Special Use Conditions for ETHERNET Devices 

If not otherwise specified, ETHERNET devices are intended for use on local 

networks. Please note the following when using ETHERNET devices in your 

system: 

• 

Do not connect control components and control networks directly to an 

open network such as the Internet or an office network. WAGO 

recommends putting control components and control networks behind a 

firewall. 

• 

Limit physical and electronic access to all automation components to 

authorized personnel only. 

• 

Change the default passwords before first use! This will reduce the risk of 

unauthorized access to your system. 

• 

Regularly change the passwords used! This will reduce the risk of 

unauthorized access to your system. 

• 

If remote access to control components and control networks is required, 

use a Virtual Private Network (VPN). 

• 

Regularly perform threat analyses. You can check whether the measures 

taken meet your security requirements. 

• 

Use “defense-in-depth” mechanisms in your system's security configuration 

to restrict the access to and control of individual products and networks. 

 

 

 

Summary of Contents for 852-1411/000-001

Page 1: ...Manual WAGO ETHERNET Accessories 852 852 1411 000 001 Industrial Eco Switch 5 Ports 1000BASE T 4 x PoE EXT Version 1 0 0...

Page 2: ...87 84 45 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appre...

Page 3: ...nditions for ETHERNET Devices 14 3 General 15 3 1 Package Contents 15 3 2 Industrial ETHERNET Technology 15 3 3 Switching Technology 15 3 4 PoE Power over Ethernet 16 3 5 Autonegotiation 17 3 6 Autocr...

Page 4: ...Version 1 0 0 4 6 Approvals 31 5 Mounting 32 5 1 Installation site 32 5 2 Installation on a DIN Rail 32 5 3 Removal from DIN Rail 33 6 Connect Devices 34 6 1 Power Supply 34 7 Appendix 35 7 1 RJ 45 C...

Page 5: ...ary 1 1 Validity of this Documentation This documentation is only applicable to WAGO ETHERNET accessory products Industrial Eco Switch 852 1411 000 001 This documentation is only applicable from 1 2 C...

Page 6: ...Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not...

Page 7: ...s 852 Notes about this Documentation 7 852 1411 000 001 Industrial Eco Switch Manual Version 1 0 0 Additional Information Refers to additional information which is not an integral part of this documen...

Page 8: ...nd data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item f...

Page 9: ...ialists with sufficient knowledge in automation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should a...

Page 10: ...852 852 1411 000 001 Industrial Eco Switch Manual Version 1 0 0 Further details are given in the contractual agreements Please send your request for modified and new hardware or software configuration...

Page 11: ...e the accident prevention regulations of your machine e g DGUV Regulation Electrical Installations and Equipment Emergency stop functions and equipment must not be deactivated or otherwise made ineffe...

Page 12: ...all these switches in lockable housings cabinets or electrical operation rooms Access must be limited to authorized qualified staff having the appropriate key or tool Ensure a standard connection To m...

Page 13: ...d soiled contacts with propanol Do not use any contact spray Do not use any contact spray The spray may impair contact area functionality in connection with contamination Do not reverse the polarity o...

Page 14: ...etworks behind a firewall Limit physical and electronic access to all automation components to authorized personnel only Change the default passwords before first use This will reduce the risk of unau...

Page 15: ...supply with a supply voltage range of 24 57 V Power over Ethernet PoE is supported on 4 ports Features such as auto negotiation and auto MDI MDIX crossover are realized in all 10 100 1000BASE T ports...

Page 16: ...02 3at PSE power 15 4 W 25 4 W Max power PD 12 95 W 21 90 W Max current per core pair 350 mA 600 mA Transmission standard 10Base T 100Base TX 10Base T 100Base TX 1000 BASE T Calculation example for Po...

Page 17: ...and 5 or 7 and 8 are used for the power supply An 8 core ETHERNET cable of at least category 5 or 5e is required see section Appendix RJ 45 Cable 3 5 Autonegotiation Autonegotiation allows the switch...

Page 18: ...egram length Advantage of Store and Forward The data telegrams are checked for correctness and validity This prevents faulty or damaged data telegrams from being distributed via the network 3 8 Transm...

Page 19: ...rts support Power over Ethernet PoE with 30 W These 4 ports can be used simultaneously for power supply The integrated voltage transformer enables operation on the 24 VDC power supplies common in the...

Page 20: ...ip tion Meaning Details see Section 1 PWR Status LED Power Supply Device Description Display Elements 2 POE Status LED Power over Ethernet 4 1 LED for each port Device Description Display Elements 3 S...

