“SSH Server Settings” Page 

T

he settings for the SSH service are shown on the “SSH Server Settings” page. 

“SSH Server” Group 

Table 104

: WBM “SSH Server Settings” Page – “SSH Server” Group 

Parameters 

Explanation 

Service active 

You can enable/disable the SSH server. 

Port Number 

Enter the port number. 

Allow root login 

You can enable or inhibit root access. 

Allow password login 

Enable or disable the password query function. 

 
Click the 

[Submit]

 button to apply the changes. The changes take effect 

immediately. 

 

 

 

Summary of Contents for I/O SYSTEM 750

Page 1: ...Manual WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Controller PFC200 2nd Generation 4 x ETHERNET Extreme Version 1 7 0 valid from FW Version 04 01 10 23...

Page 2: ...84 45 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always apprecia...

Page 3: ...f the Software Package Used 20 2 4 Special Use Conditions for ETHERNET Devices 21 3 Overview 22 4 Properties 25 4 1 Hardware Description 25 4 1 1 View 25 4 1 2 Labeling 27 4 1 2 1 Production Code 27 4...

Page 4: ...t Certificates 63 5 1 3 Network Configuration 64 5 1 3 1 Host Name Domain Name 64 5 1 3 2 Routing 64 5 1 4 Network Services 68 5 1 4 1 DHCP Client 68 5 1 4 2 DHCP Server 68 5 1 4 3 DNS Server 70 5 1 5...

Page 5: ...the IP Address of the Host PC 105 8 3 Setting an IP Address 106 8 3 1 Assigning an IP Address using DHCP 107 8 3 2 Changing an IP Address Using the CBM Configuration Tool and a Terminal Program 108 8...

Page 6: ...nostics Messages via Flashing Sequences 148 11 2 1 Flashing Sequences 148 11 2 2 Example of a Diagnostics Message Indicated by a Flashing Sequence 149 11 2 3 Meaning of Blink Codes and Procedures for...

Page 7: ...198 15 2 1 2 15 Configuration of NTP Client Page 200 15 2 1 2 16 PLC Runtime Services Page 201 15 2 1 2 17 SSH Server Settings Page 202 15 2 1 2 18 DHCP Server Configuration Page 203 15 2 1 2 19 Confi...

Page 8: ...3 2 4 4 Channel Digital Output Modules with Diagnostics and Input Data244 15 3 2 5 8 Channel Digital Output Modules 244 15 3 2 6 8 Channel Digital Output Modules with Diagnostics and Input Data244 15...

Page 9: ...ncluded if necessary 1 1 Validity of this Documentation This documentation is only applicable to the PFC200 G2 4ETH XTR controller 750 8210 040 000 This documentation is only applicable from FW Versio...

Page 10: ...tooth is a registered trademark of Bluetooth SIG Inc CiA and CANopen are registered trademarks of CAN in AUTOMATION International Users and Manufacturers Group e V CODESYS is a registered trademark of...

Page 11: ...0 23 PROFIBUS is a registered trademark of the PROFIBUS Nutzerorganisation e V PNO PROFINET is a registered trademark of the PROFIBUS Nutzerorganisation e V PNO QR Code is a registered trademark of DE...

Page 12: ...nal Injury Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation w...

Page 13: ...s Documentation 13 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 Additional Information Refers to additional information which is not an integral part of t...

Page 14: ...of paths and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a...

Page 15: ...ents All changes to the coupler or controller should always be carried out by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 750 Series in Compliance with Underlying Pr...

Page 16: ...stallation of the system in a housing or switch cabinet The implementation of safety functions such as EMERGENCY STOP or safety door monitoring must only be performed by the F I O modules within the m...

Page 17: ...e protection against contact Prevent fire from spreading outside of the enclosure Offer adequate protection against UV irradiation Guarantee mechanical stability Restrict access to authorized personne...

Page 18: ...hot during operation If the device was operated at high ambient temperatures allow it to cool off before touching it Ensure proper contact with the DIN rail Proper electrical contact between the DIN r...

Page 19: ...serve the safety precautions against electrostatic discharge per DIN EN 61340 5 1 3 When handling the devices please ensure that environmental factors personnel work space and packaging are properly g...

Page 20: ...troller 750 8210 040 000 contains open source software The licence conditions of the software packages are stored in the controller in text form They can be accessed via the WBM page Legal Information...

Page 21: ...default passwords before first use This will reduce the risk of unauthorized access to your system Regularly change the passwords used This will reduce the risk of unauthorized access to your system...

Page 22: ...or IEC 61131 3 programming in CODESYS applications the controller provides 32 MB of program memory flash 128 MB of data memory RAM as well as 128 kB of retentive memory retain and flag variables in an...

Page 23: ...e CODESYS program to the data in the fieldbus process image and vice versa Direct access is not possible CODESYS V3 makes configuring the fieldbus possible A Web based management system WBM is also av...

Page 24: ...om FW Version 04 01 10 23 a DNS server a CODESYS V3 Runtime Environment Based on IEC 61131 3 programming data processing takes place on site in the controller The logical process results can be output...

Page 25: ...arking options Mini WSB 2 LED indicators power pupply Display Elements Power Supply Indicating Elements 3 Data contacts Connectors Data Contacts Local Bus 4 CAGE CLAMP connectors for power supply Conn...

Page 26: ...elements Operating Mode Switch 10 Network cable tie slot Connecting Connecting Network Cables 11 ETHERNET connectors X11 X12 Connectors Network connectors 12 Safe locking feature Mounting Inserting De...

Page 27: ...e delivery status directly after production Figure 2 Marking Area for Serial Numbers There are two serial numbers in two rows in the side marking They are left of the release tab The first 10 position...

Page 28: ...cription 1 24 V System power supply voltage 24 V 2 Field side power supply voltage UV 3 Field side power supply voltage 0 V 5 0 V System power supply voltage 0 V 6 Field side power supply voltage UV 7...

Page 29: ...ernet Settings Figure 4 Service Interface Closed and Open Flap Table 5 Service Interface Number Description 1 Open flap 2 Service interface Device must be de energized To prevent damage to the device...

