8 •
750-433 [4 DI DC 24 V 0.2 ms / 2- conductor]
Display
Elements
WAGO-I/O-SYSTEM
750
I/O
Modules
Any configuration of the input modules is possible when designing the
fieldbus node. Grouping of module types is not necessary.
The field side supply voltage of 24V for the input module is derived from
adjacent I/O modules or from a supply module
.
The supply voltage for the
field side is made automatically through the individual I/O modules by means
of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The digital input module 750-433 can be used with all couplers/controllers of
the WAGO-I/O-SYSTEM 750.
2.1.1.3 Display
Elements
LED
Channel Designation State Function
off
Input DI 1: Signal voltage (0)
A
green
1 Status
DI 1
on
Input DI 1: Signal voltage (1)
off
Input DI 2: Signal voltage (0)
C
green
2 Status
DI 2
on
Input DI 2: Signal voltage (1)
off
Input DI 3: Signal voltage (0)
B
green
3 Status
DI 3
on
Input DI 3: Signal voltage (1)
off
Input DI 4: Signal voltage (0)
13 14
C
D
B
A
C
A
Fig. 2.1.1-2: Display
Elements
g041402x
D
green
4 Status
DI 4
on
Input DI 4: Signal voltage (1)