WAGO I/O SYSTEM 750 XTR
Diagnostics 119
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 68: Status messages
Byte-
off-
set
Information
Meaning
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
0
0
0
0
1
0
0
0
Header byte
Alarm or
status
Length of the status message incl.
header
1
1
0
0
0
0
0
0
1
Message type
Sta-
tus
Status type = 1 (status message)
2
Slot
Slot of the reporting I/O module
(value range 2 - 64)
3
0
0
0
0
0
0
0
0
Status specification
Status
differentiati
on = 00
B
(none)
4
Value (LB)
Error or status value (LB), due to compatibility,
available for earlier firmware versions
5
Channel information
Type of
channel:
00B: Input
01B: Output
10B: Module
11B: reserved
Channel number (value range 0 - 63)
4
Value (HB)
5
Error or status value (HB)
4
Value (LB)
5
Error or status value (LB)
9.3.8
PROFIsafe Parameterization Fault
Table 69: PROFIsafe parameterization fault
PROFIsafe parameterization fault
Item number
Fault number
Meaning
750-660/000-001
750-665/000-001
753-662/000-002
753-667/000-002
75x-661/000-003
75x-662/000-003
75x-666/000-003
75x-667/000-003
64dez (0x0040)
Differing F_Dest_Add
65dez (0x0041)
Invalid F_Dest_Add
66dez (0x0042)
Invalid F_Source_Add
67dez (0x0043)
Invalid F_WD_Time
68dez (0x0044)
Not supported F_SIL
69dez (0x0045)
Incorrect F_CRC_Length
70dez (0x0046)
Incorrect F_Par_Version
71dez (0x0047)
Invalid F_CRC1
75x-661/000-003
75x-662/000-003
75x-666/000-003
75x-667/000-003
73dez (0x0049)
Error when uploading the individual parameters
74dez (0x004A)
Error when downloading the individual parameters
75dez (0x004B)
Invalid individual parameters from iPar server
76dez (0x004C)
Not supported F_Block_ID
See PROFIsafe manuals or the GSD file for more information about the error
messages.