WAGO I/O SYSTEM 750 XTR
Appendix 215
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
12.3.2.9 Parameters of the Serial Interface
The table shows the parameterization properties of the serial interface with partial
asynchronous diagnostic properties, but without individual parameters.
Table 168: Parameters of the serial interface (SER)
SER
Representatives of SER:
75x-650, 75x-651, 75x-653, 75x-654
Parameterization data length in bytes
Standard parameterization
Structured parameterization
4
8
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero or filtered by the
fieldbus coupler.
Plugged
*)
•
processed by the I/O module.
Diagnosis
1)
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
*)
Default settings
1)
Does not apply to 75x-654
The table shows the parameterization properties of the serial interfaces with