background image

 

 

750-634 [Incremental Encoder Interface] 

  

  9 

  

Display 

Elements  

WAGO-I/O-SYSTEM 750 
I/O Modules 

2.1.1.3 Display 

Elements 

LED  Denotation 

State 

Function

 

on 

is equivalent to U > 15 V 


green 

Quadrature

Input 

off 

is equivalent to U < 5 V 

on 

is equivalent to U > 15 V 


green 

Quadrature

Input 

off 

is equivalent to U < 5 V 

on 

is equivalent to U > 15 V 

13 14

C
D

B

A

C

B

A

 

Fig. 2.1.1-2: Display 
Elements     

g063402x

 


green 

Zero 

reference 

Input 

off 

is equivalent to U < 5 V 

 

2.1.1.4 Schematic 

Diagram 

A

B

C

0V

24V

1

2

3

4

5

6

7

8

750-634

A
B
C

A,B,C

0V

24V

10nF

270pF

shield (screen)

Logic

 

Fig. 2.1.1-3:Incremental Encoder Interface 750-634 

g063401e 

Summary of Contents for 750-634

Page 1: ...Fieldbus Independent I O Modules Incremental Encoder Interface 750 634 Manual Version 1 0 3...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Special Modules 7 2 1 1 750 634 Incremental Encoder Interface 7 2 1 1 1 View 7 2 1 1 2 Descr...

Page 4: ...ufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual...

Page 5: ...ation ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient...

Page 6: ...ESD information is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be as...

Page 7: ...Description The I O module is an interface for the direct connection of any 24 V incremental encoders A 16 bit counter with quadrature decoder and a 16 bit latch for the zero pulse can be read set or...

Page 8: ...erived from adjacent I O modules or from a supply module The supply voltage for the field side is made automatically through the individual I O modules by means of power jumper contacts Attention This...

Page 9: ...valent to U 5 V on is equivalent to U 15 V B green Quadrature Input off is equivalent to U 5 V on is equivalent to U 15 V 13 14 C D B A C B A Fig 2 1 1 2 Display Elements g063402x C green Zero referen...

Page 10: ...m supply Bit width 2 x 16 bits data 1 x 8 bits Control Status 1 x 8 bits reserved Dimensions mm W x H x L 12 x 64 x 100 from upper edge of DIN 35 rail Weight ca 60 g Standards and Regulations cf Chapt...

Page 11: ...logical channel The data sent and received is stored in 2 output bytes D0 D1 and 5 input bytes D0 D1 D2 D3 D4 The output bytes D2 D4 are reserved and without function One control byte C and one statu...

Page 12: ...ER FLOW In the event of an overflow 65535 to 0 of the 16 Bit counter this bit will be set A reset will take place if the counter exceeds one third of the measuring range 21845 to 21846 or as soon as a...

Page 13: ...750 634 Incremental Encoder Interface 13 Process Image WAGO I O SYSTEM 750 I O Modules...

Page 14: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...