warema_2051514_alhb_en_v2•2022-07-01
We reserve the right to make technical modifications
4
Jumper
6,3 AT H
250 V / 5x20mm
2 3
1
M∼
Motor 1
2 3
1
M∼
Motor 2
2
3
1
M∼
Motor 3
2
3
1
M∼
Motor 4
sun shading system
sun shading system
sun shading system
sun shading system
N
PE
N
PE
N
PE
N
PE
BU
GNYE
BK BN
BU
GNYE
BK BN
BU
GNYE
BK BN
BU
GNYE
BK BN
Bus A -
Bus B +
YCYM 2×2×0.8 mm
Bus
Bus
0 V
Bus A -
Bus B +
0 V
to next bus device
2
PE
N
L
connecting line
230 V AC,
50/60 Hz, 16 A,
3 x 1.5 mm²
All bus lines
from previous bus device
Attention:
Only one motor can be connected
per motor terminal set!
If interconnected, the motor
will be damaged!
The total power (of all 4 outputs)
per fuse must not
exceed 1000 VA.
All motor lines
H05-RR-F 4 G 0.75 BK,
type WAREMA
All push button lines
JY(St)Y 2×2×0.8 mm
Max. line length 200 m
for interference-proof routing,
use a twisted paired line.
Fig. 5
Connection example BACnet 4M230.8 AP