Page 30: ...4 01 10 23 4 1 3 3 Network Connectors Figure 5 Network Connections X1 X2 X11 X12 Table 6 Legend for Figure Network Connections X1 X2 X11 X12 Contact Signal Description 1 TD Transmit Data 2 TD Transmit...

Page 31: ...electronic components that may be destroyed by electrostatic discharge When handling the devices please ensure that environmental factors personnel work space and packaging are properly equalized Do n...

Page 32: ...feed in Uv for field supply 2 Spring contact Potential feed in 0 V for field supply Risk of injury due to sharp edged blade contacts The blade contacts are sharp edged Handle the I O module carefully...

Page 33: ...Version 04 01 10 23 4 1 5 Display Elements 4 1 5 1 Power Supply LEDs Figure 8 Power Supply Indicating Elements Table 8 Legend for Figure Power Supply Indicating Elements Description Color Description...

Page 34: ...sing function blocks from the WAGO libraries to control the LEDs U6 Red Green Orange Off User LED 6 programmable using function blocks from the WAGO libraries to control the LEDs U5 Red Green Orange O...

Page 35: ...n 1 7 0 valid from FW Version 04 01 10 23 4 1 5 3 Network Connector LEDs Figure 10 Indicating Elements RJ 45 Jacks Table 10 Legend for Figure Indicating Elements RJ 45 Jacks Designation Color Descript...

Page 36: ...H XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 4 1 5 4 Memory Card Slot LED Figure 11 Indicating Elements Memory Card Slot Table 11 Legend for Figure Indicating Elements Memory Card Slot...

Page 37: ...ctor Switch dg_ Table 12 Mode Selector Switch Position Actuation Function RUN Latching Normal operation CODESYS V3 applications running STOP Latching Stop All CODESYS V3 applications have stopped RESE...

Page 38: ...10 gf 210 gf The button can be actuated using a suitable object e g pen You can initiate different functions using the Reset button depending on the position of the mode selector Temporarily set a fix...

Page 39: ...ard is protected by a cover flap The cover cap is sealable Memory card is not included in the scope of delivery Note the controller is delivered without memory card To use a memory card you must order...

Page 40: ...40 Properties WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 4 2 Schematic Diagram Figure 15 Schematic diagram...

Page 41: ...h Depth 71 9 mm 2 831 inch Depth from upper edge of DIN rail 64 7 mm 2 547 inch Weight 225 7 g 4 3 2 System Data dg_ Table 14 Technical Data System Data CPU Cortex A8 1 GHz Operating System Real time...

Page 42: ...nal power consumption 5 V system 510 mA Total current for I O modules 5 V system 1700 mA Supply voltage field 24 VDC SELV PELV Power supply via pluggable connector CAGE CLAMP connection Transmission v...

Page 43: ...m power supply and if necessary the field supply must be buffered to bridge power outages As the power demand depends on the respective node configuration buffering is not implemented internally To ac...

Page 44: ...inuous operation in the limit range A steady reduction in the specified buffer time is possible in continuous operation at 70 C 4 3 5 Programming dg_ Table 17 Technical Data Programming Programming CO...

Page 45: ...No direct access from fieldbus to the process image for I O modules Any data that is required from the I O module process image must be explicitly mapped in the CODESYS program to the data in the fiel...

Page 46: ...n Operating altitude above sea level without temperature derating with temperature derating max 0 2000 m 2000 5000 m 0 5 K per 100 m 5000 m Pollution degree 2 Protection type IP20 Resistance to harmfu...

Page 47: ...TH XTR controller 750 8210 040 000 Conformity Marking Ordinary Locations UL61010 2 201 The following ship approvals have been granted to the PFC200 G2 4ETH XTR controller 750 8210 040 000 DNV GL Tempe...

Page 48: ...ection half sine 25g 6 ms 1000 shocks per axis and direction half sine EN 50155 EN 61373 Random vibration Category 1 classes A and B Shock 5g 30 ms Category 1 classes A and B Environmental Requirement...

Page 49: ...5 26 IEEE C37 90 1 4 kV Surge Voltage Surge EN 61000 4 5 EN 60255 26 1 kV conductor conductor 2 kV conductor ground Conducted Disturbances Induced by High frequency Fields EN 61000 4 6 EN 60255 26 10...

Page 50: ...nnections EN 61000 4 17 EN 60255 26 15 Damped Oscillatory Waves EN 61000 4 18 EN 60255 26 IEEE C37 90 1 1 25 kV conductor conductor 2 5 kV conductor ground Voltage Dips Short term Interruptions and Vo...

Page 51: ...k 3 GHz 6 GHz 60 dB V m AV 3 GHz 6 GHz Shipbuilding Class B 80 dB V m 50 dB V m QP 150 kHz 300 kHz 50 dB V m 34 dB V m QP 0 3 MHz 30 MHz 54 dB V m QP 30 MHz 2 GHz 24 dB V m QP 156 MHz 165 MHz Shipbuil...

Page 52: ...d Test Value Conducted Emission of Interference Line Connection DC Voltage EN 61000 6 3 EN 60255 26 EN 55032 Class A 79 dB V QP 0 15 MHz 0 5 MHz 66 dB V AV 0 15 MHz 0 5 MHz 73 dB V QP 0 5 MHz 30 MHz 6...

Page 53: ...uitable external power supply unit Maximum continuous voltage 1 25 Un 5 1 1 3 Temporary DC power supply fluctuation Minimum fluctuation voltage 0 725 Un 0 6 Un must be provided by a suitable external...

Page 54: ...s two ports sharing a common IP address Two separate networks where one port has its own IP address and three ports share a common IP address Three separate networks one IP address per port plus a com...

Page 55: ...ble 29 MAC ID and IP Address Assignment for One Bridge with Four Ports Bridge MAC ID IP Addr Port MAC ID Port MAC ID Port MAC ID Port MAC ID 1 01 1 X1 02 X2 03 X11 04 X12 05 Two separate networks each...

Page 56: ...Assignment for Two Bridges with One Three Ports Bridge MAC ID IP Addr Port MAC ID Port MAC ID Port MAC ID Port MAC ID 1 01 1 X1 01 2 02 2 X2 03 X11 04 X12 05 3 03 3 Three separate networks one IP add...

