WAGO-I/O-SYSTEM 750
Diagnostics 109
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
9.2
Errors and Error Types
Table 48: Errors and Error Types
Error
Error Type
Coding
Acknowledge-
ment
Wire break
Channel error
0x0290
Module-internal/
Module-external
Overload
0x0297
Module -external
Overflow
0x0296
Module-internal/
Module-external
Underflow
0x0291
Module-internal/
Module-external
Internal error
0x0280
Module-internal/
Module-external
Overrange 1
Channel error
(warning)
0x0294
-
Overrange 2
0x0295
Underrange 1
0x0292
Underrange 2
0x0293
Discrepancy time
exceeded
Channel pair
error
0x021E
Module-internal/
Module-external
Overload sensor supply
Module error
0x0233
Module-external
Undervoltage field supply
0x0202
Module-external
Overvoltage field supply
0x0230
Module-external
Overtemperature (with
passivation)
0x0205
Module-external
Overtemperature
(warning)
0x0232
-
Safety-related shutdown
0x0219
Firmware update required
0x0231
Invalid/missing
iParameters
0x0200
Differing F_Dest_Add
Configuration/co
mmunication
error
0x0040
-
Invalid F_Dest_Add
0x0041
Invalid F_Source_Add
0x0042
Invalid F_WD_Time
0x0043
Non-supported F-SIL
0x0044
Incorrect F-CRC length
0x0045
Incorrect F-Par version
0x0046
Invalid F-CRC1
0x0047
Inconsistent F-Parameters
(incorrect iPar-CRC)
Configuration/co
mmunication
0x004B
-