8DIO FLD EI DC 24V 2.0A
No.
Parametername
Value Range
Default
Description
95
Bluetooth timeout
6 ... 59 [s]
30
Switch-off time of the Bluetooth
®
interface if
not used;
a new Bluetooth
®
connection can be estab-
lished by an optical signal after the Blue-
tooth
®
interface is reactivated.
The unit for the switch-off time is seconds.
Entering 0 is not allowed, since the Blue-
tooth
®
interface must always switch off after
the switch-off time elapses.
96
Reserved
0
0
–
Parameters 100 to 129
Parameters 100 and 101 configure port X01.
Parameters 104 and 105 configure port X02.
...
Parameters 128 and 129 configure port X08.
Table 33: Port Parameters
No.
Parametername
Value Range
Default
Description
100,
104, ...
DIO port X01/X02/...
– pin 4 mode
0: Normally open
0
Pin 4 is a digital input. The input signal is
not inverted.
1: Normally closed
Pin 4 is a digital input. The input signal is
inverted.
2: Output
Pin 4 is a digital output.
3: Static On
Pin 4 is a digital output and switched on
(+24 VDC).
101,
105, ...
DIO port X01/X02/...
– pin 4 input filter
0: Deactivated
0
No filter active for detecting a signal change
of the pin 4 digital input signal.
3: 3 ms filter time
Filter time setting for detecting a signal
change of the pin 4 digital input signal. The
filter time is the amount of time the signal
must be present in order for a signal
change to be detected.
15: 15 ms filter time
20: 20 ms filter time