Page 57: ...Four separate networks where each port has its own IP address Figure 21 Four Bridges with One One One One Ports Table 33 MAC ID and IP Address Assignment for Four Bridges with One One One One Ports B...

Page 58: ...ging these passwords on startup Change passwords Default passwords are documented in these instructions and therefore do not offer adequate protection Change the passwords to meet your particular need...

Page 59: ...ago admin All administrator wago user Supported to a limited extent user guest Display only General Rights of WBM Users The WBM users root admin and user have rights beyond the WBM to configure the sy...

Page 60: ...wago admin CODESYS user home admin wago user Normal user home user user You can configure passwords for these users via a terminal connection Change passwords Default passwords are documented in these...

Page 61: ...allow secure authentication you must replace the generic security certificate with a security certificate specific for the individual device 5 1 2 2 1 TLS Encryption When an HTTPS connection is estab...

Page 62: ...BSI Guidelines on Migration to TLS 1 2 The German Federal Office for Information Security guidelines on migration to TLS 1 2 contain compatibility matrices that show what software is comparable with T...

Page 63: ...root CA bundle form the basis for authentication of services hosted on the Internet e g email providers and cloud services The standard storage location for the root certificates is etc ssl certs ca...

Page 64: ...djust the configuration of the active DHCP server so that no host names are transferred in the DHCP response The default host name or the configured name is active again if the network interfaces are...

Page 65: ...k address or network address range are sent to the gateway address corresponding to the entry Alternatively a bridge a modem or a VPN interface can be specified in the Interface field via which all da...

Page 66: ...e controller can function as a router For forwarding network communication through a router it is necessary to note that corresponding routing entries must be provided not only for the router but also...

Page 67: ...ion of static routes the controller also supports IP masquerading This can be enabled for selected network interfaces of the controller Network data packets that depart the controller through a networ...

Page 68: ...riority is specified alphanumerically by the name of the network interface Thus Bridge1 has the highest priority followed by Bridge2 Bridge3 Wwan0 5 1 4 2 DHCP Server The controller provides the DHCP...

Page 69: ...ask The subnet mask configured in the network settings of the DHCP server for the local network concerned is passed The subnet mask and IP address determine the range of valid IP addresses on the loca...

Page 70: ...CP server This DNS server routes requests for non local names such as from the Internet to higher level DNS servers if configured and accessible The following settings are possible for the DNS server...

Page 71: ...e cloud You can specify the cloud service to use Microsoft Azure Amazon Web Services and IBM Cloud are available Figure 22 Connecting the Controller to a Cloud Service Example Data is transmitted from...

Page 72: ...our country Observe the additional documentation You can find a detailed description of the cloud connectivity software package with a controller and information on PLC programming in Application Note...

Page 73: ...ed to one or more controllers Deactivate write protection In order to be able to write data to the memory card you must deactivate the write protection using the small push switch for the write protec...

Page 74: ...T32 or NTFS If the CODESYS user admin see the section Network Network Security Users and Passwords Services and Users is supposed to be able to access files created on the memory card the memory card...

Page 75: ...erating system System selection is only permissible and possible if the firmware versions at the backup and restore times are identical If necessary skip restoring the controller operating system or m...

Page 76: ...en the time required 5 2 2 2 Restore Function The restore function is used to load the data and device settings from the memory card to the internal memory during operation The restore function can be...

Page 77: ...that the amount of data in the media sd copy directory must not exceed the total size of the internal drive Restoration only possible from internal memory If the device was booted from the memory card...

Page 78: ...opy procedures are triggered The LED above the memory card flashes yellow during the access The memory card is then ready for operation and available under media sd 5 2 4 Removing the Memory Card duri...

Page 79: ...he Submit button to apply the setting which takes effect after the next restart No files are applied from the old to the new home directory After moving the directory a project must be loaded and a bo...

Page 80: ...oject is Loaded No No No No no boot project exists Yes No no boot project exists Yes No No no boot project exists in the internal flash memory Yes Yes from memory card Yes no No Yes from internal flas...

Page 81: ...ounting rail Height dimension in the direction of the y axis vertical in nominal mounting position Depth dimension in the direction of the z axis horizontal in nominal mounting position perpendicular...

Page 82: ...n end stop in the case of vertical installation When mounting in the vertical top or vertical bottom mounting position also mount an end stop below the fieldbus node to protect the fieldbus node again...

Page 83: ...ximum total length of a fieldbus node The maximum total length of a fieldbus node without fieldbus coupler controller may not exceed 780 mm Also note the limitations of individual fieldbus couplers co...

Page 84: ...d if necessary several mounting points every 20 cm should be used in order to prevent bending and twisting torsion The geometry of the carrier rail must not be altered in order to secure the safe hold...

Page 85: ...romated slotted unslotted 210 197 114 35 15 1 5 mm steel blue chromated slotted unslotted 210 118 35 15 2 3 mm steel blue chromated unslotted 210 198 35 15 2 3 mm copper unslotted 210 196 35 8 2 1 6 m...

Page 86: ...ed for the complete fieldbus node Figure 25 Spacing The spacing creates room for heat transfer installation or wiring The spacing to cable conduits also prevents conducted electromagnetic interference...

Page 87: ...ts are sharp edged Handle the I O module carefully to prevent injury Do not touch the blade contacts Insert I O modules only from the proper direction All I O modules feature grooves for power jumper...

Page 88: ...n repair or maintenance work 6 6 1 Inserting the Controller 1 When replacing the controller for an already available controller position the new controller so that the tongue and groove joints to the...

Page 89: ...m the power supply 2 Secure the system component against unintentional restart 3 Check if the voltage is positively isolated 7 1 Power Contacts Field Supply Risk of injury due to sharp edged blade con...

Page 90: ...90 Connecting WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23...

Page 91: ...modules to be supplied with power Only connect one conductor to each CAGE CLAMP connection Only one conductor may be connected to each CAGE CLAMP connection Do not connect more than one conductor at o...

Page 92: ...ng to the component with the strictest electrical safety requirements For components which are only allowed to be supplied by SELV voltage sources these requirements are listed in the technical data M...

Page 93: ...y Filter 24 VDC HI XTR Supply Filter 24 VDC higher isolation extreme System and field supply with filtering 24 V 0 V i e fieldbus coupler controller and System Power Supply 24 VDC XTR 750 613 040 000...

Page 94: ...4 Filter module for field side power supply surge 24 VDC higher isolation without power jumper contacts extreme 750 624 040 001 5 Power supply 24 VDC fuse holder extreme 750 601 040 000 oder 750 610...

Page 95: ...FW Version 04 01 10 23 7 3 2 Supply Example Suppl Sggggggggggggggggg The system supply and the field supply shall be separated You should separate the system supply and the field supply in order to en...

Page 96: ...from FW Version 04 01 10 23 Table 43 Legend for Figure Power Supply Example Item Description 1 Power supply on the fieldbus coupler controller via external system supply module 2 Supply module 24 V 3...

Page 97: ...o achieve power outages of 1 ms to 10 ms according to IEC61131 2 determine the buffering appropriate for your node configuration and structure it as an external circuit The power demand must be determ...

Page 98: ...rantee sufficient grounding 7 4 1 2 Insulated Assembly Insulated assembly has been achieved when there is constructively no direct ohmic contact between the cabinet frame or machine parts and the carr...

Page 99: ...ro magnetic interferences to the carrier rail Figure 31 Carrier Rail Contact Example The bottom CAGE CLAMP connectors of the supply modules enable optional connection of a field side functional ground...

Page 100: ...e Shield at Ground Potential Improve shielding performance by placing the shield over a large area Higher shielding performance is achieved via low impedance connection between shield and ground For t...

Page 101: ...ure that the accuracy and interference immunity specified for the respective I O module can be achieved even in the presence of interference acting on the signal cable 7 5 4 WAGO Shield Connecting Sys...

Page 102: ...0 valid from FW Version 04 01 10 23 7 6 Connecting Network Cables Insert the RJ 45 connector of the network cable into the required network socket X1 X2 X11 X12 until you hear it click into place Then...

Page 103: ...ached locking screws have connected the electronics and field side power supply see section Connections have mounted the end module see Section Installation have performed appropriate potential equali...

Page 104: ...104 Commissioning WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23...

Page 105: ...t To determine the IP address of the host PC with the Microsoft Windows operating system using the MS DOS prompt proceed as follows 1 Open the MS DOS prompt window To do this enter the command cmd in...

Page 106: ...pecific system structure to ensure that the PC and the controller can communicate with one another using one of the available configuration tools see section Configuration Example for incorporating th...

Page 107: ...s been assigned by means of DHCP default setting it can be determined through the settings and the output of the specific DHCP server In the example figure shown here the corresponding output of Open...

Page 108: ...t CBM is given in the Section Configuration 1 Connect a PC to the ETHERNET interface X1 of the controller using an SSH terminal program 2 Start the terminal program 3 Select SSH as the connection type...

Page 109: ...6 In the Main menu use the keyboard arrow keys or numeric keypad to move to and select Networking and then press Enter Figure 37 CBM Selecting Networking 7 In the Networking menu select TCP IP and pre...

Page 110: ...4 01 10 23 9 In the menu TCP IP Configuration select IP Address and press Enter Figure 40 CBM Selecting the IP Address 10 In the menu Change IP Address enter the new IP address and confirm by clicking...

Page 111: ...roller use at least Version 6 4 1 1 dated 2015 06 29 of WAGO Ethernet Settings You can use WAGO communication cables or WAGO radio adapters or even the IP network for data communication 1 Switch off t...

Page 112: ...ally activated as the default setting 8 In the column Input enter the required IP address and if applicable the address of the subnet mask and of the gateway 9 Click on Write to accept the address in...

Page 113: ...t is performed To set temporary fixed IP addresses proceed as follows 1 Set the mode selector switch to STOP and 2 Press and hold the Reset button RST for longer than 8 seconds Execution of the settin...

Page 114: ...ter the command ping and the IP address of the controller for example ping 192 168 1 17 and then press Enter Host entries in the ARP table It may also be useful to delete the current host entries in t...

Page 115: ...ords for the WBM users Proceed as follows to change these passwords 1 Connect the controller to a PC via one of the network interfaces X1 X2 2 Start a web browser program on the PC and call up the WBM...

Page 116: ...ware Reset Restart Alternatively you can switch off the controller and switch it back on again Do not power cycle the controller after changing any parameters Some parameter changes require a controll...

Page 117: ...a and the retain variables are set to their initialization values This corresponds to the CODESYS V3 IDE Reset Cold command dg_ To perform a cold start reset set the mode selector switch to Reset and...

Page 118: ...retained The inactive system is not changed by the reset If you have any questions contact WAGO Support The controller is restarted after the controller reset Proceed as follows to reset the controlle...

Page 119: ...ailable for configuring the controller Access to the Web based management system via the PC using a web browser section Configuration Using Web Based Management WBM Access to the Console Based Managem...

Page 120: ...located within the same subnet see Section Setting an IP Address If you do not know the IP address and cannot determine it switch the controller temporarily to the pre set address 192 168 1 17 Fixed...

Page 121: ...user selected the navigation bar and the tabs of the WBM are displayed If you have disabled cookies in your web browser you can continue to use the WBM as long as you move directly inside it However...

Page 122: ...e these passwords a warning will appear each time you call up a website after logging in Figure 46 Password Reminder Table 47 User Settings in the Default State Users Permissions Default Password root...

Page 123: ...untime Configuration user Networking TCP IP Configuration TCP IP Configuration user Ethernet Configuration Ethernet Configuration user Host Domain Name Configuration of Host and Domain Name user Routi...

Page 124: ...ettings admin Users WBM User Configuration admin Fieldbus BACnet Status BACnet Status admin Configuration BACnet Configuration admin Storage Location BACnet Storage Location admin Files BACnet Files a...

Page 125: ...ons are displayed in the header of the browser window The Reboot button only appears if you are logged in as an administrator If not all tabs can be displayed in the selected width of the window a tab...

