22
Device Description
WAGO-I/O-SYSTEM 750
750-402 4DI 24V DC 3.0ms
Manual
Version 1.1.0
Pos : 45.1 /All e Seri en ( Allgemei ne Module)/Ü bers chrift en f ür alle Serien/G erätebesc hreibung/Ansc hlus st echni k - Ü berschrif t 3 @ 17\ mod_1380123271324_21.doc x @ 132788 @ 3 @ 1
3.5.5
Connection Type
Pos : 45.2 /Serie 750 (WAGO-I/ O-SYST EM)/ Ger ätebesc hrei bung/T echnisc he Daten/T ec hnische D at en Verdr ahtungs ebene CC - 0,08 bis 2, 5mm2 @ 17\ mod_1380121238809_21. doc x @ 132780 @ @ 1
Table 8: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² … 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in
Pos : 45.3 /Serie 750 (WAGO-I/ O-SYST EM)/ Ger ätebesc hrei bung/T echnisc he Daten/ Ansc hluss tec hni k/T ec hnisc he D at en Leist ungs kont akt e (Messer/ Feder) @ 17\ mod_1380123464149_21. doc x @ 132791 @ @ 1
Table 9: Technical Data – Power Jumper Contacts
Power jumper contacts
blade/spring contact, self-cleaning
Voltage drop at I
max.
< 1 V/64 modules
Pos : 45.4 /Serie 750 (WAGO-I/ O-SYST EM)/ Ger ätebesc hrei bung/T echnisc he Daten/ Ansc hluss tec hni k/T ec hnisc he D at en Kl emmenbus @ 17\ mod_1380123495844_21. doc x @ 132794 @ @ 1
Table 10: Technical Data – Internal Bus
Data contacts
slide contact, hard gold plated 1.5 µm,
self-cleaning
Pos : 46 /Serie 750 ( WAGO-I/ O-SYST EM)/ Ger ät ebesc hrei bung/T echnisc he Daten/T ec hnische D at en Kli matisc he U mwel tbedi ngungen m. er w. Tempber eich; 0.. .55°C /-20.. .+60°C/- 25...+ 85°C @ 5\ mod_1247658089120_21. doc x @ 37606 @ 3 @ 1
3.5.6
Climatic Environmental Conditions
Table 11: Technical Data – Climatic environmental conditions
Operating temperature range
0 °C … 55 °C
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
-20 °C … +60 °C
Storage temperature range
-25 °C … +85 °C
Storage temperature range for
components with extended
temperature range (750-xxx/025-xxx)
-40 °C … +85 °C
Relative humidity
max. 5 % … 95 % without condensation
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75%
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are
taken, which are used in an environment
involving:
– dust, caustic vapors or gases
– ionizing radiation
Pos : 47 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1