8.6.3
Standard Modul Parameters
Certain module properties of some I/O modules can be parameterized during
configuration. At present, this only applies to the output modules whose substitute
value behavior can be set independent of the modules used.
Table 44: Default Module Parameters
Attribute name
Attribute value
Description
Substitute value
behavior of the outputs
If the PROFINET IO Controller does not supply
valid output data for the module or the group of
modules, then
according to the
device settings*)
•
the set strategy of the station substitute applies
(IO device).
according to the
referenced module
settings*)1)
•
the set strategy of the reference digital module
applies by which the output data has been
reserved. These settings apply to digital output
modules without process data. These are
characterized by a “*” after the item number.
Output states are set
to 0.
•
all outputs are reset.
Outputs maintain the
last valid value.
•
all outputs maintain the last valid value.
Outputs take their
substitute states.
•
all outputs switch to their configured substitute
values.
*)
Default setting
1)
Digital modules whose process data has been allocated to their previous
slots implicitly take the substitute value strategy of the module on the
slot allocated.