Walther 979429.02 Operating Manual Download Page 12

Rev. 1.2

 

Operating Manual 979429.02 

Page 12 of 13 

 

 

 

Walther Systemtechnik GmbH 

– D 76726 Germersheim 

Telefon: +49 (0)7274-7022-0 Telefax: +49 (0)7274-7022-91 
http://www.walther-2000.de 

– [email protected] 

 

6.2  P.I.D. Programming  

 

Menu

 

Selection 

 

Description of Selection 

 

Default

 

 

0.1 -99.9 (%) 

Input value proportional term of P.I.D. control 

5.0 

 

2 - 1999 

Input value integral term (time value) of P.I.D. control 

100 

 

0 - 399 

Input value of differential term of P.I. D. control 

20 

 

0.0 - 1.0 

Input value overshoot suppression  

0.2 

 

2 - 199 

Input value of a proportional cycle. Usual value at SSR (voltage-puts output) = 2, with use 

of relay outlet J2 8relay contact-output) = 5-15 

 

0 - 3 

Digital filter factor 

 

 

After selecting  

 , confirm your menu setting by pushing 

.. 

You will now 

automatically return to the menu selection or the control mode.

 

 

 

6.3  Function "Automatic Self-Adjustment" (Autotuning) 

The  control  unit  979429.02  has  a  program  that  automatically  finds  the  optimal  P.I.D.  settings  of  the 
connected load. For this purpose it is necessary that the control unit is ready-to-operate, the load is clamped 
on, and an uncritical set value for temperature is already set. 

 

CAUTION 

When  the  auto-tuning  function  is  used,  the  control  unit  runs  through  one  or  several 
control cycles in order to determine the parameters. In doing so, strong deviations from 
the set value may appear. Take this into consideration when setting the set value. 

 

Process 

Result  

Simultaneously  press  the  buttons   

  and 

hold for approx.4 seconds.  

The  red  LED  (AT)  flashes.  The  process  is  finished 
when AT stops blinking.  

In  order  to  turn  off  auto-tuning  earlier,  press  the  arrow  button   

  for  approx.  4  seconds  until AT  stops 

blinking. The previous settings remain unchanged.   
 

 

Access to these parameters is obtained by pressing 

"SET"

 and then entering the code 

0036. 
 
Use  the  table  below  for  the  settings  or  corrections  of  the  P.I.D.  temperature  values,  after 
you have selected the setting 1 or 2 ac

cording to the parameter table “Basic Settings” as 

operating  mode  under 

OUTY

.  We  recommend  defining  a  basic  setting  beforehand  by 

using the auto-tuning function.

 

Summary of Contents for 979429.02

Page 1: ...troller 230 V AC Article Number 979429 02 NOTE Please read this Operating Manual carefully before first using the device and strictly adhere to the instructions This device may only be worked with and...

Page 2: ...5 3 Description of Function 6 3 1 Purpose of the Device 6 3 2 Technical Data 6 4 Initial Start Up 7 4 1 Mounting and Installation 7 4 2 Operating and Display Elements 7 4 3 Interfaces 8 4 4 Wiring Dia...

Page 3: ...declaration loses its validity Manufacturer Walther Systemtechnik GmbH Hockenheimer Stra e 3 D 76726 Germersheim Description Universal Temperature Controller Article Number 979429 02 We declare that t...

Page 4: ...er particularly useful information No dangerous situation 2 Safety 2 1 General Information The construction of this device is according to the latest technology and is absolutely reliable The individu...

Page 5: ...e of the content of this operating manual the user follows the instructions and notes contained in this operating manual the user does not rebuild or make changes on parts of the device without prior...

Page 6: ...ined by the employed sensor type Simple operation and parameterization as well as useful additional functions such as recognition of sensor damage with automatic power cut off alarm output 3 completel...

Page 7: ...nect the consumers relays to the described clamps see p 9 5 3 Connect the control voltage as described check voltage beforehand see p 9 5 3 Parameterize the control unit according to your requirements...

Page 8: ...resistance Cable lengths of up to 50 meters measuring lead can be realized without intermediate transmitter min 3x0 22mm Inlets Control Voltage The supply voltage for the controller is 230V AC 50Hz s...

Page 9: ...easuring range Turn off value Temperature Relays J2 90 0 After selecting confirm your menu settings by pushing SET You will then automatically return to the menu selection or to the control mode Note...

Page 10: ...e active display flashes confirm with SET The display will now switch into the setting mode of the selected menu in this case the setting of the sensor types to be connected The upper display PV will...

Page 11: ...P I D outlet without voltage pulse function only on off cycled 2 Outlet relay programmable as in Mode 0 additionally activated SSR P I D outlet at clamps 6 and 7 voltage impulse outlet approx 10V 3 S...

Page 12: ...I D settings of the connected load For this purpose it is necessary that the control unit is ready to operate the load is clamped on and an uncritical set value for temperature is already set CAUTION...

Page 13: ...1 General Information NOTE First check all supply lines for connectivity and serviceability In case of serious problems that cannot be resolved please contact the Walther Systemtechnik GmbH customer s...

Reviews: