96
Commissioning
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Pos: 69.5 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbusknoten i n Betrieb nehmen/PROFINET IO/Par ametri erung (750- 370) @ 23\mod_1433231032749_21.docx @ 183216 @ 234444443 @ 1
8.6
Parameterization
The configuration is used to set the parameters (attributes) for the fieldbus coupler
as a station proxy (DAP) and for the I/O modules based on the device description
(GSD). The individual parameters are set via selectable textual descriptions.
8.6.1
Parameterization of the Station Proxy (DAP)
The following list provides an overview of configurable attributes for the station
proxy and descriptions of the individual parameters are listed in the subsequent
section.
Table 37: Parameterization – Overview of Attributes for the Station Proxy (DAP)
Attributes for the station proxy (DAP)
-
Restart on K-Bus failure
-
Internal data bus extension
-
Diagnostics of external module/channel errors
-
Process data representation
-
Response to PROFINET IO failure
-
Response to K-Bus failure
8.6.1.1 Restart on K-Bus Failure
Table 38: Parameterization DAP – Attribute Restart on K-Bus Failure
Attribute Name
Attribute Value
Description
Restart on K-Bus
failure
After a fault, for example a missing end module, a
restart of the internal data bus will be initiated, if
POWER ON
RESET
*)
•
an interruption of the fieldbus controller
supply.
AUTORESET
•
immediately after disappearing of the internal
bus fault.
*)
Default settings
8.6.1.2 Internal Data Bus Extension
Table 39: Parameterization DAP – Attribute Internal Data Bus Extension
Attribute Name
Attribute Value
Description
Internal data bus
extension
The use of the internal data bus extension
EEPROM-setting is
used
*)
•
depends on the setting in EEPROMs are made
according to the unlock value saved in the
EEPROM.
is not used
•
is excluded.
is used
•
is possible.
*)
Default settings