WAGO-I/O-SYSTEM 750 XTR
Device Description 55
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
4.5.3
Supply
Table 4: Technical Data – Supply
Power supply via CAGE CLAMP
®
connectors
under laboratory conditions
+15 °C … +35 °C
for ambient operating temperature
−
40 °C … +55 °C
for ambient operating temperature
+55 °C … +70 °C
24 VDC (power supply via SELV/PELV
power supply unit)
18 V … 31.2 V (17.4 V … 31.2 V)
1)
18 V … 28.8 V (17.4 V … 28.8 V)
1)
18 V … 26.4 V (17.4 V … 26.4 V)
1)
Internal current consumption (5 VDC) 450 mA
Total current for I/O modules (5 VDC) 700 mA
Input current typ. at nominal load
(24 VDC)
280 mA
Power failure time acc. IEC 61131-2 Depending on external buffering
Efficiency of power supply typ. at
nominal load
90 %
Isolation (peak value)
510 VAC
2)
or 775 VDC power supply/DIN
rail
Rated impulse voltage
1 kV
Degree of pollution
acc. to IEC 61131-2
2
1)
Including residual ripple of 15%
2)
When performing insulation testing, observe the instructions in the manual!
Buffer for system power supply!
The system power supply must be buffered to bridge power outages. As the
power demand depends on the respective node configuration, buffering is not
implemented internally.
To achieve power outages of 1 ms to 10 ms according to IEC61131-2, determine
the buffering appropriate for your node configuration and structure it as an
external circuit.
4.5.4
Fieldbus MODBUS/TCP
Table 5: Technical Data – Fieldbus MODBUS/TCP
Input process image
max
1020 words
Output process image
max
1020 words