New Installation
Positioning the chargers
The Primary charger communicates
with the Secondary chargers through
a cabling system that connects the
chargers in a chain: one charger
is connected to the next one.
Chargers at the beginning and end
of the chain must be configured
as Terminating (T) chargers
Chargers between the terminating
chargers must be configured as non-
terminating (NT) chargers
Each charger includes an electric
element that defines whether it is a T
or NT charger
1.
2.
3.
4.