268 Run-time System CODESYS 2.3
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
2.
Generate a start page for the visualization. Right-click the “Visualization”
folder in the “Visualization” tab. Select
Add object
... from the contextual
menu. The “New visualization” dialog box opens.
Figure 103: Creating the PLC_VISU Starting Visualization
3.
In the “New visualization” dialog window, enter the name
PLC_VISU
for the
start visualization. This page is then displayed as the start page upon
system startup.
4.
Activate the CODESYS Web server in the WBM on the “Ports and Services
– CODESYS Services” page in the “CODESYS Webserver” group.
5.
Activate the http service in the WBM on the “Ports and Services – Network
Services” page in the “HTTP” group.
If you transfer the PLC program to the controller (
Online > Login
) and start the
program (
Online > Start
), enter one of the following lines in the address line of
the Web browser for online visualization:
-
“https://<IP address of the controller>/webvisu”, preferred method (http can
also be used instead of https)
-
“https://<IP address of the controller>”, if the default Web server in the
WBM has been set to“WebVisu” (http can also be used instead of https)
-
“http://<IP address of the controller>:8080/webvisu.htm”
You can also have Web visualization displayed via the WBM (see Section
“`CODESYS - WebVisu´” Page).