Gas Conversion and Specifications
26
- UK Only:
Category:
II
2H3P.
Flue Type:
A
1.
*
Measure burner operating pressure at target top hob manifold test point with target top burner
(Inner and outer ring) operating at full setting. Operating pressure is ex-factory set through
appliance regulator and not to be adjusted, apart from when carrying out gas conversion, if
required. (Refer to details in this section for information).
Natural Gas (G20)
Propane (G31)
Main Burner Injector (Inner Ring)
Ø 1.70mm
Ø 1.10mm
Main Burner Injector (Outer Ring)
Ø 2.60mm
Ø 1.55mm
Pilot Burner Injector
0.35 0.25
Burner Aeration Screw X (Inner)
25mm 20mm
Burner Aeration Screw Y (Outer)
28mm 25mm
Low Fire Adjustment
2
1
/
2
turns out (ccw)
1
¾
turn out (ccw)
Supply Pressure
20 mbar
37 mbar
Burner Operating Pressure (*)
9.9 mbar (*)
26.8 mbar (*)
Gas Regulator Cap Screw