WAGO 765-1505/100-000 Product Manual Download Page 55

765-1505/100-000

Connection

Product manual | Version: 2.0.0

55

8DIO FLD EI DC 24V 2.0A

Connection Option

Description

Connection of a digital output

Required port configuration: pin 4 as digital output

Summary of Contents for 765-1505/100-000

Page 1: ...Product manual Version 2 0 0 WAGO I O System Field 8 Channel Digital Input Output EtherNet IP 24 V DC 2 0 A 8 M8 Connection 765 1505 100 000...

Page 2: ...n to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreci ate any information or suggestions for improving the documentation E Mai...

Page 3: ...16 4 2 2 1 Digital Inputs Outputs 16 4 2 3 Network Connections 17 4 2 3 1 ETHERNET Interfaces 17 4 3 Circuit Diagram 17 4 4 Technical data 17 4 4 1 Product 17 4 4 2 Mechanical Data 18 4 4 3 Connectio...

Page 4: ...Settings Options 42 6 3 1 Module Parameters 42 7 Transport and Storage 44 8 Installation and Removal 45 8 1 Installation 45 8 1 1 Tools Required for Installation 45 8 1 2 Before Installation 45 8 1 3...

Page 5: ...2 Configuring IP Parameters 65 10 3 1 4 3 Storing Maintenance Information 66 10 3 1 4 4 Update Firmware 67 10 3 1 4 5 Resetsetting the Module to the Factory Settings 69 10 3 1 4 6 Configure Bluetooth...

Page 6: ...0 000 Table of Contents vi Product manual Version 2 0 0 8DIO FLD EI DC 24V 2 0A 14 Appendix 110 14 1 Installation Regulations Specified by Approvals 110 14 2 Operational Description 111 14 3 Protected...

Page 7: ...is permitted Operation of the product in other application areas is only permitted when correspond ing approvals and labeling are present Improper Use Improper use of the product is not permitted The...

Page 8: ...th In addition the Installation regulations specified by Approvals must be observed In the event of non compliance the products may not be operated within the scope of the approval 1 2 Typographical C...

Page 9: ...ce risk WARNING Type and source of hazard Possible consequences of hazard that also include severe injury Action step to reduce risk CAUTION Type and source of hazard Possible consequences of hazard t...

Page 10: ...einafter The trademarks are listed in the Appendix 8 Protected Rights 113 Subject to Change The instructions guidelines standards etc in this manual correspond to state of the art at the time the docu...

Page 11: ...ct please ensure that environmental factors personnel work space and packaging are properly equalized Do not touch any conducting parts Cables Maintain spacing between control signal and data lines an...

Page 12: ...ld cause scratches for cleaning Clean tools and materials are imperative for handling the product If automation solutions are implemented that can cause personal injury or major prop erty damage in th...

Page 13: ...data Configuration and parameterization via EtherNet IP Bluetooth interface for diagnostics and configuration using the WAGO I O Field app and a mobile device WAGO I O Field Webserver Integrated Webs...

Page 14: ...4 Product manual Version 2 0 0 8DIO FLD EI DC 24V 2 0A 4 Properties 4 1 View Figure 1 View Table 1 Legend for View Figure Function Position Custom Name Description ETHERNET 2 X21 ETHERNET interface M1...

Page 15: ...s outputs 1L powered 13 X01 X04 Digital inputs outputs ports X01 X04 1 channel M8 A coded 12 LEDs with no function 14 0 1 2 3 Port LEDs for connections X01 X04 pin 4 Digital inputs outputs 2L powered...

Page 16: ...r out Before connecting one or more products to the power supply on socket X32 Power out read section 8 Power Supply Examples 40 There you will find information on the maximum permitted current consum...

Page 17: ...egative receive data Housing Shield Shield connection housing is connected to functional ground 4 3 Circuit Diagram The following figure shows the schematic circuit diagram of the product Figure 2 Cir...

Page 18: ...t Output 1L or 2L Powered Table 9 Digital Input Output 1L or 2L Powered Property Value Value per UL Digital Input Characteristic Type 3 IEC 61131 2 Parameter Digital software input filter without 3 ms...

Page 19: ...supply voltage Self protection Overcurrent overload overtemperature and overvolt age Voltage drop through high side path Less than 200 mV Maximum capacitive load 1000 F parallel to 24 0 1 Hz 470 F par...

Page 20: ...R OUT it may be necessary for the maximum total cur rent to be monitored with external power supply management Conductor cross section 0 5 2 5 mm2 Note Observe the cur rent carrying capacity and cable...

Page 21: ...data 4 bytes output data 0 bytes Connection 2 Listen only I O connection types implicit Exclusive Owner Input Only Listen Only I O connection trigger type Cyclic DHCP Supported default setting BOOTP...

Page 22: ...perature T Please note the derating for use of the product The surrounding air temperature and the current affect the product s heat generation The derating curve was created with the following condit...

Page 23: ...in as a function of the ambient temperature T Figure 5 Derating of a Contact Pin of the A Coded Connections Port X01 X02 for Core Cross Section 0 34 mm2 AWG 22 High currents may occur on connections p...

Page 24: ...rdinary Location In preparation Bluetooth This module has an RF transmitter with the follow ing specifications Operating frequency 2402 2480 MHz Maximum RF output power 20 mW RED Certificate number R2...

Page 25: ...scribes the structure of the input process data of connections 1 through 4 Table 19 Input Process Data Byte Off set Byte Count Input Process Data Description 0 1 DI status 0 DI data invalid 1 255 DI d...

Page 26: ...Output Process Data Description 0 1 DO Status 0 DO data invalid Substitute values are used 1 255 DO data valid 1 1 Dummy byte Reserved 0 2 3 2 DO Data The port and pin assignment of process data depen...

Page 27: ...placement values means setting or resetting the mod ule outputs independent of the module s process image Forcing Outputs To force output data for test purposes you can control all the outputs indepen...

Page 28: ...m In the module the measured values are compared to limiting values An alarm or event is generated if a value falls above or below a limiting value e g a temperature limiting value The module can send...

Page 29: ...ted into the 765 Series module With a Web browser users can view the Web pages and display and modify parameters WAGO I O Field App The WAGO I O Field app is an app for mobile devices that can communi...

Page 30: ...er 5 5 2 WAGO Webserver I O Field The WAGO I O System Field module has an integrated Webserver It can be accessed with a standard Web browser in order to use the following functions Display port infor...

Page 31: ...n and backup Process Data Display the process data input output Settings All Product Settings Device Configuration Configure parameters for IP connection 8 Configuring IP Param eters 65 Maintenance In...

Page 32: ...nnection for wireless commu nication Querying product information including serial number UII Unique Item Identifier Managing known devices for direct selection without scanning the DM code Querying s...

Page 33: ...and parameter ized Event Log Object 65 IO Link events are logged in event log object 65 0x41 The controller or a diagnostic tool can read event log object 65 0x41 5 6 2 OPC UA Server The module has a...

Page 34: ...all ports and services not required by your application to minimize the risk of cyber attacks and to enhance cybersecurity Only open the ports and services for the duration of the commissioning confi...

Page 35: ...ssible current feedthrough exceeded There is a risk of damage to the device and or other devices connected to it if the maxi mum permissible current feedthrough is exceeded Power Supply of the Module...

Page 36: ...PWR IN and supply voltage input X32 PWR OUT Rule 1 Take maximum load capacity of each connection contact pin into ac count Rule 2 Take 1L and 2L current feedthrough into account Ports X01 X02 etc Rul...

Page 37: ...rent feedthrough limiting The supply voltage for the devices of a supply cable that are connected to the PWR OUT output supply connection is passed on through the device via the input supply connec ti...

Page 38: ...Total current for supply cable 1 at digital input output X0i i e port X01 X02 X04 corresponds to current IX0i_pin3_1L on pin 3 ground This current is the sum of the currents at pins 1 and 4 of digital...

