background image

10  •

 

750-554 [2 AO 4-20 mA] 
Technical Data 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

2.1.1.6 Technical 

Data 

Module Specific Data 

Number of outputs 

Voltage via power jumper contacts 

DC 24 V (-25% ... +30%) 

Current consumption  

typ

. (internal) 

70 mA 

Signal current 

4 mA... 20 mA 

Load impedance 

< 600 

 

Linearity 

±

 10 µA 

Resolution 12 

Bit 

Conversion time

 

approx. 2 ms 

Measuring error 

25°C

 

<

±

 0.1 % of the full scale value 

Temperature coefficient 

<

±

 0.015 % / K of the full scale value 

Isolation 

500 V (Field/System) 

Bit width 

2 x 16 bits data 
2 x 8 bits control/status (option) 

Dimensions (mm) W x H x L 

12 x 64* x 100 
* from upper edge of 35 DIN rail 

Weight 

ca. 55 g 

Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual) 

EMC-Immunity to interference (CE)  acc. to EN 50082-2 (96) 

EMC-Emission of interference (CE) 

acc. to EN 50081-1 (93) 

EMC-Immunity to interference 
(Ship building) 

acc. to Germanischer Lloyd (97) 

EMC-Emission of interference 
(Ship building) 

acc. to Germanischer Lloyd (97) 

Summary of Contents for 750-554

Page 1: ...Fieldbus Independent I O Modules 2 AO 4 20 mA 750 554 Manual Version 1 0 3...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...e 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Analog Output Modules 7 2 1 1 750 554 2 AO 4 20 mA 7 2 1 1 1 View 7 2 1 1 2 Variations 7 2 1 1 3 Description...

Page 4: ...ufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual...

Page 5: ...D Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of...

Page 6: ...e ESD information is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be...

Page 7: ...eistungskontakte Datenkontakte Funktion AO 2 24V 0V Funktion AO 1 AO 1 Schirm Schirm Fig 2 1 1 1 2 Channel Analog Output Module 750 554 g055400e 2 1 1 2 Variations Item No Designation Description 750...

Page 8: ...nction LED Any configuration of the output modules is possible when designing the fieldbus node Grouping of module types is not necessary The voltage supply is done via the field supply The field side...

Page 9: ...ouble free internal data bus communication off No operational readiness or the internal data bus communication is interrupted 13 14 C D B A C A Fig 2 1 1 2 Display elements g055202x C green 2 Function...

Page 10: ...scale value Temperature coefficient 0 015 K of the full scale value Isolation 500 V Field System Bit width 2 x 16 bits data 2 x 8 bits control status option Dimensions mm W x H x L 12 x 64 x 100 from...

Page 11: ...AGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Tools and Docs Item No 0888 0412 or in the internet under www wago com Documentation WAGO I O SYSTEM 750 System Description 2 1 1 7 Proc...

Page 12: ...1 0000 0000 0000 0x7000 28672 0x00 20 0111 1111 1111 1111 0x7FFF 32767 0x00 2 1 1 7 2 Special Formats To digitalize the output value the variation 750 554 000 200 uses a data format adapted to the S5...

Page 13: ...750 554 2 AO 4 20 mA 13 Process Image WAGO I O SYSTEM 750 I O Modules...

Page 14: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: