2.4
WDT Variables and their Limits
Low Limit
High Limit
Conductivity menu
PPM Conversion Factor
0.200 ppm/µS/cm 1.000
ppm/µS/cm
Interval Time (sampling)
5 minutes
24:00 hours
Duration Time (sampling)
1 minute
59 min: 59 sec
% Calibration Range
-50
+50
Temperature Menu
No variables
Bleed Menu
Set Point
0 µS/cm
10,000 µS/cm
Dead Band
5 µS/cm
500 µS/cm
Bleed Limit Time (set in hours/minutes)
1 minute
8 hrs: 20 min
(enabled)
0=unlimited (disabled)
Feed Menu
Feed Lockout Timer (Mode A)
1 second
99 min: 59 sec
Percent of Bleed (Mode B)
5 %
99 %
Feed Time Limit (Mode B)
1 minute
99 min: 59 sec
Percent of Time (Mode C)
5 %
99 %
Feed Cycle Time (Mode C)
10 minutes
59 min: 59 sec
Time per Contact (Mode D)
1 second
59 min: 59 sec
÷ Contacts by (Mode D)
1 contact
100 contacts
Time Limit (Mode D & E)
1 minute
99 min: 59 sec
Time/Vol (Mode E)
1 second
59 min: 59 sec
Vol to Initiate Feed (Mode E)
1
9,999
WM1 and WM2 Menus
Gallons per Contact
1 gal/contact 500
gal/contact
Liters per Contact
1 L/contact 500
L/contact
K
Factor
(Paddlewheel)
0.01 pulse/vol
999.99 pulses/vol
4-20 mA Menus
4 & 20 mA Settings
0 µS/cm
10,000 µS/cm
Access Code
New Value
0 9999
Alarms Menu*
High & Low (set to zero to disable)
1%
50%
Datalog Menu (Optional)
No variables
Config Menu (Optional)
No variables
Upgrade Menu
No variables
*Note: The Alarm relay is non-programmable. Refer to the Main Menu diagram on page 16 for the list of error
conditions that trigger the alarm relay.
3