852-1328
Configuration in the WBM
Product manual | Version: 1.2.0
55
Industrial Managed Switch
To add a new SNMP V3 user, the user have to select the user Name from the dropdown
list which can be either Admin or User. Then, the authentication password with a maxi-
mum length of 31 characters must be entered in the Auth. Password field and re-entered
again in the Confirmed Password field. Note that if no password is provided, there will be
no authentication for SNMP V3. Finally, the encryption key with a maximum length of 31
characters can be entered in the Encryption Key field and re-entered again in Confirmed
Key field. After filling all the required fields, please click on
[Add]
button to update the in-
formation on the industrial managed switch. Table “WBM “Diagnostics” Page – “SNMP”
Tab, SNMP V3 Auth.” lists the descriptions of SNMP V3 settings.
Table 27: WBM “Diagnostics” Page – “SNMP” Tab, SNMP V3 Auth.
Parameters
Factory Default
Description
Name
admin
Choose from one of the following options:
Admin: Administration level (Default)
User: Normal user level
Auth. (Authentica-
tion) Password
wago0852
Set an authentication password for the user name specified
above. If the field is left blank, there will be no authentication. Note
that the authentication password is based on MD5 and the maxi-
mum length of the password is 31 characters.
Confirmed Password wago0852
Re-entering the Authentication Password to confirm.
Encryption Key
wago0852
Set an encryption key for more secure protection of SNMP com-
munication. Note that the encryption algorithm is based on DES
and the maximum length of the key is 31 characters.
Confirmed Key
wago0852
Re-entering the Encryption Key to confirm.
10.5.2 Modbus TCP
WAGO’s industrial managed switch can be connected to a Modbus network using Mod-
bus TCP/IP protocol which is an industrial network protocol for controlling automation
equipment. The switch’s status and settings can be read through Modbus TCP/IP proto-
col which operates similar to the Management Information Base (MIB) browser. The
switch will be a Modbus slave which can be remotely configured by a Modbus master.
The Modbus slave address must be set to match the setting inside the Modbus master. In
order to access the switch, a Modbus Address must be assigned as described in this sub-
section. A Modbus memory mapping table, which lists all the register’s addresses inside
the switch and their descriptions, is provide in “Modbus Memory Map” table in the “Ap-
pendix”. Figure “WBM “Diagnostics” Page – “Modbus TCP” Tab” shows the Modbus TCP
tab page “.