Page 126: ...e cursor is positioned over an LED The text that is displayed also contains the message that put the LED into its current status The time of the message is also shown The states displayed in the WBM w...

Page 127: ...not be displayed in a terminal window in a reasonable way and are not necessary for initial startup are not displayed 1 Connect a PC to the ETHERNET interface X1 of the controller using an SSH termina...

Page 128: ...ny parameters Some parameter changes require a controller restart for the changes to apply Saving changes takes time Do not power cycle the controller to perform a restart i e changes may be lost by s...

Page 129: ...e the software version To configure the controller use at least Version 6 4 1 1 dated 2015 06 29 or newer of WAGO Ethernet Settings You must select the corresponding interface after launching the WAGO...

Page 130: ...23 Figure 52 WAGO Ethernet Settings Communication Link Once you have configured WAGO Ethernet Settings and have clicked Apply connection to the controller is established automatically If WAGO Ethernet...

Page 131: ...Version 04 01 10 23 8 8 3 1 Identification Tab An overview of the connected device is given here Besides some fixed values e g item No MAC address and firmware version the currently used IP address a...

Page 132: ...address subnet mask gateway Specify the specific network parameters for static configuration Restricted setting for default gateways Only the default gateway 1 can be set via WAGO Ethernet Settings T...

Page 133: ...rsion 1 7 0 valid from FW Version 04 01 10 23 MAC address This standard value is also used whenever the chosen name in the Input column is deleted Domain name The current domain name is displayed here...

Page 134: ...oning WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 8 8 3 3 PLC Tab Figure 55 WAGO Ethernet Settings PLC Tab Here you can select the ru...

Page 135: ...ning 135 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 8 8 3 4 Status Tab Figure 56 WAGO Ethernet Settings Status Tab General information about the control...

Page 136: ...210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 9 Run time System CODESYS V3 9 1 General Notes Additional Information Information on the installation startup and...

Page 137: ...and changes the state of the PLC application start stop reset warm cold CODESYS watchdog 83 Execution of the watchdog functions Cyclic and event controlled IEC task 55 53 1 3 For real time tasks whic...

Page 138: ...and are requested when downloading to the system depending on the scope of the program If the size limit is exceeded it is displayed as an error 9 3 2 Function Block Limitation Together with the data...

Page 139: ...C200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 10 Modbus A direct Modbus connection is not supported by the current firmware version Modbus connection is possible via the CODE...

Page 140: ...1 1 A LED The A LED system power supply indicates following diagnostics Table 50 System Power Supply Diagnistics Status Explanation Solution Green 24V system power supply voltage present Off No 24V s...

Page 141: ...t Connect to the device via the standard address 192 168 1 17 or restart the device to restore the original value set Green red flashing Firmware update mode Orange red flashing No license evaluation...

Page 142: ...pplication after in the STOP status after exception e g memory access error Start the application with a reset via the mode selector switch or in the connected IDE If the application cannot be started...

Page 143: ...WAGO I O System 750 Diagnostics 143 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23...

Page 144: ...ization has been completed Red A hardware fault is present Contact WAGO Support Red flashing 2 Hz An error which may be able to be eliminated is present First try to eliminate the error by switching t...

Page 145: ...Version 04 01 10 23 11 1 2 4 MS LED The MS LED indicates following diagnostics Table 55 MS LED Diagnostics Status Explanation Remedy Off No error Red flashing flashing sequence A configuration error...

Page 146: ...ks 11 1 3 1 LNK LED The LNK LED indicates following diagnostics Table 56 LNK LED Diagnostics Status Explanation Remedy Off 10 Mbit s Green 100 Mbit s 11 1 3 2 ACT LED The ACT LED indicates following d...

Page 147: ...from FW Version 04 01 10 23 11 1 4 Memory Card Slot LED Figure 60 Indicating Elements Memory Card Slot The memory card slot LED indicates following diagnostics Table 58 Diagnostics via Memory Card Slo...

Page 148: ...ence flickering initiates reporting of the fault error 2 After a short break approx 1 second the second flashing sequence starts The number of blink pulses indicates the error code which describes the...

Page 149: ...th position of the bus node Initiation of the Start Phase 1 The I O LED flashes for 1 cycle at about 10 Hz 10 flashes second 2 This is followed by a pause of about one second Error Code 4 Data Error i...

Page 150: ...annot be cleared by the measured specified for them contact WAGO support Be ready to explain to them the blink code that is displayed Phone 49 571 887 44 55 5 Fax 49 571 887 84 45 55 E mail support wa...

Page 151: ...witch the power back on If the I O flashes red switch off the power supply again and place the end module in the middle of the first half of the I O modules toward the controller If the LED is no long...

Page 152: ...o the controller and reduce the number of I O modules Then switch the power back on 12 Time to access the serial EEPROM exceeded Switch off the power to the controller and replace it Then switch the p...

Page 153: ...ollows Switch off the power supply Place the end module in the middle of the I O modules connected to the system Switch the power back on If the I O LED continues to flash red switch off the power sup...

Page 154: ...les that do not provide any data are ignored e g supply module without diagnostics Table 64 Error Code 5 Explanation of Blink Codes and Procedures for Troubleshooting Error Argument Cause Solution n R...

Page 155: ...ntact WAGO Support 2 Stack overflow Malfunction of the program sequence Contact WAGO Support 3 Stack underflow Malfunction of the program sequence Contact WAGO Support 4 Invalid event NMI Malfunction...

Page 156: ...the blink code that is displayed Phone 49 571 887 44 55 5 Fax 49 571 887 84 45 55 E mail support wago com Table 67 Overview of MS LED Error Codes Error Code Explanation 1 Configuration error Table 68...

Page 157: ...y in When you let go the memory card will move back a little and then snap in place push push mechanism 5 Close the cover flap by flipping it down and pushing it in until it snaps into place 6 You can...

Page 158: ...ervice WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 6 Close the cover flap by flipping it down and pushing it in until it snaps into p...

Page 159: ...can modify remove or add controller properties and functions As a result described properties or functions of the controller may not be available or available properties or functions may not be descri...

Page 160: ...IP address of your controller in the Transfer via TCP IP option 4 Click Find Controller Your controller is now displayed in the list 5 Select the displayed controller and click Next 6 In the Select Up...

Page 161: ...suitable PC tool 2 Save your application and the controller settings 3 Switch off the controller 4 Insert the memory card with the new firmware image into the memory card slot Use a special downgrade...

Page 162: ...e prior to performing any installation repair or maintenance work 13 1 1 Removing the Controller 1 Use a screwdriver blade to turn the locking disc until the nose of the locking disc no longer engages...

Page 163: ...harmful substances in electrical and electronic equipment Observe national and local regulations for the disposal of electrical and electronic equipment Clear any data stored on the electrical and el...

Page 164: ...0 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 Dispose of packaging of all types that allows a high level of recovery reuse and recycling Improper disposal of packaging can be ha...

Page 165: ...ization Profile 6 0 0 15 10 01 04 23 3 5 17 30 CODESYS V3 5 SP17 Patch 3 Notes on firmware versions Not every new firmware contains a new version of the runtime environment which is why the compiler v...

Page 166: ...ows information about product identification and the most important network properties Device Details Group This group shows information about product identification Table 70 WBM Device Status Page De...

Page 167: ...ct identification and addressing IP Source Current reference type of the IP address None No IP allocation method is selected this occurs for example if a bridge was added due to changes to the bridge...

Page 168: ...O I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 2 Vendor Information Page You can find the manufacturer and address on the Vendor I...

Page 169: ...provided on the PLC Runtime Information page You will also find a link here to open WebVisu Runtime Group Table 72 WBM PLC Runtime Information Page Runtime Group Parameter Explanation Version The ver...

Page 170: ...10 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 4 WAGO Software License Agreement Page The WAGO Software License Agreement page lists the license terms fo...

Page 171: ...PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 5 Open Source Licenses Page The license conditions for the open source software used for the product are listed in al...

Page 172: ...0 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 6 WBM Third Party License Information Page On the WBM Third Party License Information page you can find the license text o...

Page 173: ...ix 173 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 7 Trademarks Information Page On the Trademarks Information page you will find a list of prop...

Page 174: ...ual Version 1 7 0 valid from FW Version 04 01 10 23 15 2 1 1 8 WBM Version Page On the WBM Version page you can find the version information for the various sections Plug ins that the WBM contains Thi...

Page 175: ...CODESYS V3 CODESYS V3 runtime system is enabled Home directory on memory card enabled Define if the home directory for the runtime system should be moved to the memory card Disabled The home directory...

Page 176: ...ck Submit to apply the change The change takes effect immediately In its default setting the WBM is called up when only entering the IP address To update the display after switching enter the IP addre...

Page 177: ...urrent IP Address This displays the current IP address Current Subnet Mask This displays current subnet mask Current Default Gateway The IP address of the current default gateway is displayed IP Sourc...

Page 178: ...e displayed If no DNS server has been assigned by DHCP or BootP No DNS Servers assigned by DHCP is displayed Assigned by user The addresses of the defined DNS servers are displayed If no server has be...

Page 179: ...ge at a time Click the Submit button to apply the change The change takes effect immediately Ethernet Interface Configuration Group Table 78 WBM Ethernet Configuration Page Ethernet Interface Configur...

Page 180: ...ned a host name via DHCP it is given preference and the manually configured host name is not used To accept the manually configured host name the configuration of the DHCP server may have to be reduce...

Page 181: ...WAGO I O System 750 Appendix 181 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23...

Page 182: ...e interfaces Group Parameter Explanation Enabled Specify whether forwarding of IP data packets is allowed between different network interfaces If the box is not checked the settings under Static Route...

Page 183: ...Enter the address of the gateway If the Interface input field is empty an entry is required here If a value is entered in the Interface input field the input here is optional Gateway Metric Set the n...

Page 184: ...184 Appendix WAGO I O System 750 750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23...

Page 185: ...IP Masquerading Group Parameters Explanation Enabled Specify whether IP masquerading should be used Disabled IP masquerading is not used Enabled IP masquerading is used Interface You can select the s...

Page 186: ...ect the protocol to be used for the port forwarding The options are TCP UDP or both protocols Destination Address Specify the network address of the destination device This address replaces the origin...

Page 187: ...os Angeles Whitehouse GMT BST Greenwich Mean Time GB P IRL IS CET CEST Central European Time B DK D F I CRO NL EET EEST Eastern European Time BUL FI GR TR CST China Standard Time JST Japan Korea Stand...

Page 188: ...on 1 7 0 valid from FW Version 04 01 10 23 Local Time and Date Group Table 87 WBM Clock Settings Page Local Time and Date Group Parameter Explanation Local Date Set the date Local Time Set the local t...

Page 189: ...boot Table 88 WBM Configuration of Service Interface Page Assign Owner of Service Interface Group Parameters Explanation WAGO Service Communication Specify that the service interface is used for the W...

Page 190: ...for the image to be generated System was booted from Target partition for bootable image Memory Card Internal Flash Internal memory Memory Card Free space on target device If the available memory spac...

Page 191: ...oject If you want to save the PLC runtime project select this checkbox Settings If you want to save the device settings select this checkbox System If you want to back up the operating system of the d...

Page 192: ...orage location only one package may be selected for each storing process No backup of the memory card Backup from the memory card to the internal flash memory is not possible Account for backup time G...

Page 193: ...CODESYS project here The input field only appears if the network is selected as the data source Settings Enter the name of the backup file for the settings here The input field only appears if the ne...

Page 194: ...firmware cannot be restored Reset by restore A reset is performed when the system or settings are restored by CODESYS Connection loss through restore If the restore changes the parameters of the ETHER...

Page 195: ...hich the device was booted is displayed here System n Internal Flash Groups Table 93 WBM Active System Page System n Internal Flash Group Parameter Explanation Active This shows whether the system is...

Page 196: ...arameter Explanation Device The storage medium is displayed Boot device This shows whether the device has booted from this storage medium Volume name The name of the storage medium is displayed Create...

Page 197: ...ion Software file The file name of your selected software package is displayed as long as you have not yet transferred it to the product If you have not yet selected a package Choose ipk file appears...

