27
Figure 13 Biocide 1 Menu
Bio 1 Add Mode
1 Week Cycle
Bio 1 Add Mode
Daily Adds
Bio 1 Add Mode
2 Week Cycle
Bio 1 Add Mode
4 Week Cycle
Bio 1
PRE BLD
HAND OFF >AUTO
2000 S 68° F
Bio 1
PRE BLD
Bio 1
Prog Bio 1 Adds
PRE BLD
Bio 1
Pre Bleed (µS) 1800
PRE BLD
Bio 1
Lockout (H) 2:00
PRE BLD
Bio 1
Bio 1 Add Mode
PRE BLD
Bio 1
10:00
ADD
Bio 1
2:00
LCK
Bio 1 OFF
Bio 1
NO FLOW
Bio 1
PENDING
Biocide 1 Menu
Possible status screens
Menu choices that appear when 1 Week Biocide
Cycle mode is selected.
Press Enter key to enter menu.
Press Exit key to exit menu.
Blinking fields may be edited with the adjust arrows.
Press Enter when modification is complete.
Use Next and Prev keys to change days in Prog.
Menu choices that appear when 2 Week Biocide
Cycle mode is selected.
Menu choices that appear when 4 Week Biocide
Cycle mode is selected.
NEXT
PREV.
ENTER
EXIT
ENTER
EXIT
ENTER
EXIT
Legend
Operation
NEXT
PREV.
Prog Bio 1 Adds
1 Sun 12:00 99
Prog Bio 1 Adds
1 Sat 12:00 0
Prog Bio 1 Adds
1 Sun 12:00 10
Prog Bio 1 Adds
1 Sun 12:00 0
Prog Bio 1 Adds
Daily A 12:00 99
Prog Bio 1 Adds
4 Sat 12:00 0
Prog Bio 1 Adds
Daily J 12:00 30
Prog Bio 1 Adds
2 Sat 12:00 0
7 days, total
14 days, total
28 days, total
up to ten times/day
(Hint: program Mode first)
1
2
3
1
1
2
3
3
3
2
1
2
1