WAGO-I/O-SYSTEM 750
Commissioning 85
750-450 4 AI RTD
Manual
Version 1.2.0
Table 66: Menu Item "Scaling" > "Channel 1 …4"
Option
Description
Line resistance
Line resistance offset Here, specify the line resistance that is to be applied when calculating the
measured values.
Scaling settings
Activate manufacturer
scaling
Manufacturer scaling is active. Manufacturer scaling is being
applied. This means that you cannot input the individual gain
multiplier, gain divisor or offset.
Manufacturer scaling deactivated.
Activate user scaling
User-defined scaling is active. By activating this setting you can
also specify the individual gain multiplier and offset.
User-defined scaling deactivated.
Offset
The offset value shifts the zero point of the non-scaled process value
(shift along the Y axis).
Gain multiplier
The gain multiplier changes the slope factor for the non-scaled process
value.
Gain divisor
The gain divisor determines the resolution for the gain multiplier. The
factory default setting for the gain divisor is 256.
Process value
The process value is the resistance/temperature value that is yielded from
the temperature or resistance measurement. Depending on the set sensor
type, the process value is given in °C or Ohm.
The measured values calculated by the I/O module can also be scaled by the
user as an option. A linear equation is applied to the sensor-specific variable for
this:
• y2 = ((y1 × Reg40) / Reg41) + Reg39
With:
• y2= scaled process value
• y1= unscaled process value
• Reg40= gain multiplier
• Reg41= gain divisor = factory default setting 256
• Reg39= scaling offset
The values gain multiplier and scaling offset are required to perform user-defined
scaling. When these two factors are input, a scaled process value is yielded as
the result. The gain divisor determines the resolution for the gain multiplier. The
factory default setting for the gain devisor is 256.