Page 21: ...0 4 1 2 Top View Figure 2 Top View of the Industrial ECO Switch Table 6 Legend for Figure Top View of the Industrial ECO Switch Pos Descrip tion Meaning Details see Section 1 Grounding screw Device D...

Page 22: ...dustrial Eco Switch Manual Version 1 0 0 4 2 Connectors 4 2 1 Grounding screw The switch must be grounded Connect the grounding screw to the ground potential Do not operate the switch without an appro...

Page 23: ...le connector shows the following pin assignment Figure 4 Power Supply PWR Port Table 7 Legend fort Figure Power Supply PWR Port Pin Description Meaning PWR Primary DC input PWR Primary DC input Damage...

Page 24: ...t ETHERNET and Gigabit ETHERNET Capping unused ports Cap unused ports with included protective covers Figure 5 Network Connections Table 8 Legend fort the Figure Network Connections No Descrip tion Me...

Page 25: ...g for PoE Budget The PoE Budget at Power supply DC 48 V is 120 W and at Power supply DC 48 V is 60 W 4 2 3 2 10 100 1000Base T ports The 10 100 1000Base T ports support network speeds of 10 Mbit s 100...

Page 26: ...u can see the status of the industrial switch at a quick glance of the device LEDs while the port LEDs provide information about connection actions 4 3 1 Device LED Figure 6 Device LED Table 9 Legend...

Page 27: ...on 1000 10 100 1000BASE T Ports LED 1 LED for each port Green Port in operation at 1000 Mbit s OFF Connection in operation at less than 1000 Mbit s LNK ACT LNK ACT LED 1 LED for each port Green Lights...

Page 28: ...anual Version 1 0 0 4 4 Label 4 4 1 Hardware and Software Version There is a label with the serial no S N on the back of the industrial switch Figure 8 Label Table 11 Legend for Figure Label No SN Des...

Page 29: ...h Carrier rail mounting 120 mm Weight 550 g Degree of protection IP30 4 5 2 System Data Table 13 Technical Data System Data MAC table Up 8000 Addresses VLAN Port based and tag based 4094 VIDs Jumbo Fr...

Page 30: ...thernet PoE IEEE 802 3at High Power over Ethernet PoE IEEE 802 3az Energy Efficient Ethernet Topology Star 4 5 5 Environmental Conditions Table 16 Technical Data Environmental Conditions Surrounding a...

Page 31: ...52 1411 000 001 Industrial Eco Switch Manual Version 1 0 0 4 6 Approvals The following approvals have been granted for the WAGO ETHERNET accessory product Industrial Eco Switch 852 1411 000 001 Confor...

Page 32: ...d humidity operating ranges Make sure that the heat output from the industrial ECO switch and ventilation around it is adequate Do not place any objects on the industrial ECO switch 5 2 Installation o...

Page 33: ...52 1411 000 001 Industrial Eco Switch Manual Version 1 0 0 5 3 Removal from DIN Rail To remove the device from the DIN rail press down on the industrial ECO switch and pull it out of the DIN rail Figu...

Page 34: ...cables are connected 1 Connect a suitable grounding conductor to the grounding lug on the top of the switch Ground for the switch The ground for the switch prevents electromagnetic interference from e...

Page 35: ...below Table 17 RJ 45 Cable Contact Description Pair Color acc EIA TIA 568B 4 wire 8 wire 1 TD D1 2 White Orange 2 TD D1 2 Orange 3 RX D2 3 White Green 4 Not assigned D3 1 Blue 5 Not assigned D3 1 Whi...

Page 36: ...ut Power at PD output 0 15 4 W 13 0 W 1 4 0 W 3 84 W 2 7 0 W 6 49 W 3 15 4 W 13 0 W 4 25 5 W 25 5 W PoE acc IEEE 802 3at The PSE Power Sourcing Equipment applies a defined voltage to the PD Power Devi...

Page 37: ...nt View of the Industrial ECO Switch 20 Figure 2 Top View of the Industrial ECO Switch 21 Figure 3 Grounding screw 22 Figure 4 Power Supply PWR Port 23 Figure 5 Network Connections 24 Figure 6 Device...

Page 38: ...Industrial ECO Switch 21 Table 7 Legend fort Figure Power Supply PWR Port 23 Table 8 Legend fort the Figure Network Connections 24 Table 9 Legend for Figure Device LED 26 Table 10 Legend for Figure P...

Page 39: ...WAGO ETHERNET Accessories 852 39 852 1411 000 001 Industrial Eco Switch Manual Version 1 0 0...

Page 40: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com...

Reviews: