232 I/O Modules
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 100.15 /Seri e 750 ( WAGO-I/O-SYSTEM)/Prozessabbil d M apping/ETHER NET - EtherNet/IP - MOD BU S/TC P/PA ETH ERNET - Sondermodul e XTR N EU @ 16\mod_1374049203711_21.docx @ 126385 @ 344444 @ 1
12.2.6 Specialty Modules
In addition to the data bytes, the control/status byte is also displayed for select
I/O modules. This byte is used for the bi-directional data exchange of the I/O
module with the higher-level control system.
The control byte controls the I/O module's behavior and operation. The status
byte reports the I/O module's status. It is possible to set the counter with the
control byte or indicate a range overflow/underflow with the status byte.
The control/status byte is always in the low byte in the process image.
Information for the control/status byte development
Please refer to the corresponding description of the I/O modules for the structure
of the control/status bytes. You can find a manual with the relevant I/O module
description at:
http://www.wago.com
.
12.2.6.1 Serial Interfaces with Alternative Data Format
The process image depends on the parameterized operating mode!
The operating mode of the configurable I/O module can be set. Based on the
operating mode, the process image of these I/O modules is then the same as
that of the respective version.
The I/O modules with serial interface that are set to the alternative data format
occupy 4 bytes of user data in the input and output area of the process image, 3
data bytes and one additional control/status byte. Two words are assigned in the
process image via word alignment.
Table 270: Serial interfaces with alternative data format
Input and Output Process Image
Offset
Byte designation
Remark
High byte
Low byte
0
D0
C/S
Data byte
Control/status
byte
1
D2
D1
Data bytes