Process Image
WAGO-I/O-SYSTEM 750
750-506 2DO 24V DC 0.5A/ diagnostics
Manual
Version 1.2.0
Pos: 61 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/__ noch nicht ei nsortierte Ü berschriften müssen noch einsorti ert werden __/Prozessabbil d - Ü berschrift 1 @ 4\mod_1240983067828_21.docx @ 31942 @ 1 @ 1
4
Process Image
Pos: 62 /Serie 750 ( WAGO-I/O-SYST EM)/Prozessabbild Kl emmenbus/Hinweis: Prozessabbildmapping abhängig von FBK/PFC, ohne Status-/C ontr olbyte @ 6\mod_1256126797251_21.docx @ 43340 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the process data of some I/O modules or their variants in the
process image depends on the fieldbus coupler/controller used. Please take this
information from the section “Fieldbus Specific Design of the Process Data”
included in the description concerning the process image of the corresponding
fieldbus coupler/controller.
Pos: 63 /Serie 750 ( WAGO-I/O-SYST EM)/Prozessabbild Kl emmenbus/Digitalausg angskl emmen/Prozessabbild 750- x5xx 02 DO/D IAG @ 10\mod_1299506283577_21.docx @ 70540 @ @ 1
Table 16: Output Bits
Bit 1
Bit 0
DO 2
DO 1
DO 1
Signal state DO 1 – Digital output channel 1
DO 2
Signal state DO 2 – Digital output channel 2
Table 17: Input Bits
Bit 1
Bit 0
DIAG 2
DIAG 1
DIAG 1
0:
Normal operation, output DO 1 follows the output bit.
1:
Error at output DO 1:
a) No load connected or
b) Short circuit with GND or
c) Short circuit with 24 V or
d) Overtemperature at overload
DIAG 2
0:
Normal operation, output DO 2 follows the output bit.
1:
Error at output DO 2:
a) No load connected or
b) Short circuit with GND or
c) Short circuit with 24 V or
d) Overtemperature at overload
Pos: 64 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1