WAGO-SPEEDWAY 767
Process Image
69
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
8.1.2
Output Data
The image for the process data, which are transmitted by the fieldbus coupler to
the I/O module, has a size of 1 byte. If you configure a synchronous diagnostic
confirmation of the I/O module, the process image has a size of 3 bytes.
The process data and the diagnostic confirmation are structured as follows:
Table 39: DO output data in the process image
Byte 0
7
0
Digital outputs (process data)
\
-----------------
\/
-----------------
/
1
B
: Input value = True
Byte 1
7
0
Diagnostic confirmation
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1 conf.
| | | | | | 1
B
: Overtemperature on channel 2 conf.
| | | | | 1
B
: Overtemperature on channel 3 confirmed
| | | | 1
B
: Overtemperature on channel 4 confirmed
| | | 1
B
: Overtemperature on channel 5 confirmed
| | 1
B
: Overtemperature on channel 6 confirmed
| 1
B
: Overtemperature on channel 7confirmed
1
B
: Overtemperature on channel 8 confirmed
Byte 2
7
0
Diagnostic confirmation
\
--------
\/
--------
/
| | | |
|
|
|
|
|
|
|
|
1
B
: Short circuit/overload
field supply confirmed
|
| | Not assigned
|
| 1
B
: Undervoltage U
LS
confirmed
|
1
B
: Undervoltage U
A
confirmed
Not assigned: always 0