Page 39: ...ive Extra Low Voltage or SELV Safety Extra Low Voltage voltage sources Failure to do so may result in electric shock If 1L and 2L are to be supplied separately e g for safe switch off of 2L then eithe...

Page 40: ...ra tures and voltages on the connections 6 2 4 Power Supply Examples The product can be powered alone with its operating voltage or form part of a power sup ply group along with multiple products Powe...

Page 41: ...le 1 then has a total current consumption of 2 2 A 0 2 A 4 2 A and sup ply cable 2 has a total current consumption of 2 2 A 4 0 A These do not exceed the maximum permissible value of 16 A per supply c...

Page 42: ...gital outputs to low level in the event of error 1 Use substitute val ues Set digital outputs to a pre defined substi tute value in the event of error If this setting is used the value of the DO subst...

Page 43: ...port X02 Parameters 128 and 129 configure port X08 Table 33 Port Parameters No Parametername Value Range Default Description 100 104 DIO port X01 X02 pin 4 mode 0 Normally open 0 Pin 4 is a digital i...

Page 44: ...optimal protection during transport and storage Store the product in suitable packaging preferably the original packaging Only transport the product in suitable containers packaging Make sure the prod...

Page 45: ...t weather exposure no di rect sunlight no salt water or spray Note that the module should not be installed in the immediate vicinity of objects or de vices that can get hot For a high level of module...

Page 46: ...e past the edge of the housing Where high surrounding air temperatures occur at the same time as high current loads modules should not be installed directly next to each other to prevent them from eac...

Page 47: ...per DIN 912 ISO 4762 8 2 2 Before Removal CAUTION Device gets hot During operation high surface temperatures can arise on the metal housing and metal connection sockets If the product has been in oper...

Page 48: ...twork cables e g fieldbus cables in their own cable ducts Do not lay network cables parallel to power supply cables through which high power flows When installing shielded pluggable connectors screws...

Page 49: ...nection X32 The following procedure is especially advantageous Install the power supply for the module electronics independently of the power supply for the actuators Provide independent fuse protecti...

Page 50: ...Damage to electronics For passthrough of the supply voltage the following should be noted The maximum total current permitted on 1L is 16 A The maximum total current permitted on 2L is 16 A The temper...

Page 51: ...the cable used is not known it can be calculated approximately with the following formula RL l K A where RL Cable resistance I Cable length K Specific cable resistance of the conductor material usuall...

Page 52: ...ERNET network by plugging the socket of the ETH ERNET cable onto the X21 connection 3 Tighten the pluggable connector using the knurled head screw Connecting Multiple Products to One ETHERNET Network...

Page 53: ...t Sensors Actuators The sensor actuator cable powers the connected sensors actuators and transfers the sensor and actuator signals Note the current load capacity of the supply contacts see Rule 3 sect...

Page 54: ...1 4 3 1L 1L DIO 1L 1 4 3 1L 1L DIO 1L 1 4 3 2L 2L DIO 2L 1 4 3 2L 2L DIO 2L 1 4 3 2L 2L DIO 2L 1 4 3 2L 2L DIO 2L Figure 10 Schematic Circuit Diagram of the Power Supply The following table shows the...

Page 55: ...765 1505 100 000 Connection Product manual Version 2 0 0 55 8DIO FLD EI DC 24V 2 0A Connection Option Description Connection of a digital output Required port configuration pin 4 as digital output...

Page 56: ...twork for test purposes you can use Open DHCP Server for example Please note If a DHCP server is installed on your computer you should never connect it to a larger network Since global networks usuall...

Page 57: ...onfiguration project Select a connection connection 1 connection 2 etc Set the parameters The individual steps are describe in detail below 10 2 1 1 Selecting the Module Select the module used from th...

Page 58: ...n software of the scanner and transferred to the module through this con nection The scanner can read the module s input data and write the output data Connection 2 Exclusive Owner without Config No p...

Page 59: ...to affect the product s behavior Requirement Opening the user interface of WAGO I O Field Webserver requires that product s IP address is configured and known Proceed as follows Enter the following t...

Page 60: ...ing measurement data that is measured by the integrated sensors in the module The module temperature The supply voltage for supply cables 1L and 2L The sum of all currents for supply cables 1L and 2L...

Page 61: ...ensors Actuators Figure 12 Information Tab Port X0i Menu Item Example View The Information tab shows the following information The measured values and states of the port diagnostics The information on...

Page 62: ...appears 10 3 1 3 4 State The current port information of the digital input output is displayed Possible values are Digital Input The port is in digital input mode Digital Output The port is in digita...

Page 63: ...the WAGO I O Field Webserver You can make the following settings on the module with WAGO Webserver I O Field 8 Configure Ports 64 8 Configuring IP Parameters 65 8 Storing Maintenance Information 66 8...

Page 64: ...If you do not have these the Con figuration tab is grayed out and the displayed values cannot be edited If the controller and module are exchanging process data configuration is not possible In this...

Page 65: ...igital output All elements of the port configuration are ig nored except for the input and output data length Digital output static on The port is used as a digital output The signal on pin 4 is perma...

Page 66: ...ction Device IP address IP address for the ETHERNET configuration with static IP address configuration Subnet mask Subnet mask for the ETHERNET configuration with static IP address configuration Gatew...

Page 67: ...64 characters Readable comment field plain text to store free text containing individual state information and com ments I M3 DESCRIPTOR Signature Printable ASCII string max 128 characters Signature...

Page 68: ...figuration data backup exists Changes to settings require operator or admin rights If you do not have these the Set tings tab is grayed out and cannot be edited To update the firmware you need a firmw...

Page 69: ...actory settings This can be done for various selectable classes of settings with the Settings menu item on the Fac tory reset tab Figure 19 Settings Menu Item Factory Reset Tab Example View Changes to...

Page 70: ...g functions Displaying information on the product s Bluetooth interface module Displaying diagnostic information Activating the Bluetooth interface via DM code Starting a Bluetooth firmware update Res...

Page 71: ...he status of the last Bluetooth firmware update is indicated as follows Table 44 Status of the Last Bluetooth Firmware Update Value Status 0 Ready for operation 1 Firmware file is being checked 2 Firm...

Page 72: ...rts Switching the Bluetooth Interface Wireless Transmitter on off To switch the Bluetooth interface wireless transmitter on Slide the Bluetooth Radio switch to the right The Bluetooth interface wirele...

Page 73: ...menu left select the Sign out menu item You can now no longer work in the WAGO I O Field Webserver with the rights you had been using till this point The username used to log on is no longer shown in...

Page 74: ...reen appears Figure 22 User Administration Menu Item Initial State Example View The user root with pre set password password exists by default see first row An additional user can be created in the se...

Page 75: ...deleted The user root cannot be deleted so the red deletion button is grayed out there 10 3 1 4 8 Forcing Digital Inputs and Outputs To access the forcing functionality for the digital inputs and outp...

Page 76: ...tter checkbox is only relevant if the force box is checked The following ap plies to this All inputs for input simulation are entered in the right half of the table under Input process data all the in...

Page 77: ...2 1 Parameterizing a Module with the WAGO I O Field App Note Read the online help You can find Product specific information on the WAGO App I O Field in the online help for the app 10 3 3 OPC UA Serv...

Page 78: ...areRevision node The path to this node is Root Object DeviceSet device name Table 46 Identify Devices Node Name Node Class Access Description Manufacturer Variable Read Device manufacturer Manufacture...

Page 79: ...L DI DO DIO IO Link unit mV OverVoltage2L Variable Read 30000 mV Upper limiting value for the voltage in supply ca ble 2 unit mV TemperatureHysteresis Variable Read 2 C Temperature hysteresis unit 0...

Page 80: ...monitoring not enabled 10 3 3 1 4 Reading Port Process Values The OPC UA server provides nodes with process data For example the OPC UA client can read out the value on pin 4 of a port in the Pin4Proc...

Page 81: ...mperature The following table lists device specific calculated measured temperature values Table 51 Device Specific Calculated Measured Temperature Values Node Name Node Class Access Description MeanT...

Page 82: ...t can read out the maximum measured current on pin 1 of a port in the MaxCur rentPin1 node The path to this node is Root Object DeviceSet device name DigitalConnector PortXX Statistics Current Tempera...

Page 83: ...ure on pin 4 since the value was reset unit C Voltage MaxVoltagePin1 Variable Read Maximum voltage on pin 1 since the value was reset unit mV MaxVoltagePin2 Variable Read Maximum voltage on pin 2 sinc...

Page 84: ...n IP ad dress in the format A B C D A 256 B 256 C 256 D IP address as decimal number Example for IP address 192 53 103 108 192 256 53 256 103 256 108 3224725356 10 3 3 1 9 I O Forcing via OPC UA The O...

Page 85: ...The module has an integrated OPC UA server You can communicate with the module with an OPC UA client For text purposes you can for example use UaExpert from Unified Automation GmbH which is available...

Page 86: ...765 1505 100 000 Commissioning 86 Product manual Version 2 0 0 8DIO FLD EI DC 24V 2 0A Figure 26 Add Server Dialog Discovery Tab Default...

Page 87: ...d tab 6 In the Server Information section of the Advanced tab enter the following informa tion in the Endpoint URL field opc tcp IP address 4840 For IP ad dress use the module s IP address 7 In the Au...

Page 88: ...already established a connection to the module Example for an NTP Server The NTP server ptbtime1 ptb de of the Federal Institute of Physics and Metrology in Brunswick Germany with IP address 192 53 10...

Page 89: ...l Version 2 0 0 89 8DIO FLD EI DC 24V 2 0A Figure 28 NtpClientUpdateConfiguration Node 2 In the context menu select Call Figure 29 NtpClientUpdateConfiguration Node Context Menu The Call NtpClientUpda...

Page 90: ...ion enter the number 3224725352 for the IP address of the alternate NTP in the ServerIpAddressFallback field 5 Click Call If the function was successful the output field in the Output Arguments sectio...

Page 91: ...e an OPC UA client You must know the username and password and this user must have permission to execute methods You must have already established a connection to the I O module Step by Step Instructi...

Page 92: ...ll was successful then the Force ID is displayed and 0 appears under Status The FLD LED on the I O module flashes at a rate of 1 Hz Figure 33 GetForcingID Method Successful If the method call was not...

Page 93: ...lationPin4 method simulates the input value of pin 4 of one or more ports Requirements You must have an OPC UA client You must know the username and password and this user must have permission to exec...

Page 94: ...s Description of the Input Arguments Table 56 Input Arguments of the InputSimulationPin Method Input Arguments Description Force ID Here the OPC UA client must use the Force ID that the OPC UA client...

Page 95: ...e input value of ports X01 and X03 to 1 Description of the Output Arguments Table 57 Output Arguments of the InputSimulationPin Method Output Arguments Description Status and Message 0 Forcing digital...

Page 96: ...s Description of the Input Arguments Table 58 Input Arguments of the InputSimulationPin Method Input Arguments Description Force ID Here the OPC UA client must use the Force ID that the OPC UA client...

Page 97: ...the InputSimulationPin Method Output Arguments Description Status and Message 0 Forcing digital outputs successful 1 Forcing digital outputs failed 10 3 3 1 10 5 Forcing Digital Outputs The OutputPin4...

Page 98: ...he Force ID that the OPC UA client had received after the GetForcingID method was called Force Mask Ports for which forcing should be enabled Bit mask and port assignment Bit 0 port X01 Bit 1 port X02...

Page 99: ...ssage 0 Forcing digital outputs successful 1 Forcing digital outputs failed 10 3 3 1 10 6 Disabling Forcing Requirements You must have an OPC UA client You must know the username and password and this...

Page 100: ...rcingID method was called Description of the Output Arguments Table 63 Output Arguments of the DisableForcing Method Output Arguments Description Status and Message 0 Forcing IO Link successful 1 Forc...

Page 101: ...No 2L supply voltage System Status The SYS LED indicates the status of the system product Table 65 System Status LED Color State Description SYS system status Duo LED yellow green Green On System stat...

Page 102: ...urns red for about 250 ms and then lights up green again and contin ues to do so until the test is completed NS LED lights up green for about 250 ms turns red for about 250 ms and then goes out and re...

Page 103: ...NS LED is not permanently reset to green until all Exclusive Owner connections whose time limits were exceeded are reestablished Red On Duplicate IP The module has detected that its IP address is alre...

Page 104: ...taneously red and green yellow On Status of digital input output 1 Off Off Status of digital input output 0 red On Overload short circuit pin 4 and pin 3 red Flashing 1 Hz Overload sensor supply short...

Page 105: ...ady exists An attempt was made to create an instance of an existing object 14 0x0E Attribute cannot be adjusted An attempt was made to modify a fixed attribute 15 0x0F Rights violation The rights or p...

Page 106: ...if none of the general error codes can be used 32 0x20 Invalid parameter A parameter in the request is invalid because it does not meet the requirements of the CIP specification and or an application...

Page 107: ...sion 2 0 0 107 8DIO FLD EI DC 24V 2 0A CIP Status Description 43 0x2B 207 0xCF Reserved Reserved for future extensions of the CIP standard 208 0xD0 255 0xFF Reserved for object classes and service err...

Page 108: ...on the procedure in 8 Resetsetting the Module to the Factory Settings 69 12 2 Updating Firmware The firmware of the module can be updated Use the WAGO I O Field Webserver for this purpose You need the...

Page 109: ...nd electronic equipment and enables sus tainable and efficient use of resources Observe the national and local regulations for the disposal of electrical and electronic equipment lithium ion batteries...

Page 110: ...s are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio fre quency e...

Page 111: ...sing serves the acquisition and output of data via sensors and actuators for the industrial control technology The integrated Blue tooth interface of the product allows the parameterization operation...

Page 112: ...5 30 210 mm WideLine W H D 60 30 210 mm Temperature Ranges Table 77 Temperature Ranges Ambient temperature operation 25 C 70 C Ambient temperature storage 40 C 80 C Maximum temperature change 3 K min...

Page 113: ...tal Illumination Interface Alliance DiiA EtherCAT is a registered trademark and patented technology licensed by Beckhoff Automation GmbH Germany ETHERNET IP is a registered trademark of the Open Devic...

Page 114: ...ut Process Data 25 Table 20 Process Data of the Digital Inputs Port Based Assignment 25 Table 21 Process Data of the Digital Inputs Pin Based Assignment 26 Table 22 Output Process Data 26 Table 23 Pro...

Page 115: ...ated Measured Current Values 81 Table 51 Device Specific Calculated Measured Temperature Values 81 Table 52 Device Specific Calculated Measured Voltage Values 81 Table 53 Port Specific Diagnostics 82...

Page 116: ...of Tables 116 Product manual Version 2 0 0 8DIO FLD EI DC 24V 2 0A Table 74 Error Codes CIP Status 104 Table 75 WEEE Mark 109 Table 76 Bluetooth Transmitter 111 Table 77 Temperature Ranges 112 Table...

Page 117: ...igure 15 Port XX Menu Item Configuration Tab 64 Figure 16 Settings Menu Item Device Configuration Tab Example View 65 Figure 17 Settings Menu Item Maintenance Information Tab Example View 66 Figure 18...

Page 118: ...765 1505 100 000 List of Figures 118 Product manual Version 2 0 0 8DIO FLD EI DC 24V 2 0A Figure 36 InputSimulationPin4 Method 96 Figure 37 OutputPin4 Method 98 Figure 38 DisableForcing Method 100...

Page 119: ...765 1505 100 000 List of Figures Product manual Version 2 0 0 119 8DIO FLD EI DC 24V 2 0A...

Page 120: ...gs videos and other WAGO media are subject to copyright Distri bution or modification of the contents of these pages and videos is prohibited Furthermore the content may neither be copied nor made ava...