Page 198: ...r application in the control components e g port 6626 for WAGO I O CHECK and port 11740 for CODESYS V3 Only open ports and services during commissioning and or configuration FTP Group Table 97 WBM Con...

Page 199: ...ion abort on disabling If the HTTP service is disabled the connection to the product may be interrupted In that case reopen the page HTTPS Group Table 100 WBM Configuration of Network Services Page HT...

Page 200: ...disabled time update Update interval sec Specify the update interval of the time server Time Server n Enter here the IP addresses of up to 4 time servers Time server No 1 is queried first If no data...

Page 201: ...3 WBM PLC Runtime Services Page CODESYS V3 Group Parameter Explanation CODESYS V3 State This displays the status enabled disabled of the CODESYS V3 runtime system Webserver enabled Enable or disable t...

Page 202: ...SSH Server Settings page SSH Server Group Table 104 WBM SSH Server Settings Page SSH Server Group Parameters Explanation Service active You can enable disable the SSH server Port Number Enter the port...

Page 203: ...s range Lease time min Specify the lease time here in seconds 120 minutes are entered by default Static Hosts This displays the static assignments of MAC IDs to IP addresses If no assignment was defin...

Page 204: ...Proxy Requests are buffered to optimize throughput Relay All requests are routed directly Static Hosts This displays the names for IP addresses If no assignment was defined No static hosts configured...

Page 205: ...108 WBM Status Overview Page Connection n Group Parameter Explanation Operation The status of the cloud connectivity application is displayed Data from PLC Runtime This shows how many data collection...

Page 206: ...83 for unencrypted connections Device ID Enter the device ID for the selected cloud platform Client ID Enter the client ID for the selected cloud platform Authentication Select the authentication meth...

Page 207: ...is to be compressed using GZIP compression Data Protocol Here you can select the data protocol Cache mode Specify in which memory the cache for the data telegrams should be created This selection fie...

Page 208: ...e following placeholders are available to create this property m Message type p Protocol version d Device ID Examples MyKey HelloWorld_ m TestKey m p d DeviceId d Click the Submit button to apply a ch...

Page 209: ...5 Data Protocol X X X X X Use compression X X1 X1 Cache mode X X X X X X Last Will X X X X Last Will Topic X3 X3 X3 X3 Last Will Message X3 X3 X3 X3 Last Will QoS X3 X3 X3 X3 Last Will Retain X3 X3 X3...

Page 210: ...g Table 112 Display of the Selection and Input Fields Depending on the Selected Data Protocol Selection or Input Field Data Protocol WAGO Protocol WAGO Protocol 1 5 Native MQTT Sparkplug payload B Cli...

Page 211: ...n 1 7 0 valid from FW Version 04 01 10 23 Table 114 Display of the Selection and Input Fields Depending on the Selected Authentication Selection or Input Field Authentication Shared Access Key X 509 C...

Page 212: ...ral SNMP Configuration Group Parameter Explanation Service active Activate deactivate the SNMP service Name of device Enter here the device name sysName Description Enter here the device description s...

Page 213: ...local community name is deleted when the protocol is disabled Local Community Name Specify the community name for the SNMP manager configuration The community name can establish relationships between...

Page 214: ...s the SNMP version via which the traps are sent v1 or v2c traps higher than v3 are displayed in a separate form Add new Trap Receiver In this area you can enter a new trap receiver IP Address Specify...

Page 215: ...Digest 5 MD5 Secure Hash Algorithm SHA Authentication Key The authentication key is displayed Privacy The encryption algorithm for the SNMP message is displayed Possible values No encryption None Data...

Page 216: ...encryption algorithm for the SNMP message Possible values No encryption None Data Encryption Standard DES Advanced Encryption Standard AES Privacy Key min 8 char Enter the key for encryption of the SN...

Page 217: ...25 Page Docker Settings On the page Docker Settings see the settings for the Docker service Group Docker Status Table 119 WBM Page Docker Settings group Docker Status Parameter Meaning Service Instal...

Page 218: ...New Password Enter the new password here Permitted characters for the password are the following ASCII characters a z A Z 0 9 blank spaces and special characters _ Confirm Password Enter the new passw...

Page 219: ...roup Table 121 WBM Page BACnet Status BACnet Information Group Parameter Meaning State This group shows whether the BACnet fieldbus is enabled or disabled Status Info The status of the BACnet fieldbus...

Page 220: ...er must be enabled default setting for the BACnet fieldbus protocol to be used On a runtime restart a security message is displayed in a pop up window asking if you really want to perform a restart Ta...

Page 221: ...an select the data to be deleted or reset on the next restart Table 125 WBM Page BACnet Configuration BACnet Data Reset Group Parameter Meaning Delete Persistence Data Persistent BACnet data is delete...

Page 222: ...sible only when both storage options are available Internal Flash Data will be stored in the controller s internal memory SD Card Data will be stored on the SD card If SD card has been selected and th...

Page 223: ...net Storage Location BACnet Eventlog Group Parameter Meaning Storage location Select the storage location for the event log data here Selection is possible only when both storage options are available...

Page 224: ...this page The changes only take effect after the controller restarts For this purpose use the WBM reboot function Do not shut down the controller too early BACnet override xml Group Table 129 WBM Pag...

Page 225: ...is displayed stopped The service is disabled running The service is enabled OpenVPN enabled Enable or disable the OpenVPN service openvpn config Select an OpenVPN configuration file to be transferred...

Page 226: ...rvice ipsec conf Select an IPsec configuration file to be transferred from PC to product or vice versa ipsec secrets Select an IPsec configuration file to be transferred from PC to product or vice ver...

Page 227: ...he firewall is disabled all other settings have no direct effect The configuration of the other parameters is possible nevertheless so that you can set the firewall parameters correctly before you ena...

Page 228: ...2 1 4 3 Interface Configuration Page The individual interfaces for the firewall settings are displayed on the Interface Configuration page Firewall Configuration Bridge n VPN WAN Group A separate gro...

Page 229: ...limit per second You can specify the maximum number of ICMP pings per second Input is only effective when ICMP echo protection is disabled 0 Disabled ICMP burst limit 0 disabled You can specify the m...

Page 230: ...ddress in the MAC Address Filter Whitelist Otherwise you cannot access the device via the ETHERNET This also applies to other services that are used by your device e g the IP configuration via DHCP If...

Page 231: ...p Parameters Explanation Description Description of the devices or areas that can be enabled by activating the filter when the firewall is generally enabled The description is only visible for entries...

Page 232: ...respective filter is displayed Destination Port The destination port number for the respective filter is displayed Protocol The permitted protocols for the respective filter is displayed Input interfa...

Page 233: ...ce and UDP service are filtered TCP The TCP service is filtered UDP The UDP service is filtered Input interface Enter here the interfaces for the new filter Any All interfaces are filtered Bridge n Th...

Page 234: ...Upload button The changes take effect immediately The certificates are stored in the directory etc certificates and the keys in the directory etc certificates keys Click Delete to delete an entry The...

Page 235: ...ot option for the product Memory card or internal flash You can boot from the internal flash or from the memory card Internal flash only You can only boot from the internal flash If you force booting...

Page 236: ...HTTPS Standard The Webserver allows TLS 1 0 TLS 1 1 and TLS 1 2 as well as cryptographic methods that are no longer considered secure Strong The Webserver only allows TLS Version 1 2 and strong algor...

Page 237: ...The database is initialized and filled with the current values check The current values are compared against the values stored in the database update The current values are compared with the values st...

Page 238: ...750 8210 040 000 PFC200 G2 4ETH XTR Manual Version 1 7 0 valid from FW Version 04 01 10 23 update is stopped until you call up the Advanced Intrusion Detection Environment AIDE page again The messages...

Page 239: ...is still in beta Unauthenticated Requests Group Table 144 WBM Page WAGO Device Access Unauthenticated Requests Group Parameter Meaning Allow unauthenticated Device Scan You set whether the node can be...

Page 240: ...depending on status Source Select the source of the diagnostic messages The drop down list depends on the user who is logged in user Default diagnostic messages only admin Default diagnostic messages...

Page 241: ...System 750 XTR I O modules in the process image as well as the configuration of the process values Equipment damage due to incorrect address To prevent any damage to the device in the field you must a...

Page 242: ...t DI 2 Channel 2 Data bit DI 1 Channel 1 15 3 1 2 8 Channel Digital Input Modules Table 147 8 Channel Digital Input Modules Input Process Image Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Data bit...

Page 243: ...Digital Output Modules Output Process Image Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Controls DO 2 Channel 2 Controls DO 1 Channel 1 15 3 2 2 2 Channel Digital Output Modules with Diagnostics...

Page 244: ...Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Controls DO 8 Channel 8 Controls DO 7 Channel 7 Controls DO 6 Channel 6 Controls DO 5 Channel 5 Controls DO 4 Channel 4 Controls DO 3 Channel 3 Control...

Page 245: ...t 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Con trols DO 16 Chan nel 16 Con trols DO 15 Chan nel 15 Con trols DO 14 Chan nel 14 Con trols DO 13 Chan nel 13 Con trols DO 12 Chan nel 12 Con trol...

Page 246: ...on the structure of a particular I O module s control status bytes please refer to that module s manual Manuals for each module can be found on the Internet at www wago com 15 3 3 1 2 Channel Analog I...

Page 247: ...le Input Process Image Offset Byte Destination Description High Byte Low Byte 0 S0 Status byte 0 1 D1 D0 Input data word 1 2 S1 Status byte 1 3 D3 D2 Input data word 2 4 S2 Status byte 2 5 D5 D4 Input...

Page 248: ...nto the Output Process Image in front of the digital data Information on the structure of control and status bytes For detailed information on the structure of a particular I O module s control status...

Page 249: ...nding description of the I O modules for the structure of the control status bytes You can find a manual with the relevant I O module description at http www wago com 15 3 5 1 Serial Interfaces with A...

Page 250: ...5 3 Distance and Angle Measurement The incremental encoder interface module occupies 6 bytes of user data in the input and output area of the process image 4 data bytes and two additional control stat...

Page 251: ...The above Counter Modules have a total of 5 bytes of user data in both the Input and Output Process Image 4 bytes of counter data and 1 byte of control status The two counter values are supplied as 3...

Page 252: ...the process image sizes are set with the startup tool WAGO I O CHECK Table 166 CAN Gateway Input and Output Process Image Process image size Offset Byte Designation Descrition High Byte Low Byte 8 byt...

Page 253: ...with One One One One Ports 57 Figure 22 Connecting the Controller to a Cloud Service Example 71 Figure 23 Coordinates Model Width x Height y Depth z 81 Figure 24 Mounting Positions 82 Figure 25 Spaci...

Page 254: ...Communication Link 130 Figure 53 WAGO Ethernet Settings Identification Tab Example 131 Figure 54 WAGO Ethernet Settings Network Tab 132 Figure 55 WAGO Ethernet Settings PLC Tab 134 Figure 56 WAGO Ethe...

Page 255: ...Table 21 Technical Data Power Jumper Contacts 45 Table 22 Technical Data Data Contacts 45 Table 23 Technical Data Mechanical Environmental Conditions 46 Table 24 Technical Data Climatic Environmental...

Page 256: ...dures for Troubleshooting 153 Table 63 Error Code 4 Explanation of Blink Codes and Procedures for Troubleshooting 154 Table 64 Error Code 5 Explanation of Blink Codes and Procedures for Troubleshootin...

Page 257: ...WBM Software Uploads Page Upload New Software Group 197 Table 97 WBM Configuration of Network Services Page FTP Group 198 Table 98 WBM Configuration of Network Services Page FTPES explicit FTPS Group...

Page 258: ...Location BACnet Eventlog Group 223 Table 129 WBM Page BACnet Files BACnet override xml Group 224 Table 130 WBM OpenVPN IPsec Configuration Page OpenVPN Group 225 Table 131 WBM OpenVPN IPsec Configurat...

Page 259: ...agnostics and Input Data244 Table 153 8 Channel Digital Output Modules 244 Table 154 8 Channel Digital Output Modules with Diagnostics and Input Data244 Table 155 16 Channel Digital Output Modules 245...

Page 260: ...WAGO GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com...

Reviews: