WAGO I/O SYSTEM 750 XTR
Commissioning
89
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
8.4
PI Configuration
8.4.1
Application Example
The physical configuration of the node is determined by:
-
The configuration of the planned I/O modules with the DP fieldbus coupler,
-
The slot properties in the respective module parameters and
-
The “Startup if expected and actual configuration differ” parameter set as
part of the station parameterization.
The following application examples show the configuration of the node based on
the parameter selected during the station parameterization.
Table 40: Planned station configuration
Slot
I/O
module
Channel
DP module
DP identification
Slot properties
DP master
Pro-
jec-
ted
physical
Module
is physi-
cally
Diagnostics
is mapped
into the
Input-PI
I-PI
O-PI
(set-
point ≠
actual)
!(set-
point ≠
actual)
1
1
1
750-333
-
750-333 No process data channel
-
-
-
-
2
2
2
75x-1405
0
75x-1405 16DI/24V DC
[0x11]
Plug fitted
-
I 12.0
-
1
I 12.1
-
2
I 12.2
-
…
…
…
14
I 13.6
-
15
I 13.7
-
3
3
3
75x-430
0
75x-430 8DI/24V DC/3.0ms
[0x10]
Plug fitted
-
I 14.0
-
1
I 14.1
-
2
I 14.2
-
…
…
…
6
I 14.6
-
7
I 14.7
-
4
4
4
75x-457
0
75x-457 4AI/+/-10V/SE
[0x53]
Plug fitted
-
IW 16
-
1
IW 18
-
2
IW 20
-
3
IW 22
-
5
5
5
75x-402
0
75x-402 4DI/24V DC/3.0ms
[0x10]
Plug fitted
-
I 15.0
-
1
I 15.1
-
2
I 15.2
-
3
I 15.3
-
6
6
-
75x-461
0
75x-461 2AI/RTD
[0x51]
(optional)
not plug
fitted
-
IW 24
-
1
IW 26
-
7
7
-
75x-425
0
*75x-425 2DI/24V DC/NAMUR
[0x00]
(optional)
not plug
fitted
released
I 15.4
-
1
I 15.5
-
DIA 0
I 15.6
-
DIA 1
I 15.7
-
8
8
6
75x-610
-
750-610 P-Einsp. 24V DC/DIA
[0x00]
fitted
-
-
-
9
9
7
75x-1504
0
75x-1504 16DO/24V DC/0.5A
[0x21]
fitted
-
-
Q 8.0
1
-
Q 8.1
2
-
Q 8.1
…
…
…
14
-
Q 9.6
15
-
Q 9.7