B YCYM 2 2 0 8 mm Bus Bus 0 V Bus A Bus B 0 V to next bus device 2 PE N L connecting line 230 V AC 50 60 Hz 16 A 3 x 1 5 mm All bus lines from previous bus device Attention Only one motor can be connected per motor terminal set If interconnected the motor will be damaged The total power of all 4 outputs per fuse must not exceed 1000 VA All motor lines H05 RR F 4 G 0 75 BK type WAREMA All push butt...

Reviews: