10.2.53 Type 54 - Peak Time Counter type 2
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0633#04
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Toggle Bit
I
0
1
BOOL
Status up/down
I
0
2
BOOL
Status out
I
0
5
BOOL
Confirmation start counting
I
0
6
BOOL
General Error Bit
I
2
WORD
Actual count value Low Word
I
4
WORD
Actual count value High Word
Q
0
2
BOOL
Control Out
Q
0
5
BOOL
Control bit start count pulse acquisition
10.2.54 Type 55 - LON-FTT Interface
Occupied input process image [(channel x) bits]:
(1x) 192
Occupied output process image [(channel x) bits]: (1x) 192
Items that use this mapping type:
0753-0648
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
First Byte of 24
Q
0
0
BYTE
First Byte of 24
10.2.55 Type 56 - 16 Bytes Generic IN/OUT
Occupied input process image [(channel x) bits]:
(1x) 128
Occupied output process image [(channel x) bits]: (1x) 128
Items that use this mapping type:
0750-0657#16, 0750-0658#16
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
First Byte of 16
Q
0
0
BYTE
First Byte of 16