27
Technical data
ENG
11.4 Switch-on current
Luminaire
Value
HIAL 14000/...
DALI/CLO
DALI
1-10V
EA
F
53 A; t = 300 µs;
Number of luminaires
with circuit breaker
switch/MCB
“16 A type B”: Max. 8
HIAL 16000/...
HIAL 18000/...
HIAL 25000/...
DALI/CLO
13 A; t = 1320 µs;
Number of luminaires
with circuit breaker
switch/MCB
“16 A type B”: Max. 7
HIAL 20000/...
HIAL 30000/...
DALI/CLO
DALI
F
HIAL 33000/...
DALI
F
HIAL 37000/...
DALI
HIAL 20000/...
1-10V
170 A; t = 220 µs;
Number of luminaires
with circuit breaker
switch/MCB
“16 A type B”: Max. 3
HIAL 20000/...
HIAL 30000/...
EA
75 A; t = 570 µs;
Number of luminaires
with circuit breaker
switch/MCB
“16 A type B”: Max. 2
Tab. 10: Switch-on current.
11.5 Classifications
Designation
Value
Protection class
I
Degree of protection IP 65
Operating mode
Continuous
operation
Tab. 11: Classifications.
11.6 Symbols
Symbol
Explanation
Protection class
I
Operation with protective
earth conductor
CE conformity mark
Luminaire with limited
surface temperature for
production facilities sub-
ject to fire hazards
Disposal in accordance
with the European WEEE
Directive
Tab. 12: Symbols.